11/21/2026
11:01 PM
 
Permit No. 26-0430 Permit Type   COMMERCIAL TI Site Address   504 SECOND ST
CASTLE ROCK, CO 80104
Applied   02/05/2026 Applicant   LAKOTA ROOFING AND CONSTRUCTION INC
Approved   06/03/2026 Owner   VCM HOLDINGS LLC
Issued   06/03/2026 Contractor  
Parent Permit No.   Description   CREATING NEW OFFICE SPACE INSIDE BUILDING
  Notes   and adding 4 additional offices
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 06/09/2026B:RGH FRAMEJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request6/8/2026 3:34:39 PM 6/8/2026 3:34 PM LAKOTA ROOFING AND CONSTRUCTION INC Framing inspection. On lockbox 1475. Please let us know rough time so we can try to be onsite during inspection Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 6/9/2026 2:23:08 PM NOT APPROVED- 1) COMPLETE ALL RGH MEP's BEFORE RGH FRAME. 2) FRAMING PLANS DO NOT MATCH AS BUILT CONDITIONS/ UPDATED PLANS WITH PLAN REVIEW & FRONT COUNTER OR PROVIDE A STAMPED LETTER FROM A COLORADO DESIGN PROFESSIONAL OF AS BUILT CONDITION. NOTE: RECALL RGH FRAME WHEN ALL ITEMS HAVE BEEN COMPLETED.

 07/02/2026B:RGH ELECTSHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request7/1/2026 7:55:41 PM 7/1/2026 7:55 PM LAKOTA ROOFING AND CONSTRUCTION INC Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 7/2/2026 12:09:27 PM Rough electrical inspection not approved 1. Please have stamped approved town match existing one line diagram on site 2. One line diagram with print provided on site do not match what is currently installed. Subpanel was added on second floor does not show on prints. Please revise and resubmit plans to the town of Castle rock once prints are uploaded. Please contact front building counter so print can be reviewed.

 07/31/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request7/31/2026 10:25:24 AM 7/31/2026 10:25 AM LAKOTA ROOFING AND CONSTRUCTION INC Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 7/31/2026 2:53:58 PM Rough electrical partial inspection approved Notes First floor walls and ceiling ok Second floors walls only Will verify at final inspection frog eye at bottom of stairs land is surface mount and installed. Call 2nd floor rough ceiling inspection when drop ceiling is installed

 07/31/2026B:RGH MECHJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request7/31/2026 10:25:24 AM 7/31/2026 10:25 AM LAKOTA ROOFING AND CONSTRUCTION INC Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 7/31/2026 2:54:16 PM APPROVED- 1) DUCT LAYOUT, SEAL & SUPPORT-OK.

 07/31/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request7/31/2026 10:25:24 AM 7/31/2026 10:25 AM LAKOTA ROOFING AND CONSTRUCTION INC Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 7/31/2026 2:54:19 PM PARTIAL- 1) UPDATE HEADER SCHEDULE ON PLAN TO MATCH AS BUILT CONDITION. 2) REST OF RGH FRAME - OK. 3) COMPLETE RGH ELECTRICAL. NOTE: RECALL RGH FRAME INSPECTION WHEN FIRE-BLOCKING FOR DUCTING IS COMPLETE.

 08/03/2026B:RGH FRAMEBRETT LONGNECKERPARTIALeTRAKiT Inspection Request8/2/2026 8:38:38 AM 8/2/2026 8:38 AM LAKOTA ROOFING AND CONSTRUCTION INC fire blocking in soffits Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 8/3/2026 4:19:17 PM Rough frame and rough mechanical for 1st floor walls and ceiling ok. Rough frame for 2nd floor walls only. Reschedule rough electrical and rough frame for ceiling on 2nd floor.

 08/07/2026B:DRYWALLBRETT LONGNECKERAPPROVEDeTRAKiT Inspection Request8/6/2026 8:29:36 AM 8/6/2026 8:29 AM LAKOTA ROOFING AND CONSTRUCTION INC drywall screw inspection Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 8/7/2026 8:37:15 AM Drywall wall approved. Note: Inspection card not on site.

 08/13/2026B:RGH ELECTSHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request8/12/2026 1:09:26 PM 8/12/2026 1:09 PM LAKOTA ROOFING AND CONSTRUCTION INC Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 8/13/2026 10:43:18 AM Rough electrical inspection not approved 2nd floor drop ceiling inspection 1. Ceiling tiles have already been installed 2. Can lights in ceiling need to be independently supported 3. Open j boxes need to be labeled and closed Reschedule inspection when corrections are completed

 08/14/2026B:RGH ELECTSHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request8/13/2026 1:03:33 PM 8/13/2026 1:03 PM LAKOTA ROOFING AND CONSTRUCTION INC Grid upstairs Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 8/14/2026 11:06:12 AM Rough electrical inspection not approved 1. Can lights installed in 2nd floor drop ceiling need to be independently supported to building or structure minimum of #12 gauge ceiling wire. Recall inspection when corrections are completed Notes Final electrical inspection Verify main disconnect on exterior of building Verify sub panel final electrical connections on 2nd floor Verify 1st main panel final electrical connections Verify all em/ exits signs Verify all new mechanical equipment being installed 2nd floor mechanical closet / mini split located outside of front door

 08/14/2026B:RGH FRAMEJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request8/13/2026 1:03:33 PM 8/13/2026 1:03 PM LAKOTA ROOFING AND CONSTRUCTION INC Grid upstairs Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 8/14/2026 12:51:29 PM NOT APPROVED- 1) COMPLETE RGH ELECTRICAL. 2) IN CORRECT SIZE OF GRID WIRE/ 12 GAGE REQUIRED. NOTE: RECALL INSPECTION WHEN ALL ITEMS HAVE BEEN COMPLETED.

