| 07/27/2026 | R:ROUGH ELECTRICAL | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 7/24/2026 11:48:37 AM
7/24/2026 11:48 AM R&M CONSTRUCTION SERVICES
Contact Name: R&M CONSTRUCTION SERVICES
Site Address: 1590 FAIRFAX CT
Phone: 7203223659
e-Mail: Mark@RMCS5280.com
7/27/2026 9:55:20 AM
Rough electrical inspection not approved
1. No town approved plans on site. Have plans and inspection card on site for next inspection
2. Update countertop receptacle spacing per NEC 2023. Castle rock amendment can only have four receptacles on one small appliance circuit
3. Missing future island power if planning to pull off microwave or dishwasher please have instruction manual on both to verify that circuit is not overloaded
4. Current lighting does not match the plans or has not been installed at this time if changes have been made per plans please update plans and submit to the town of Castle rock.
Recall rough electrical inspection when corrections are made
Note
It appears that a new fireplace has been/being installed at this time of inspection plans do not show new fireplace. This needs to be added to the plans.
|
|
| 07/27/2026 | R:ROUGH FRAME | COLBY RIGGINS | NOT APPROVED | eTRAKiT Inspection Request | 7/24/2026 11:48:37 AM
7/24/2026 11:48 AM R&M CONSTRUCTION SERVICES
Contact Name: R&M CONSTRUCTION SERVICES
Site Address: 1590 FAIRFAX CT
Phone: 7203223659
e-Mail: Mark@RMCS5280.com
7/27/2026 2:50:03 PM
1. Electrical was not approved
2. Missing exhaust fan and fan will be at 400 cfm so you will need make up air added.
3. Remove gas line for the kitchen stove on the plans.
|
|
| 07/27/2026 | R:INSULATION | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 7/24/2026 11:48:38 AM
7/24/2026 11:48 AM R&M CONSTRUCTION SERVICES
Contact Name: R&M CONSTRUCTION SERVICES
Site Address: 1590 FAIRFAX CT
Phone: 7203223659
e-Mail: Mark@RMCS5280.com
7/27/2026 2:50:05 PM
Approved
Insulation was not taken out or added from original.
|
|
| 08/04/2026 | R:ROUGH FRAME | SHAWN VALENZUELA | APPROVED | SEE BIS | 8/3/2026 2:55:45 PM
8/3/2026 2:55 PM R&M CONSTRUCTION SERVICES
Contact Name: R&M CONSTRUCTION SERVICES
Site Address: 1590 FAIRFAX CT
Phone: 7203223659
e-Mail: Mark@RMCS5280.com
8/4/2026 9:42:08 AM
Rough frame inspection approved
Will verify at final inspection exhaust fan is under 400 cfm
|
|
| 08/04/2026 | R:ROUGH ELECTRICAL | SHAWN VALENZUELA | APPROVED | SEE BIS | 8/3/2026 2:55:45 PM
8/3/2026 2:55 PM R&M CONSTRUCTION SERVICES
Contact Name: R&M CONSTRUCTION SERVICES
Site Address: 1590 FAIRFAX CT
Phone: 7203223659
e-Mail: Mark@RMCS5280.com
8/4/2026 9:42:11 AM
Rough electrical inspection approved
Note
Will verify kitchen counter top receptacle spacing at final electrical inspection
Will verify that any electrical circuit that has been extended or altered is brought up to current codes arc fault gfci protection
|
|
| 10/06/2026 | R:FINAL BUILDING | SHAWN VALENZUELA | APPROVED | 7209806501 - COME AFTER 9:15 | 10/5/2026 9:55:01 AM
HOMEOWNER
10/6/2026 10:37:53 AM
Final building inspection approved
Notes
Kitchen exhaust fan is under 400 cfm
|
|