| 08/25/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 8/24/2026 3:24:15 PM
8/24/2026 3:24 PM MARK YOUNG CONSTRUCTION (A M)
1st half of the sales floor - Replaced fixtures - Visual overhead
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037761449
e-Mail: MOSKARSON@MARKYOUNGCONSTRUCTION.COM
8/25/2026 2:03:10 PM
Rough electrical approved for changing existing high light fixtures at sales floor. Half done
Schedule rough electrical when Perimeter and low aisle lights are complete
|
|
| 09/23/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | rough electrical partition wall | 9/23/2026 6:01:35 AM
9/23/2026 6:01 AM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037761449
e-Mail: MOSKARSON@MARKYOUNGCONSTRUCTION.COM
9/23/2026 2:56:19 PM
Rough electrical partition wall front of store
3 TV receptacles with data sleeves approved
|
|
| 10/08/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | | 10/8/2026 3:16:21 PM
Rough electrical inspection partial approved
Notes
Raceway/ wire size from MSB panel to panel HDR 4 parallel runs of 350 K mill and one three ground 3 inch conduit
Lugs torched in panel hdr run to msB incomplete due to shut required to install breaker
Wall rough inspection for 2nd floor mezzanine.
Rooms 213, 211, 212. 209, half of 201 highlighted on plans page e2.2
Talked with Jeff to schedule shut down with the town of castle to install breaker in msB.
|
|
| 10/08/2026 | B:ELECTRICAL SERVICE | SHAWN VALENZUELA | PARTIAL | VOIDED (SHVA 10/8/2026) | 10/7/2026 1:43:07 PM
10/7/2026 1:43 PM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037761449
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
10/8/2026 10:48:46 AM
Rough electrical inspection partial approved
Notes
Raceway/ wire size from MSB panel to panel HDR 4 parallel runs of 350 K mill and one three ground 3 inch conduit
Lugs torched in panel hdr run to msB incomplete due to shut required to install breaker
Wall rough inspection for 2nd floor mezzanine.
Rooms 213, 211, 212. 209, half of 201 highlighted on plans page e2.2
Talked with Jeff to schedule shut down with the town of castle to install breaker in msB.
10/8/2026 3:17:01 PM
Inspection voided by SHVA. Most recent remarks follow: eTRAKiT Inspection Request
|
|
| 10/09/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Mezzanine/Break room offices 213,211,212 | 10/8/2026 10:49:57 AM
10/8/2026 10:49 AM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037761449
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
10/9/2026 9:12:55 AM
PARTIAL-
1) RGH FRAME FOR ELECTRICAL ROOM 210, QUIET ROOM, 209, MANAGER'S OFFICE 211, AP EQUIPMENT 212 - OK. HIGHLIGHTED ON PLAN PAGE A 5.1.
|
|
| 10/09/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | Cafe underground | 10/8/2026 1:47:20 PM
10/8/2026 1:47 PM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037761449
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
10/9/2026 12:53:12 PM
All under Groung grease drains for the cafe complete
|
|
| 10/22/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | In-wall @ cafe | 10/21/2026 10:46:36 AM
10/21/2026 10:46 AM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037761449
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
10/22/2026 10:37:45 AM
Electrical wall rough approved
Cafe / snack bar
|
|
| 10/22/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | in-wall @ cafe | 10/21/2026 10:47:57 AM
10/21/2026 10:47 AM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037761449
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
10/22/2026 1:46:53 PM
In wall for cafe water and DWV approved. Marked in green on P2.8
|
|
| 10/22/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Walls @ cafe | 10/21/2026 10:48:50 AM
10/21/2026 10:48 AM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037761449
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
10/22/2026 1:55:18 PM
PARTIAL-
1) CFMF IN CAFE AREA - OK.
NOTE: PIZZA HOOD SUPPORTS- OK PER GM 2.1
|
|
| 10/26/2026 | B:ROUGH MECHANICAL | MARTIN MAGERS | PARTIAL | Cafe Rough - overhead | 10/23/2026 12:47:28 PM
10/23/2026 12:47 PM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037761449
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
10/26/2026 12:11:34 PM
Trunk lines and exhaust fan vent approved as marked in green on M 2.1. Still need hood and insulation inspections.
|
|
| 11/02/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | Floral - underground plumbing rough | 10/30/2026 3:09:58 PM
10/30/2026 3:09 PM MARK YOUNG CONSTRUCTION (A M)
Andy A. 303-710-3777
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037761449
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
11/2/2026 12:46:12 PM
Floral area under ground as marked in green on GP1.
|
|
| 11/10/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | Cafe overhead / above grid | 11/9/2026 2:54:06 PM
11/9/2026 2:54 PM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037100725
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
11/10/2026 2:23:30 PM
Cafe above ceiling rough electrical approved
Mezzanine phase 2 mid wall location vending and tech bar ( walls only )
|
|
| 11/10/2026 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | Underground plumbing @ new Sushi | 11/9/2026 3:35:54 PM
11/9/2026 3:35 PM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037100725
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
11/10/2026 3:02:24 PM
Partial on Sushi Island under ground plumbing as marked on GP1 in orange. Not connected to the main line yet.
|
|
| 11/10/2026 | B:ROUGH MECHANICAL | MARTIN MAGERS | PARTIAL | Cafe grease duct rough overhead | 11/9/2026 2:48:31 PM
11/9/2026 2:48 PM MARK YOUNG CONSTRUCTION (A M)
Jeff Boone 303-710-0725
Contact Name: MARK YOUNG CONSTRUCTION (A M)
Site Address: 5940 PROMENADE PKWY
Phone: 3037100725
e-Mail: JBOONE@MARKYOUNGCONSTRUCTION.COM
11/10/2026 3:02:26 PM
all defusers connected with hard lines, except one unit by exhaust hood, also exhaust hood approved. As marked in orange on M2.1 and M5
|
|