| 06/30/2026 | TRAC:TEMPORARY CONSTRUCTION METER | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 6/29/2026 3:16:28 PM
6/29/2026 3:16 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7196495723
e-Mail: cwagner@kbhome.com
6/30/2026 12:11:08 PM
Temporary construction meter inspection not approved
1. Both wr gfi receptacles in lowest bell box ground ports are damaged/broken
Please recall inspection when corrections are completed
|
|
| 07/02/2026 | TRAC:TEMPORARY CONSTRUCTION METER | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 7/1/2026 9:05:55 AM
7/1/2026 9:05 AM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7196495723
e-Mail: Cwagner@KBHOME.COM
7/2/2026 12:22:03 PM
Temporary construction meter inspection approved
|
|
| 08/12/2026 | TRAC:GROUND PLUMBING | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 8/11/2026 10:14:10 AM
8/11/2026 10:14 AM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
8/12/2026 12:12:25 PM
Approved
|
|
| 08/25/2026 | TRAC:WALL BRACING SHEATHING | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 8/24/2026 12:09:36 PM
8/24/2026 12:09 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
8/25/2026 2:46:43 PM
Approved
|
|
| 08/25/2026 | TRAC:PORCH POST FRONT | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 8/24/2026 12:09:36 PM
8/24/2026 12:09 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
8/25/2026 2:46:46 PM
Approved
|
|
| 08/28/2026 | TRAC:ROUGH DECK | COLBY RIGGINS | NOT APPROVED | eTRAKiT Inspection Request | 8/27/2026 8:18:49 AM
8/27/2026 8:18 AM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
8/28/2026 2:02:12 PM
1. Plans do not call out side headers for patio cover on pg S 3.0.
|
|
| 08/28/2026 | TRAC:POST REAR | COLBY RIGGINS | NOT APPROVED | eTRAKiT Inspection Request | 8/27/2026 8:18:48 AM
8/27/2026 8:18 AM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
8/28/2026 2:02:14 PM
1. Missing second post connections on upper post bases
|
|
| 08/31/2026 | TRAC:REQUEST PRE ROUGH DOC | BUILDING COUNTER | NOT APPROVED | eTRAKiT Inspection Request | 8/28/2026 1:16:49 PM
8/28/2026 1:16 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
8/31/2026 8:35:45 AM
Missing documents.
|
|
| 09/01/2026 | TRAC:WEATHER RESISTIVE BARRIER | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 8/31/2026 7:28:14 PM
8/31/2026 7:28 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/1/2026 12:15:39 PM
Approved
|
|
| 09/01/2026 | TRAC:ROUGH DECK | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 8/31/2026 2:33:46 PM
8/31/2026 2:33 PM KB HOME
Headers for that on a different page. Will cancel if I don’t see them. Thank you.
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/1/2026 12:15:42 PM
Approved
|
|
| 09/01/2026 | TRAC:POST REAR | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 8/31/2026 2:33:46 PM
8/31/2026 2:33 PM KB HOME
Headers for that on a different page. Will cancel if I don’t see them. Thank you.
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/1/2026 12:15:45 PM
Approved
|
|
| 09/02/2026 | TRAC:FIRE RESISTIVE | COLBY RIGGINS | NOT APPROVED | eTRAKiT Inspection Request | 9/1/2026 11:54:13 AM
9/1/2026 11:54 AM KB HOME
Soffit drywall, please
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/2/2026 11:02:11 AM
Soffits ok
1. Missing no burn letter for the basement
|
|
| 09/04/2026 | TRAC:FIRE RESISTIVE | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 9/3/2026 11:54:29 AM
9/3/2026 11:54 AM KB HOME
No burn uploaded. Sorry
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/4/2026 2:56:26 PM
Approved
|
|
| 09/08/2026 | TRAC:REQUEST PRE ROUGH DOC | BUILDING COUNTER | NOT APPROVED | CB | 9/4/2026 9:20:39 AM
9/4/2026 9:20 AM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/8/2026 8:28:03 AM
Missing Excavation or Open Hole inspection report
|
|
| 09/10/2026 | TRAC:REQUEST PRE ROUGH DOC | BUILDING COUNTER | APPROVED | CB | 9/9/2026 2:23:39 PM
9/9/2026 2:23 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
|
|
