| 09/30/2026 | R:ROUGH ELECTRICAL | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 9/29/2026 2:15:58 PM
9/29/2026 2:15 PM Kevin McNeill
Contact Name: Kevin McNeill
Site Address: 312 S LARKSPUR DR
Phone: 3034761519
e-Mail: Kevin.m.mcneill@gmail.com
9/30/2026 10:22:27 AM
Rough electrical inspection approved
Notes
5 junction boxes to be accessible at final.2 in West kitchen wall lower cabinets. 1 north wall upper cabinet. 2 in east wall lower and upper cabinet
Verify all circuits that's have been extended or altered have arch fault gfci protection.
Verify counter top receptacle spacing requirements at final
All new lighting locations in living and dining require arch fault protection
1 receptacle above fire place requires arch fault protection
Verify new 80amp sub panel at final, along with new speed oven fish through floor joist stubbed outside located by back door surface mounted 1 inch EMT conduit to subpanel
|
|
| 09/30/2026 | R:ROUGH FRAME | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 9/29/2026 2:15:58 PM
9/29/2026 2:15 PM Kevin McNeill
Contact Name: Kevin McNeill
Site Address: 312 S LARKSPUR DR
Phone: 3034761519
e-Mail: Kevin.m.mcneill@gmail.com
9/30/2026 2:53:05 PM
Approved
|
|
| 10/27/2026 | R:FINAL BUILDING | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 10/24/2026 4:29:47 PM
10/24/2026 4:29 PM Kevin McNeill
Contact Name: Kevin McNeill
Site Address: 312 S LARKSPUR DR
Phone: 3034761519
e-Mail: Kevin.m.mcneill@gmail.com
10/27/2026 12:50:05 PM
Final building inspection approved
Plumbing, mechanical, electrical approved
Notes
All new kitchen circuit are work fault GFI protected in panel
All circuits that have been extended or altered or arc fault protected in panel
New kitchen exhaust hood is under 400 CFM
|
|