| 05/29/2026 | TRAC:TEMPORARY CONSTRUCTION METER | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 5/28/2026 11:13:43 AM
5/28/2026 11:13 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: jfiscus@TOLLBROTHERS.COM
5/29/2026 12:28:54 PM
Temp construction meter inspection approved
|
|
| 06/17/2026 | TRAC:GROUND PLUMBING | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 6/16/2026 1:06:02 PM
6/16/2026 1:06 PM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: jfiscus@TOLLBROTHERS.COM
6/17/2026 2:55:20 PM
APPROVED.
|
|
| 07/10/2026 | TRAC:WALL BRACING SHEATHING | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 7/8/2026 12:06:31 PM
7/8/2026 12:06 PM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
7/10/2026 11:20:35 AM
APPROVED.
|
|
| 07/22/2026 | TRAC:REQUEST PRE ROUGH DOC | BUILDING COUNTER | APPROVED | eTRAKiT Inspection Request | 7/21/2026 11:02:20 AM
7/21/2026 11:02 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: jfiscus@TOLLBROTHERS.COM
|
|
| 07/22/2026 | TRAC:FIRE RESISTIVE | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 7/21/2026 10:46:22 AM
7/21/2026 10:46 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
7/22/2026 1:37:19 PM
Fire assistive inspection approved
Note
No fire protection is required on exterior eaves. No burn spray has been installed in basement.
|
|
| 07/22/2026 | TRAC:POST REAR | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 7/21/2026 10:42:24 AM
7/21/2026 10:42 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
7/22/2026 1:37:21 PM
Porch post rear inspection approved
|
|
| 07/22/2026 | TRAC:PORCH POST FRONT | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 7/21/2026 10:42:24 AM
7/21/2026 10:42 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
7/22/2026 1:37:23 PM
Porch post front inspection approved
|
|
| 07/22/2026 | TRAC:ROUGH DECK | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 7/21/2026 10:47:27 AM
7/21/2026 10:47 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
7/22/2026 2:25:20 PM
Rough deck inspection approved
Lid of deck has not been inspected at this time
|
|
| 07/22/2026 | TRAC:WEATHER RESISTIVE BARRIER | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 7/21/2026 10:46:23 AM
7/21/2026 10:46 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
7/23/2026 2:29:11 PM
Weather barrier inspection not approved
1. Above 2 car garage exposed plywood
2. Weather barrier cut short on single car garage north bottom
3. Pluming stub out missing flashing on north side
4. Exposed plywood basement windows x2
5. Weather barrier cut short south side of house
6. Multiple rips and tears on south side of house
7. missing stub out for all electrical/ flashing
8. missing back sliding glass door
Please recall inspection when corrections are completed
ok to release water meter
|
|
| 07/31/2026 | TRAC:WEATHER RESISTIVE BARRIER | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 7/30/2026 7:09:53 AM
7/30/2026 7:09 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
7/31/2026 10:19:43 AM
APPROVED.
|
|
| 08/12/2026 | TRAC:ROUGH ELECTRICAL | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 8/10/2026 9:14:54 AM
8/10/2026 9:14 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
8/12/2026 11:09:32 AM
Rough electrical inspection not approved
1. Flex in garage for future solar not fully set into flex connector.
2. Lights in cover deck lid incomplete missing light brackets.
3. Coiled romex in basement in front of slider incomplete.
Recall rough electrical inspection when corrections are completed
|
|
| 08/12/2026 | TRAC:ROUGH FRAME | COLBY RIGGINS | NOT APPROVED | eTRAKiT Inspection Request | 8/10/2026 9:14:54 AM
8/10/2026 9:14 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
8/12/2026 1:28:14 PM
1. Missing 3 2x6 at double ply girder at two car garage.
2. Double ply girder the trusses are not fully seated in the hangers
3. Missing gable end bracing above two car garage
4. Front porch trusses missing side nailing
5. Remove combustibles off the fireplace
6. Need an fha plate at the dryer duct at the bearing wall
7. No gas iso onsite
8. Trusses A5 web 4 to 18 is missing lateral bracing
Water ok
Dwv ok
Need gas
|
|
| 08/13/2026 | TRAC:LATH STONE BRICK TIE | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 8/12/2026 7:55:11 AM
8/12/2026 7:55 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
8/13/2026 1:45:22 PM
NOT APPROVED-
1) MISSING METAL LATH AT TIME OF INSPECTION.