| 09/11/2026 | TRAC:ROUGH ELECTRICAL | VINCE RAPONE | APPROVED | eTRAKiT Inspection Request | 9/10/2026 1:48:16 PM
9/10/2026 1:48 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/11/2026 11:51:12 AM
Rough electrical approved
|
|
| 09/11/2026 | TRAC:LATH STONE BRICK TIE | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 9/10/2026 9:54:08 PM
9/10/2026 9:54 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/11/2026 12:55:00 PM
Approved
|
|
| 09/11/2026 | TRAC:ROUGH FRAME | COLBY RIGGINS | NOT APPROVED | eTRAKiT Inspection Request | 9/10/2026 1:48:16 PM
9/10/2026 1:48 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/11/2026 12:55:02 PM
1. Garage missing detail B1 sd1 of 3 cs16 at top middle and bottom strapped around the sides and nailing 8" of staggered
2. FHA plate needed at exterior rear wall at metal ducting
3. Holes in floor joists at north main section at exterior wall are to large, please consult and engineer
4. Water not on test at front upper elevation bathroom
5. House not dried in at bathrooms
7. Toilets flanges missing screws
8. Shim 2x4s at upper stairs at the top plate
9. Provide stud at lvl going into the basement at the garage wall
10. Weld shims
11. Consult engineer in basement at 3 in plumbing pipe the floor joist was cut at the top of the joist and hole is to large
13. Mechanical ducting at basement top plates need an fha plates at north side
14. Anchor bolts in the basement are loose
Gas ok
Gas appliances furnace, water heater
Need water
Dwv ok
|
|
| 09/15/2026 | TRAC:RE ROUGH FRAME | VINCE RAPONE | CANCEL | eTRAKiT Inspection Request | 9/14/2026 2:31:01 PM
9/14/2026 2:31 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/15/2026 9:35:43 AM
Cancel per superintendent
Reschedule when ready
|
|
| 09/16/2026 | TRAC:RE ROUGH FRAME | COLBY RIGGINS | NOT APPROVED | eTRAKiT Inspection Request | 9/15/2026 12:37:21 PM
9/15/2026 12:37 PM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/16/2026 9:54:01 AM
Inspector VIRA changed the inspection assignment from VIRA to CORI
9/16/2026 2:57:07 PM
4. Water not on test at front upper elevation bathroom
Gas ok
Gas appliances furnace, water heater
Need water
Dwv ok
|
|
| 09/18/2026 | TRAC:RE ROUGH FRAME | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 9/17/2026 9:40:30 AM
9/17/2026 9:40 AM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/18/2026 1:45:49 PM
Approved
|
|
| 09/18/2026 | TRAC:INSULATION | COLBY RIGGINS | APPROVED | eTRAKiT Inspection Request | 9/17/2026 9:40:30 AM
9/17/2026 9:40 AM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/18/2026 1:45:51 PM
Approved
|
|
| 09/24/2026 | TRAC:SHEAR WALL DRYWALL | VINCE RAPONE | APPROVED | eTRAKiT Inspection Request | 9/23/2026 9:42:31 AM
9/23/2026 9:42 AM KB HOME
Contact Name: KB HOME
Site Address: 2024 PEACHLEAF LOOP
Phone: 7202573095
e-Mail: bworkman@KBHOME.COM
9/24/2026 9:15:26 AM
Shear wall approved
Note - window not installed at bed 2 upstairs
|
|
| 10/08/2026 | D:REQ GRADE CERT REV | ADAN RIVAS | APPROVED | eTRAKiT Inspection Request | 10/7/2026 1:59:41 PM
10/7/2026 1:59 PM JP PEREZ KB HOMES
Contact Name: JP PEREZ KB HOMES
Site Address: 2024 PEACHLEAF LOOP
Phone: 7192255607
e-Mail: JPEREZ@KBHOME.COM
|
|
| 10/08/2026 | TRAC:ILC REVIEW | BUILDING COUNTER | APPROVED | CB | 10/7/2026 1:59:41 PM
10/7/2026 1:59 PM JP PEREZ KB HOMES
Contact Name: JP PEREZ KB HOMES
Site Address: 2024 PEACHLEAF LOOP
Phone: 7192255607
e-Mail: JPEREZ@KBHOME.COM
|
|
| 10/08/2026 | D:FINAL DESC | JOHN GRAHN | APPROVED | eTRAKiT Inspection Request | 10/7/2026 10:26:17 AM
10/7/2026 10:26 AM JP PEREZ KB HOMES
Contact Name: JP PEREZ KB HOMES
Site Address: 2024 PEACHLEAF LOOP
Phone: 7192255607
e-Mail: JPEREZ@KBHOME.COM
|
|
| 10/09/2026 | U: METER SET | GRANT TAYLOR | METER INSP FAIL 1 | | 10/9/2026 11:29:01 AM
A $50.00 re-inspection fee will be charged to the building permit. Once corrections have been made, please email your request for a re-inspection to meterset@crgov.com. Please note that we have up to four business days from the initial request to complete the re-inspection.
