| 04/01/2026 | R:ROUGH ELECTRICAL | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 3/30/2026 6:17:34 AM
3/30/2026 6:17 AM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: oob2@nau.edu
3/30/2026 4:53:43 PM
3/30/2026 4:53 PM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: oob2@nau.edu
4/1/2026 12:38:20 PM
Rough electrical not approved
1. Exhaust fan is not installed in basement bathroom
2. Please add outlet outside of bedroom door. Any usable wall space 24 inches or more needs a Receptacle.
Notes. If you would like to change basement gym to bedroom. please revise and resubmit updated plan into the building counter for review. Must add a smoke detector inside bedroom and carbon/smoke 15 feet outside of bedroom.
|
|
| 04/01/2026 | R:ROUGH FRAME | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 3/30/2026 6:17:34 AM
3/30/2026 6:17 AM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: oob2@nau.edu
3/30/2026 4:53:32 PM
3/30/2026 4:53 PM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: oob2@nau.edu
4/2/2026 6:50:15 AM
NOT APPROVED-
1) MISSING FIRE BLOCKING AT SOUTH WALL.
REST OF FRAME -OK.
RGH PLUMBING NOT APPROVED. - NOT ON TEST, REST OF RGH PLUMBING- OK.
REVIEWED SMOKE & CO REQUIREMENTS FOR FINAL INSPECTION.
|
|
| 04/03/2026 | R:ROUGH ELECTRICAL | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 4/2/2026 10:06:40 AM
4/2/2026 10:06 AM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: oob2@nau.edu
4/3/2026 10:13:07 AM
Rough electrical approved
Corrections have been completed
Notes
Will verify at final electrical inspection that 4 junctions boxes in ceiling are accessible 1. In gym 2. Bottom of stairs 3. 2 in each living room. If existing lighting is demoed, please call a re-rough electrical inspection.
|
|
| 04/03/2026 | R:ROUGH FRAME | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 4/2/2026 10:06:39 AM
4/2/2026 10:06 AM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: oob2@nau.edu
4/3/2026 2:26:24 PM
APPROVED.
RGH PLUMBING - OK.
RGH MECHANICAL- OK.
|
|
| 04/07/2026 | R:ROUGH ELECTRICAL | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 4/6/2026 6:35:26 PM
4/6/2026 6:35 PM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: oob2@nau.edu
4/7/2026 3:07:39 PM
Rough electrical approved
Notes.
Verified that existing lights were demo in basement ceiling.
At final rough inspection 4 access boxes in ceiling in not required
Location 1. Center basement gym
2. Bottom of basement stairs in soffit
3. Other 2 are in each living room area
These are not required at final electrical inspection
|
|
| 05/26/2026 | R:FINAL BUILDING BASEMENT** | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 5/24/2026 8:45:55 AM
5/24/2026 8:45 AM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: oob2@nau.edu
5/27/2026 6:58:50 AM
Final building electrical corrections
1. Flexible cord ran though wall in under stairs closet is not rated to run through walls.
2. Receptacle in under stairs closet has no power
3. Smoke detectors/ carbon monoxide detectors have dust covers installed can not test at time of inspection please remove covers
4. Receptacle under sink missing sparking and cover plate incomplete
5. Tape light in gym is flashing
6. Loose receptacle to the right outside of bedroom door.
Please recall final building inspection when electrical corrections are completed
Final building corrections
1. Missing guard rails going down stairs please install
2. Please install access panel for plumbing clean out in gym
3. Missing ceiling register vent in basement bedroom
4. Missing draft stopping from unfinished to finish areas in mechanical room. Insulation is installed there are still gaps throughout
5. Could not test basement bathroom sink drain. Drain is stuck in closed position
6. Basement living room sink water is shut off could not test
7. Tighten shower trim in basement bathroom shower
8. Seal basement shower fixtures x2
9. ***Contact front building counter and upload contractors information to permit this will hold up final building contractors, name, company, name, and licensing number***
|
|
| 05/27/2026 | R:RE FINAL BUILDING BASEMENT** | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 5/26/2026 4:07:22 PM
5/26/2026 4:07 PM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: oob2@nau.edu
5/28/2026 7:53:06 AM
Final building inspection not approved
1. Please install access panel for plumbing clean out in basement gym
2. Please tighten and seal bathtub spout. In basement.
3. Please contact front building counter and upload electric fireplace location, and specs
4. Please upload contractor to permit name, company name, and license number
Please recall final building inspection when corrections are completed
***ok to occupy basement***
All other corrections have been completed
|
|
| 05/29/2026 | R:RE FINAL BUILDING BASEMENT** | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 5/28/2026 7:25:56 AM
5/28/2026 7:25 AM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: oob2@nau.edu
5/29/2026 8:54:15 AM
Final building inspection not approved
1. Please contact the front building counter and provide the information of the contractor. name, company name, and license number
Notes
All other corrections have been completed
Electrical fire place is located on south living room basement wall
***ok to occupy basement ***
|
|
| 10/23/2026 | R:RE FINAL BUILDING BASEMENT** | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 10/19/2026 3:13:00 PM
10/19/2026 3:13 PM Oscar Bujanda
Contact Name: Oscar Bujanda
Site Address: 5685 FARRIER PT
Phone: 6023495608
e-Mail: obujanda22@gmail.com
10/23/2026 1:02:25 PM
Final building inspection approved
Notes
Homeowner signed a homeowner agreement provided by the town of Castle rock that they are performing all the work themselves.
|
|