 11/16/2026B:RE ROUGH ELECTRICALSHAWN VALENZUELAAPPROVED11/16/2026 10:42:38 AM Re rough electrical inspection approved All corrections have been completed

 11/16/2026B:RGH FRAMEJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request11/13/2026 1:41:32 PM 11/13/2026 1:41 PM LAKOTA ROOFING AND CONSTRUCTION INC Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 11/16/2026 1:51:16 PM APPROVED.

 11/16/2026B:FNL ELECTRICSHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request11/13/2026 12:12:05 PM 11/13/2026 12:12 PM LAKOTA ROOFING AND CONSTRUCTION INC Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 11/17/2026 7:35:59 AM 2nd floor sub panel minimum 36in clearance in front of panel 2nd floor sub panel missing all labels, and dead front cover. AIC rating, arch flash, voltage, panel schedule, place of origin label all em circuits Open junction box next to 2nd floor sub panel Missing spark rings on 2nd floor wood deactivate walls Verify at next inspection all em are on with local lighting circuit 1st floor corrections Plans show remote head at front exterior door All receptacles in warehouse require GFCI protection per plans both on east office walls 3 locations 1st floor main panel missing dead front cover, all labels AIC rating, arch flash, voltage, panel schedule, place of origin label all em circuits close all junction boxes next to panel Verify at next inspection all em lights are on local lighting circuit 1st floor Exterior new ac requires gfci protection Label ac disconnect Label main exterior disconnect updated notes by inspector on 11/17/2026 Per plans shows remote heads at 2 locations. 1 is above main exterior door. 2 is above warehouse emergency exit door. both lights need to be provided with emergency battery backup, turn on when loss of power is simulated.

 11/16/2026B:FNL MECHJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request11/13/2026 12:12:05 PM 11/13/2026 12:12 PM LAKOTA ROOFING AND CONSTRUCTION INC Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 11/20/2026 1:58:43 PM NOT APPROVED- 1) MISSING HORIZONTAL GAS LINE SUPPORT / INSIDE OF EXTERIOR WALL. 2) MISSING THREE POINT CONNECTIONS AT EXHAUST JOINTS. Notes: - MISSING UNSCREWED CAPS FOR A/C UNIT. - A/C CURRENTLY HAS NO PERMIT / NEW INSTALL OF A/C UNIT REQUIRES A PERMIT. REST OF MECHANICAL FINAL- OK.

 11/20/2026B:FINAL BUILDINGJON WHITEINC OK FOR TCOSEE NOTES11/19/2026 2:40:25 PM 11/19/2026 2:40 PM LAKOTA ROOFING AND CONSTRUCTION INC Fire department will inspect at 10am Contact Name: LAKOTA ROOFING AND CONSTRUCTION INC Site Address: 504 SECOND ST Phone: 8552324797 e-Mail: STACIA@SMLAKOTA.COM 11/20/2026 2:12:44 PM FINAL BUILDING INSPECTION INCOMPLETE; OK FOR TCO SWO HAS BEEN APPROVE TO BE REMOVED AND OCCUPANCY CAN NOW BE ALLOWED PER THE TOWN OF CASTLE ROCK'S BUILDING DIVISION AND CRFD FIRE ANDLIFE SAFETY DIVISION THE FOLLOWING ARE CORRECTIONS TO BE MADE PRIOR TO CO ISSUANCE; 1- COMPLETE FINAL ELECTRICAL AND MECHANICAL INSPECTIONS 2- COMPLETE FINAL FIRE INSPECTION 3- MISSING TYPE X3 EMERGENCY LUMINAIRES AT SOUTH EXIT AND FRONT ENTRY PER PLAN (E2.0) 4- MAKE CLEAR EGRESS AT SOUTH EGRESS DOOR IN WAREHOUSE. MINIMUM 36" CLEAR PATH 5- SCHEDULERE-FINAL BUILDING INSPECTION NOTES; - PLEASE SEE ELECTRICAL AND MECHANICAL CORRECTIONS BELOW THAT NEED TO BE CORRECTED PRIOR TO SCHEDULING FINAL INSPECTIONS; ELECTRICAL 1- Open junction box next to 2nd floor sub panel 2- Missing spark rings on 2nd floor wood deactivate walls 1st floor corrections 1- Plans show remote head at front exterior door 2- All receptacles in warehouse require GFCI protection per plans both on east office walls 3 locations 3- 1st floor main panel missing dead front cover, all labels AIC rating, arch flash, voltage, panel schedule, place of origin label all em circuits close all junction boxes next to panel 4- Label main exterior disconnect updated notes by inspector on 11/17/2026 5- Per plans shows remote heads at 2 locations. 1 is above main exterior door. 2 is above warehouse emergency exit door. both lights need to be provided with emergency battery backup, turn on when loss of power is simulated. MECHANICAL 1) MISSING HORIZONTAL GAS LINE SUPPORT / INSIDE OF EXTERIOR WALL. 2) MISSING THREE POINT CONNECTIONS AT EXHAUST JOINTS. Notes: - MISSING UNSCREWED CAPS FOR A/C UNIT. - A/C CURRENTLY HAS NO PERMIT / NEW INSTALL OF A/C UNIT REQUIRES A PERMIT. REST OF MECHANICAL FINAL- OK. 11/20/2026 1:58:43 PM