2) RE-CALL WHEN READY.
|
|
| 08/14/2026 | TRAC:RE ROUGH ELECTRICAL | VINCE RAPONE | APPROVED | eTRAKiT Inspection Request | 8/12/2026 11:56:27 AM
8/12/2026 11:56 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
8/14/2026 10:02:11 AM
Rough electrical approved
|
|
| 08/14/2026 | TRAC:RE ROUGH FRAME | COLBY RIGGINS | NOT APPROVED | eTRAKiT Inspection Request | 8/12/2026 11:56:27 AM
8/12/2026 11:56 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
8/14/2026 2:07:44 PM
4. Front porch trusses missing side nailing, cannot verify because lid is covered now
5. Remove combustibles off the fireplace
6. Need an fha plate at the dryer duct at the bearing wall
Water ok
Dwv ok
gas ok
Gas appliances installed furnace, water heater, fireplace, range
|
|
| 08/17/2026 | TRAC:RE ROUGH FRAME | COLBY RIGGINS | INCOMPLETE-85FEE | eTRAKiT Inspection Request | 8/14/2026 11:32:13 AM
8/14/2026 11:32 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
8/17/2026 10:48:10 AM
4. Front porch trusses missing side nailing, cannot verify because lid is covered now
5. Remove combustibles off the fireplace
Water ok
Dwv ok
gas ok
Gas appliances installed furnace, water heater, fireplace, range
|
|
| 08/19/2026 | TRAC:LATH STONE BRICK TIE | BRETT LONGNECKER | APPROVED | eTRAKiT Inspection Request | 8/18/2026 6:29:09 AM
8/18/2026 6:29 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: SCOOLEY@TOLLBROTHERS.COM
|
|
| 08/19/2026 | TRAC:RE ROUGH FRAME | BRETT LONGNECKER | APPROVED | eTRAKiT Inspection Request | 8/18/2026 6:28:26 AM
8/18/2026 6:28 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
|
|
| 08/25/2026 | TRAC:INSULATION | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 8/24/2026 7:48:20 AM
8/24/2026 7:48 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
8/25/2026 12:45:59 PM
Insulation inspection approved
|
|
| 08/28/2026 | TRAC:SHEAR WALL DRYWALL | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 8/27/2026 3:15:56 PM
8/27/2026 3:15 PM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
8/28/2026 12:23:25 PM
APPROVED
|
|
| TRAC:ILC REVIEW | BUILDING COUNTER | | eTRAKiT Inspection Request | 9/15/2026 1:44:08 PM
9/15/2026 1:44 PM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: jfiscus@TOLLBROTHERS.COM
|
|
| 09/16/2026 | D:REQ GRADE CERT REV | JOHN GRAHN | APPROVED | | |
|
| 09/22/2026 | U: METER SET | GRANT TAYLOR | METER INSP FAIL 1 | | 9/22/2026 11:31:17 AM
A $50.00 re-inspection fee will be charged to the building permit. Once corrections have been made, please email your request for a re-inspection to meterset@crgov.com. Please note that we have up to four business days from the initial request to complete the re-inspection.
Meter tree leaking
|
|
| 10/05/2026 | U: METER SET | GRANT TAYLOR | METER INSP FAIL 2 | | 10/5/2026 1:49:27 PM
A $50.00 re-inspection fee will be charged to the building permit. Once corrections have been made, please email your request for a re-inspection to meterset@crgov.com. Please note that we have up to four business days from the initial request to complete the re-inspection.
