| 07/14/2026 | TRAC:TEMPORARY CONSTRUCTION METER | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 7/13/2026 9:55:55 AM
7/13/2026 9:55 AM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: jboeckers@tollbrothers.com
7/14/2026 12:35:56 PM
Construction meter inspection approved
|
|
| 07/15/2026 | TRAC:GROUND PLUMBING | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 7/14/2026 9:28:45 AM
7/14/2026 9:28 AM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: JBoeckers@tollbrothers.com
7/15/2026 11:52:17 AM
APPROVED.
NOTE: NO PLUMBING PENETRATIONS THROUGH FOUNDATION STEM WALL AT TIME OF GROUND PLUMBING INSPECTION.
|
|
| 08/14/2026 | TRAC:WALL BRACING SHEATHING | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 8/12/2026 5:29:15 PM
8/12/2026 5:29 PM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: jboeckers@tollbrothers.com
8/14/2026 10:28:26 AM
APPROVED.
|
|
| 08/25/2026 | TRAC:REQUEST PRE ROUGH DOC | BUILDING COUNTER | APPROVED | cb | 8/24/2026 11:18:48 AM
8/24/2026 11:18 AM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: jboeckers@tollbrothers.com
|
|
| 09/04/2026 | TRAC:WEATHER RESISTIVE BARRIER | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/2/2026 2:55:07 PM
9/2/2026 2:55 PM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: jboeckers@tollbrothers.com
9/4/2026 11:30:27 AM
Inspector JOCA changed the inspection assignment from JOCA to CORI
9/4/2026 1:48:38 PM
APPROVED
|
|
| 09/04/2026 | TRAC:ROUGH DECK | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/2/2026 2:55:07 PM
9/2/2026 2:55 PM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: jboeckers@tollbrothers.com
9/4/2026 11:29:58 AM
Inspector JOCA changed the inspection assignment from JOCA to CORI
9/4/2026 1:48:41 PM
APPROVED
|
|
| 09/04/2026 | TRAC:POST REAR | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/2/2026 2:55:07 PM
9/2/2026 2:55 PM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: jboeckers@tollbrothers.com
9/4/2026 11:30:53 AM
Inspector JOCA changed the inspection assignment from JOCA to CORI
9/4/2026 1:48:43 PM
APPROVED.
|
|
| 09/04/2026 | TRAC:FIRE RESISTIVE | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/2/2026 2:55:07 PM
9/2/2026 2:55 PM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: jboeckers@tollbrothers.com
9/4/2026 11:31:09 AM
Inspector JOCA changed the inspection assignment from JOCA to CORI
9/4/2026 1:48:45 PM
APPROVED.N
|
|
| 09/11/2026 | TRAC:ROUGH ELECTRICAL | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 9/10/2026 12:27:08 PM
9/10/2026 12:27 PM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: JBoeckers@tollbrothers.com
9/11/2026 12:36:32 PM
Rough electrical inspection not approved
1. Romex throughout first floor attic not supported properly every 4.5 feet check everything
2. Master bathroom light a minimum of 1/4 of sheathing required in junction box
3. Support dryer romex going down wall
4. Cold water incomplete in basement verify at final
5 Ufer loose in garage
Recall inspection when ready
|
|
| 09/11/2026 | TRAC:ROUGH FRAME | COLBY RIGGINS | NOT APPROVED | eTRAKiT Inspection Request | 9/10/2026 12:27:08 PM
9/10/2026 12:27 PM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: JBoeckers@tollbrothers.com
9/11/2026 12:54:58 PM
1. Missing side nailing in THJA on both sides of the garage
2. Missing 3 2x12 at the basement windows
4. Missing two cs at 4x4 post at basement stairs
5. Shim stud at stairs to the basement
Gas ok
Gas appliances furnace,water heater, drier, range
Water ok
Dwv ok
|
|
| 09/16/2026 | TRAC:RE ROUGH FRAME | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 9/15/2026 8:52:47 AM
9/15/2026 8:52 AM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: jboeckers@tollbrothers.com
9/16/2026 12:54:25 PM
Rough frame inspection approved
All corrections completed
Verify cold water bond at final
Electrical, plumbing, mechanical
|
|
| 09/16/2026 | TRAC:INSULATION | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 9/15/2026 8:52:47 AM
9/15/2026 8:52 AM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: jboeckers@tollbrothers.com
9/16/2026 12:54:28 PM
Insulation inspection approved
|
|
| 09/22/2026 | TRAC:SHEAR WALL DRYWALL | VINCE RAPONE | APPROVED | eTRAKiT Inspection Request | 9/21/2026 9:34:59 AM
9/21/2026 9:34 AM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: jboeckers@tollbrothers.com
9/22/2026 1:27:25 PM
Shear wall approved
|
|
| 10/05/2026 | TRAC:LATH STONE BRICK TIE | VINCE RAPONE | APPROVED | eTRAKiT Inspection Request | 10/2/2026 3:27:43 PM
10/2/2026 3:27 PM TOLL SOUTHWEST SEE CR25-0649
Contact Name: Jason Boeckers
Site Address: 564 BASIN DAISY ST
Phone: 3037096246
e-Mail: JBoeckers@tollbrothers.com
10/5/2026 10:29:14 AM
Lath approved
No inspection card
|
|