Pex must be cut flushed to the MXU mount, also meter tree can't have plastic securements must be copper securements.
|
|
| 10/12/2026 | U: METER SET | GRANT TAYLOR | METER INSP FAIL 2 | | 10/12/2026 12:31:08 PM
A $50.00 re-inspection fee will be charged to the building permit. Once corrections have been made, please email your request for a re-inspection to meterset@crgov.com. Please note that we have up to four business days from the initial request to complete the re-inspection.
Pex must be cut flushed to the MXU mount, also meter tree can't have plastic securements must be copper securements.
|
|
| 10/20/2026 | U: METER SET | ADRIAN GODINEZ | APPROVED | | |
|
| 10/30/2026 | TRAC: FINAL DOC REVIEW | BUILDING COUNTER | NOT APPROVED | eTRAKiT Inspection Request | 10/29/2026 4:54:02 PM
10/29/2026 4:54 PM JP PEREZ KB HOMES
Contact Name: JP PEREZ KB HOMES
Site Address: 2024 PEACHLEAF LOOP
Phone: 7192255607
e-Mail: JPEREZ@KBHOME.COM
10/30/2026 8:01:07 AM
Fees due; No toilet inspection; no backflow reports (irrigation & domestic); need HERS report.
|
|
| 11/02/2026 | U:HE TOILET | WILLIAM BROWN | APPROVED | eTRAKiT Inspection Request | 10/30/2026 8:52:59 AM
10/30/2026 8:52 AM JP PEREZ KB HOMES
3
Contact Name: JP PEREZ KB HOMES
Site Address: 2024 PEACHLEAF LOOP
Phone: 7192255607
e-Mail: JPEREZ@KBHOME.COM
|
|
| 11/04/2026 | TRAC: FINAL DOC REVIEW | BUILDING COUNTER | APPROVED | Fee check was delivered today 11/3/26 | 11/3/2026 1:02:13 PM
11/3/2026 1:02 PM JP PEREZ KB HOMES
Fee check was delivered today 11/3/26
Contact Name: JP PEREZ KB HOMES
Site Address: 2024 PEACHLEAF LOOP
Phone: 7192255607
e-Mail: JPEREZ@KBHOME.COM
|
|
| 11/05/2026 | TRAC:FINAL ELECTRICAL | VINCE RAPONE | APPROVED | eTRAKiT Inspection Request | 11/4/2026 10:25:25 AM
11/4/2026 10:25 AM JP PEREZ KB HOMES
Contact Name: JP PEREZ KB HOMES
Site Address: 2024 PEACHLEAF LOOP
Phone: 7192255607
e-Mail: JPEREZ@KBHOME.COM
11/5/2026 10:45:06 AM
Final electrical approved
|
|
| 11/05/2026 | TRAC:FINAL BUILDING | COLBY RIGGINS | NOT APPROVED | eTRAKiT Inspection Request | 11/4/2026 10:25:25 AM
11/4/2026 10:25 AM JP PEREZ KB HOMES
Contact Name: JP PEREZ KB HOMES
Site Address: 2024 PEACHLEAF LOOP
Phone: 7192255607
e-Mail: JPEREZ@KBHOME.COM
11/5/2026 12:51:10 PM
1. Seal around pvc next to the gas meter
2. Seal around furnace and water heater exhaust pipes
3. Intake needs a screen on it
4. Secure hose bib in the rear
5. Seal around the irrigation line
6. Kitchen exhaust fan inoperable
7. Exposed plywood at garage bottom plate
8. No ladder for attic access in the master closet.
9. Gas pipe at the furnace and water heater needs two sediment traps one for each appliance.
|
|
| 11/06/2026 | TRAC:RE FINAL BUILDING | COLBY RIGGINS | APPROVED FOR CO | Late PM if possible. | 11/5/2026 2:10:16 PM
11/5/2026 2:10 PM JP PEREZ KB HOMES
Late PM if possible.
Contact Name: JP PEREZ KB HOMES
Site Address: 2024 PEACHLEAF LOOP
Phone: 7192255607
e-Mail: JPEREZ@KBHOME.COM
11/6/2026 3:14:51 PM
Approved
|
|