Curbstop needs to be visible and accessible upon arrival
|
|
| 10/09/2026 | U: METER SET | GRANT TAYLOR | METER INSP FAIL 3 | | 10/9/2026 11:28:56 AM
A $50.00 re-inspection fee will be charged to the building permit. Once corrections have been made, please email your request for a re-inspection to meterset@crgov.com. Please note that we have up to four business days from the initial request to complete the re-inspection.
Need to have TOCR placard in the garage.
|
|
| 10/13/2026 | U: METER SET | GRANT TAYLOR | APPROVED | | |
|
| 10/13/2026 | D:FINAL DESC | JOHN GRAHN | APPROVED | eTRAKiT Inspection Request | 10/12/2026 8:43:20 AM
10/12/2026 8:43 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
10/13/2026 3:33:04 PM
Front and backyard are fully landscaped.
|
|
| 10/21/2026 | U:HE TOILET | WILLIAM BROWN | APPROVED | | |
|
| 10/27/2026 | TRAC: FINAL DOC REVIEW | BUILDING COUNTER | APPROVED | eTRAKiT Inspection Request | 10/26/2026 2:52:15 PM
10/26/2026 2:52 PM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: jfiscus@TOLLBROTHERS.COM
|
|
| 10/29/2026 | TRAC:FINAL BUILDING | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 10/28/2026 11:26:46 AM
10/28/2026 11:26 AM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3039948274
e-Mail: cdawson@TOLLBROTHERS.COM
10/29/2026 2:23:15 PM
Final building inspection not approved
Electrical corrections
1. Dead front not sitting flush/interfering with kitchen island breaker needs to be adjusted
2. AC requires GFCI protection
3. 125 amp subpanel breaker in main exterior panel in the off position all breakers required to be on
4. Low voltage stub not terminated in junction box on north east exterior of home/not sealed
5. Receptacle south east corner of home in Eve painters Tape is covering bell box unable to verify a receptacle is installed.
6. Lighting controlled outlet in attic is not switched from attic entry point
7. Hardwired oven requires breaker lock
8. Receptacle above fireplace is loose
9. Cord for sump pump has been cut
10. Receptacle for sub pump cord does not reach receptacle location
Final building corrections
11. Exhaust vent for water heater required to be 10 feet horizontal or 3 feet vertical from make up air intake
12. Sub pump drain needs to extend 5 feet past foundation
13. Seal exterior penetration where line set is coming through
14. Insulation needs to be permanently attached to attic lid access
15. Recirculating pump installed at hot water heater requires all hot water lines to be insulated in basement. Shut off is required to be installed underwater heater for recirculating line.
16. Fire blocking missing in basement above stair ceiling
17. No burn spray missing in basement and one location bottom of stair ceiling
Recall inspection when corrections are completed
|
|
| 11/02/2026 | TRAC:RE FINAL BUILDING | SHAWN VALENZUELA | INCOMPLETE-85FEE | eTRAKiT Inspection Request | 10/29/2026 2:25:51 PM
10/29/2026 2:25 PM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3038980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
11/2/2026 12:42:20 PM
Final building inspection not approved
Corrections from 1st inspection
1. Recirculating pump installed all hot water lines required to be insulated in the basement including half-inch.
2. Install a shut-off below the water heater for the recirculating line.
3. Receptacle supplying sub pump is too far away for sub pump cord extension cord is not a permanent means of power.
4. Missing fire blocking above stair landing in basement ceiling unfinished to finish areas.
Recall inspection when corrections are completed
Rest of final building OK
|
|
| 11/03/2026 | TRAC:RE FINAL BUILDING | SHAWN VALENZUELA | APPROVED FOR CO | eTRAKiT Inspection Request | 11/2/2026 1:57:15 PM
11/2/2026 1:57 PM TOLL BROTHERS
Contact Name: TOLL BROTHERS
Site Address: 5525 VERVAIN TRL
Phone: 3938980006
e-Mail: Jfiscus@TOLLBROTHERS.COM
11/3/2026 11:12:30 AM
Final building inspection approved
All corrections have been completed
Electrical, plumbing, mechanical approved
|
|