Permit No. 26-0995 Permit Type   COMMERCIAL TI Site Address   312 METZLER DR B
CASTLE ROCK, CO 80108
Applied   03/19/2026 Applicant   EQUITY REMODELING LLC
Approved   06/26/2026 Owner   LORAC PROPERTIES INC
Issued   06/27/2026 Contractor  
Parent Permit No.   Description   OSTEOSTRONG
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 07/06/2026B:UNGRD PLUMBMARTIN MAGERSAPPROVEDeTRAKiT Inspection Request7/2/2026 2:57:06 PM 7/2/2026 2:57 PM EQUITY REMODELING LLC Project Manager: Jeff Connell 303-345-8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 7/6/2026 11:45:33 AM No permit on site. Please pick up permit from the office ASAP.

 07/06/2026B:RGH PLUMBMARTIN MAGERSAPPROVEDeTRAKiT Inspection Request7/2/2026 2:57:06 PM 7/2/2026 2:57 PM EQUITY REMODELING LLC Project Manager: Jeff Connell 303-345-8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 7/6/2026 11:45:37 AM No permit on site. Please pick up permit from the office ASAP.

 07/06/2026B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request7/2/2026 2:57:06 PM 7/2/2026 2:57 PM EQUITY REMODELING LLC Project Manager: Jeff Connell 303-345-8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 7/6/2026 12:19:21 PM Rough electrical walls only approved Bathroom hard lid electrical rough approved Need can lighting installed to complete ceiling rough No inspection card

 07/06/2026B:RGH MECHJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request7/2/2026 2:57:06 PM 7/2/2026 2:57 PM EQUITY REMODELING LLC Project Manager: Jeff Connell 303-345-8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 7/6/2026 3:04:25 PM NOT APPROVED- 1) AS BUILT CONDITION (LAY - OUT ) DOESN'T MATCH STAND PLANS. NOTE: RECALL RGH MECHANICAL WHEN ITEM HAS BEEN CORRECTED.

 07/06/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request7/2/2026 2:57:06 PM 7/2/2026 2:57 PM EQUITY REMODELING LLC Project Manager: Jeff Connell 303-345-8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 7/6/2026 3:04:30 PM PARTIAL- 1) RGH FRAME OK (PENDING) RGH MECHANICAL.

 07/15/2026B:DRYWALLJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request7/14/2026 11:03:52 AM 7/14/2026 11:03 AM EQUITY REMODELING LLC Superintendent: Cody Carbone 720-933-8522 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 7/15/2026 11:52:13 AM PARTIAL- NOTE: 1) ALL PLUMBING VALUES TO BE ACCESSIBLE & OPERABLE/ CLOSET 2) CHECK AT FINAL. 3) REST OF DRYWALL & SCREW INSPECTION- OK.

 09/17/2026B:RGH ELECTVINCE RAPONEAPPROVEDeTRAKiT Inspection Request9/16/2026 3:29:42 PM 9/16/2026 3:29 PM EQUITY REMODELING LLC Project Manager Jeff Connell - 303-345-8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 9/17/2026 2:24:27 PM Rough electrical walls and ceiling approved Need inspection card on site for all inspections

 10/01/2026B:RGH MECHMARTIN MAGERSAPPROVEDeTRAKiT Inspection Request10/1/2026 5:33:51 AM 10/1/2026 5:33 AM EQUITY REMODELING LLC Site Contact: Jeff Connell 303-345-8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 10/1/2026 11:38:18 AM Corrections made

 10/09/2026B:FNL ELECTRICSHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request10/8/2026 12:57:21 PM 10/8/2026 12:57 PM EQUITY REMODELING LLC Site Contact: Jeff Connell - 303.345.8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 10/9/2026 11:59:02 AM Final electrical inspection not approved 1. Panel missing all labels, arch flashing, AIC rating, place of origin and location, 2. Missing spark rings in bathroom receptacle and switch Recall inspection when corrections are completed Notes Fire alarm never had a rough ceiling inspection from the town of castle rock. Drop ceiling was still open at final electrical. At time of inspection verified that fire alarm cable is supported properly

 10/09/2026B:FNL PLUMBMARTIN MAGERSAPPROVEDeTRAKiT Inspection Request10/8/2026 12:57:21 PM 10/8/2026 12:57 PM EQUITY REMODELING LLC Site Contact: Jeff Connell - 303.345.8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM

 10/12/2026B:FNL ELECTRICSHAWN VALENZUELAAPPROVEDeTRAKiT Inspection Request10/9/2026 3:23:54 PM 10/9/2026 3:23 PM EQUITY REMODELING LLC Site Contact: Jeff Connell - 303.345.8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 10/12/2026 9:46:41 AM Final electrical inspection approved Notes Per All corrections completed Note 2 glass lighting fixtures crack to be replaced before opening

 10/14/2026B:FINAL BUILDINGJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request10/13/2026 5:24:59 PM 10/13/2026 5:24 PM EQUITY REMODELING LLC Site Contact: Jeff Connell - 303.345.8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 10/14/2026 10:43:33 AM NOT APPROVED- 1) COMPLETE FINAL FIRE , ALONG WITH SIGNATURES ON BUILDING INSPECTION CARD. 2) MISSING SIGNAGE FOR FRONT DOOR FOR "THIS DOOR TO REMAIN UNLOCKED DURING OCCUPANCY". 3) MISSING CODE COMPLIANT RESTROOM IDENTIFICATION PLATE. 4) MISSING LABELING ON BREAKER PANEL FOR 36 INCHES OF CLEARANCE IN FRONT OF PANNEL. 5) UPLOAD TEST & BALANCE REPORT. REST OF BUILDING FINAL-OK. NOTE: EMERGENCY LIGHTING, TESTED & APPROVED. RECALL BUILDING FINAL WHEN ITEMS HAVE BEEN CORRECTED.

 10/14/2026B:FNL MECHJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request10/13/2026 9:21:22 AM 10/13/2026 9:21 AM EQUITY REMODELING LLC Site Contact: Jeff Connell - 303.345.8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 10/14/2026 10:43:36 AM NOT APPROVED- 1) ATTACH TEST & BALANCE REPORT. NOTE: REST OF FNL MECH - OK.

 10/21/2026B:FINAL MECHANICALJOE CARBAUGHAPPROVEDJEFF 303345846810/21/2026 12:48:49 PM APPROVED.

 10/21/2026B:FINAL BUILDINGJOE CARBAUGHPARTIALJEFF 303345846810/21/2026 12:48:51 PM PARTIAL- 1) BUILDING FINAL OK PENDING FIRE FINAL 2) COMPLETE FIRE FINAL & SIGNATURES ON BUILDING INSPECTION CARD. NOTE: OK FOR STOCK & TRAIN ONLY. RE- CALL BUILDING FINAL WHEN FIRE IS COMPLETED.

 10/22/2026B:FINAL BUILDINGJOE CARBAUGHINC OK FOR TCOeTRAKiT Inspection Request10/21/2026 4:36:37 PM 10/21/2026 4:36 PM EQUITY REMODELING LLC Site Contact: Jeff Connell - 303-345-8468 Contact Name: EQUITY REMODELING LLC Site Address: 312 METZLER DR B Phone: 9703903582 e-Mail: EQUITYREMODELING@YAHOO.COM 10/22/2026 1:55:21 PM Partial- 1) COMPLETE FIRE FINAL. & FIRE SIGNATURE ON BUILDING INSPECTION CARD. REST OF BUILD FINAL - OK. NOTE: RECALL BUILDING FINAL WHEN ITEM HAS BEEN COMPLETED. (OK FOR TCO. )