| 03/20/2026 | R:ROUGH ELECTRICAL | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 3/19/2026 1:02:31 PM
3/19/2026 1:02 PM 5 STAR BASEMENT FINISH
Contact Name: 5 STAR BASEMENT FINISH
Site Address: 3140 MASTERS PT
Phone: 7206718984
e-Mail: 303CONTRACTOR@GMAIL.COM
3/20/2026 12:19:32 PM
Rough electrical not approved
1: wire above smoke detector junction box needs to be terminated into a junction box.
Please call in rough electrical when corrections have been completed
|
|
| 03/20/2026 | R:ROUGH FRAME | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 3/19/2026 1:07:27 PM
3/19/2026 1:07 PM 5 STAR BASEMENT FINISH
Contact Name: 5 STAR BASEMENT FINISH
Site Address: 3140 MASTERS PT
Phone: 7206718984
e-Mail: 303CONTRACTOR@GMAIL.COM
3/20/2026 2:15:39 PM
NOT APPROVED-
1) COMPLETE ROUGH ELECTRIC ELECTRICAL INSPECTION.
2) MISSING FIRE-BLOCKING IN CONCEALED SPACES AND TOP PLATE PENETRATIONS.
REST OF FROUGH FRAME - OK.
NOTE: REVIEWED SMOKE ALARM AND CARBON MONOXIDE REQUIREMENTS WITH CONTRACTOR FOR FINAL.
|
|
| 04/09/2026 | R:RGH FRAME | SHAWN VALENZUELA | NOT APPROVED | 7206718948 | 4/9/2026 11:35:22 AM
Inspector JOCA changed the inspection assignment from JOCA to SHVA
4/9/2026 12:21:44 PM
Rough frame not approved
1. Please add draft stopping/ fire blocking above sump pump.
2. Please add draft stopping/ fire blocking in basement bedroom above concealed spaces south west corner of bedroom in furred out wall.
|
|
| 04/09/2026 | R:RGH ELECT | SHAWN VALENZUELA | APPROVED | 7206718948 | 4/9/2026 12:21:47 PM
Rough electrical approved
All connections have been completed
Will verify on final electrical inspection that access panel is installed in basement bedroom south west corner of wall. Electrical junction box is located behind the framing. Will need to be accessible.
|
|
| 04/13/2026 | R:RE_ROUGH FRAME | COLBY RIGGINS | APPROVED | 7206718948 | 4/13/2026 1:03:58 PM
Approved
|
|
| 10/26/2026 | R:FINAL BUILDING BASEMENT** | SHAWN VALENZUELA | NOT APPROVED | | 10/26/2026 3:20:59 PM
Final building basement inspection not approved
1. Revise plans showing basement as one room when new plans are up loaded contact front building counter for plans to be reviewed
2. Add weather stripping to mechanical room doors x2 doors.
3. Smoke detectors and carbon monoxide detectors are not communicating with each other or through out the house
4. Receptacle buried behind drywall in the back room left of the mechanical room door.
Recall inspection when corrections are completed
Plumbing, mechanical approved
|
|