| 10/20/2026 | R:ROUGH FRAME | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 10/19/2026 1:25:49 PM
10/19/2026 1:25 PM A2Z BUILDERS
**Requesting Mechanical** Site Contact: Barak (720) 346-4166
Contact Name: A2Z BUILDERS
Site Address: 2833 ECHO PARK DR
Phone: 7207980700
e-Mail: PERMITS@A2ZBUILDERS.COM
10/20/2026 10:08:31 AM
Rough frame inspection not approved
1. Missing fire blocking horizontal in walls every 10 feet required floor to ceiling
2. Missing fire blocking in soffit every 10 feet where mechanical duct is installed
Reschedule inspection when corrections are completed
Notes
Aav under bathroom sink to be accessible at final, plumbing clean to be accessible in basement living west wall, plumbing clean out to in basement bedroom at final west wall
Under stair protection required at final
Fire blocking from unfinished area to finish area required at final
Shower pan inspection required
Have inspection card and approved stamp plans at next inspection
|
|
| 10/20/2026 | R:INSULATION | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 10/19/2026 1:25:50 PM
10/19/2026 1:25 PM A2Z BUILDERS
**Requesting Mechanical** Site Contact: Barak (720) 346-4166
Contact Name: A2Z BUILDERS
Site Address: 2833 ECHO PARK DR
Phone: 7207980700
e-Mail: PERMITS@A2ZBUILDERS.COM
10/20/2026 10:08:34 AM
Insulation inspection approved existing foundation insulation install installed by previous builder
|
|
| 10/20/2026 | R:GROUND PLUMBING | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 10/19/2026 1:25:50 PM
10/19/2026 1:25 PM A2Z BUILDERS
**Requesting Mechanical** Site Contact: Barak (720) 346-4166
Contact Name: A2Z BUILDERS
Site Address: 2833 ECHO PARK DR
Phone: 7207980700
e-Mail: PERMITS@A2ZBUILDERS.COM
10/20/2026 10:08:37 AM
Ground plumbing inspection approved
Note
Aav to be accessible below sink at final
|
|
| 10/23/2026 | R:RE_ROUGH FRAME | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 10/22/2026 2:43:50 PM
10/22/2026 2:43 PM A2Z BUILDERS
Site Contact: Ariel (720) 431-9923
Contact Name: A2Z BUILDERS
Site Address: 2833 ECHO PARK DR
Phone: 7207980700
e-Mail: PERMITS@A2ZBUILDERS.COM
10/23/2026 11:10:49 AM
Rough frame inspection approved
All corrections have been completed
Electrical, plumbing, mechanical, good
Schedule shower pan inspection when ready
Notes
Aav under bathroom sink to be accessible at final, plumbing clean to be accessible in basement living west wall, plumbing clean out to in basement bedroom at final west wall
Under stair protection required at final
Fire blocking from unfinished area to finish area required at final
Have inspection card and approved stamp plans at next inspection
|
|
| 10/23/2026 | R:INSULATION | SHAWN VALENZUELA | CANCEL | eTRAKiT Inspection Request | 10/22/2026 2:43:50 PM
10/22/2026 2:43 PM A2Z BUILDERS
Site Contact: Ariel (720) 431-9923
Contact Name: A2Z BUILDERS
Site Address: 2833 ECHO PARK DR
Phone: 7207980700
e-Mail: PERMITS@A2ZBUILDERS.COM
10/23/2026 11:10:51 AM
insulation inspection was approved on 10/20/2026
|
|
| 11/04/2026 | R:SHOWER PAN | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 11/3/2026 12:58:23 PM
11/3/2026 12:58 PM A2Z BUILDERS
Site Contact: Josh (720) 408-3477
Contact Name: A2Z BUILDERS
Site Address: 2833 ECHO PARK DR
Phone: 7207980700
e-Mail: PERMITS@A2ZBUILDERS.COM
11/4/2026 11:32:05 AM
PARTIAL-
1) CUSTOM SHOWER PAN- OK PER CODE P2708.1, P2708.2 & P2709.2.1 .
NOTE: SPOKE WITH SUPERINTENDENT FOR PERMIT ON PHONE THAT SHOWER CURB TO BE CHECKED AT BUILDING FINAL FOR COMPLIANCE WITH (P2709 SHOWER RECEPTORS - P2709.1 CONSTRUCTION) AS THE SHOWER PAN & CURB ARE A MONO POUR & WAS NOT DONE AT FIRST SHOWER PAN INSPECTION.
PLEASE RE-SCHEDULE SHOWER PAN INSPECTION IN ADDITION TO BUILD FINAL WHEN READY.
|
|