| 07/06/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/3/2026 8:19:54 AM
7/3/2026 8:19 AM ANDREW SCOTT - LAYTON
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
7/6/2026 12:12:20 PM
PARTIAL-
1) N/REAR, E/RIGHT & FRONT/ , W/ LEFT ELEVATION PARPIT FRAMING- OK.
NOTE: FRONT/ SOUTH CONNECTIONS TO EXCITING BUILDING TO BE INSPECTED AT FUTURE INSPECTION.
|
|
| 07/15/2026 | B:RGH FRAME | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 7/15/2026 2:45:47 AM
7/15/2026 2:45 AM ANDREW SCOTT - LAYTON
Requesting interior framing inspection and consultation
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
7/15/2026 11:52:04 AM
NOT APPROVED.
NOTE: CONSULTATION ON INSPECTION STEPS & PROCESS, NO RGH FRAME INSPECTION PERFORMED.
|
|
| 07/21/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/20/2026 8:42:36 AM
7/20/2026 8:42 AM ANDREW SCOTT - LAYTON
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
7/21/2026 3:29:57 PM
PARTIAL-
1) ONE SIDE TOP OF WALL FRAME & DRYWALL SCREW INSPECTION - AS MARKED, OK.
|
|
| 07/21/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/20/2026 8:42:36 AM
7/20/2026 8:42 AM ANDREW SCOTT - LAYTON
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
7/21/2026 3:29:59 PM
PARTIAL-
1) ONE SIDE TOP OF WALL FRAME & DRYWALL SCREW INSPECTION - AS MARKED, OK.
|
|
| 07/28/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/27/2026 1:52:31 PM
7/27/2026 1:52 PM ANDREW SCOTT - LAYTON
This will be to inspect the other side of top out drywall.
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
7/28/2026 10:24:34 AM
PARTIAL-
TOP OUTPUT
1) HEAD OF WALL DRYWALL, FRAME & MINERAL WOOL HIGHLIGHTED IN GREEN- OK.
2) FIRST LAYER 5/8 X GYP AT EXAM G26, G24 & G22 - OK.
|
|
| 07/29/2026 | B:RGH MECH | MARTIN MAGERS | PARTIAL | | 7/29/2026 11:44:18 AM
Supply and return ducts for the vault approved. Still needs insulation on supply.
|
|
| 07/31/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | Partial Rough Plumbing Inspection | 7/30/2026 3:29:04 PM
7/30/2026 3:29 PM COLORADO MECHANICAL SYSTEMS LLC
Rough plumbing inspections for Domestic water and DWV.
Call 10-20 minutes ahead. Be aware of bad cell service onsite.
Contact Name: Ben Harris
Site Address: 2360 MEADOWS BLVD
Phone: 7203477147
e-Mail: mrutherfurd@coloradomech.com
7/31/2026 2:47:06 PM
Vault room rough plumbing inspection. Approved marked on P1.2.1 ans P1.1.1 ,all water , in blue, and DWV , in orangeand well roof drains, in green. Approved.
|
|
| 08/04/2026 | B:DRYWALL | BRETT LONGNECKER | PARTIAL | Top of wall 4ft both sides | 8/3/2026 8:52:29 AM
8/3/2026 8:52 AM Blake Daldegan
Screw Inspection low wall G32, G34, G36, G37, G12, G11
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
8/4/2026 11:35:17 AM
Inspection for top of wall both sides for areas highlighted in blue. Photo uploaded.
|
|
| 08/04/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | Partial Rough Plumbing Inspection | 8/3/2026 9:37:38 AM
8/3/2026 9:37 AM COLORADO MECHANICAL SYSTEMS LLC
Partial Rough inspection for Chiller water lines.
Please call 20 min before arrival
Contact Name: Mark Peters
Site Address: 2360 MEADOWS BLVD
Phone: 7205279350
e-Mail: mrutherfurd@coloradomech.com
8/4/2026 2:17:10 PM
Hydronic line for chiller in vault area only approved. See picture
8/4/2026 2:21:04 PM
Hydronic line for chiller in vault area only approved. See picture
|
|
| 08/07/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | Partial Rough Inspection | 8/6/2026 3:06:54 PM
8/6/2026 3:06 PM COLORADO MECHANICAL SYSTEMS LLC
Partial Chilled water inspection
Contact Name: Mark Peters
Site Address: 2360 MEADOWS BLVD
Phone: 7205279350
e-Mail: mrutherfurd@coloradomech.com
8/10/2026 7:07:15 AM
Hydronic lines from vault to Linac Equipment room approved. Marked in green on M2.2.0
|
|
| 08/10/2026 | MF:ROUGH FRAME | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 8/7/2026 3:20:32 PM
8/7/2026 3:20 PM Blake Daldegan
Consultation on exterior wall fur out framing firestop
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
8/10/2026 12:44:04 PM
NOT APPROVED-
CONSOLE ON CONCEALED SPACES.
|
|
| 08/10/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | partial rough plumbing inspection | 8/7/2026 8:13:08 AM
8/7/2026 8:13 AM COLORADO MECHANICAL SYSTEMS LLC
Rough Plumbing inspection for DWV and Domestic Water
Contact Name: Ben Harris
Site Address: 2360 MEADOWS BLVD
Phone: 7203477147
e-Mail: mrutherfurd@coloradomech.com
8/10/2026 3:04:30 PM
Water lines and recirculating lines west of main hallway to vault. Missing wall boxes. Ok insulate. Marked in green.
|
|
| 08/12/2026 | B:RGH FRAME | BRETT LONGNECKER | PARTIAL | Circulation corridor wall | 8/10/2026 2:18:48 PM
8/10/2026 2:18 PM Blake Daldegan
Rough frame inspection for drywall closure in rooms G51, G50, G39, G39
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
8/12/2026 10:01:50 AM
Rough frame for wall along circulation corridor ok. Highlighted in yellow and uploaded to permit.
|
|
| 08/12/2026 | B:DRYWALL | BRETT LONGNECKER | PARTIAL | G39 interior drywall | 8/10/2026 2:18:48 PM
8/10/2026 2:18 PM Blake Daldegan
Rough frame inspection for drywall closure in rooms G51, G50, G39, G39
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
8/12/2026 10:01:52 AM
Drywall for room G39 interior only ok. Highlighted in blue and uploaded to permit.
|
|
| 08/17/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 8/14/2026 10:26:06 AM
8/14/2026 10:26 AM ANDREW SCOTT - LAYTON
Interior framing for linac vault inspection
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
8/17/2026 10:08:52 AM
PARTIAL-
RGH FRAME -OK IN VAULT ROOM.
|
|
| 08/17/2026 | B:INSULATION | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 8/14/2026 9:58:41 AM
8/14/2026 9:58 AM ANDREW SCOTT - LAYTON
This is a roofing (tpo/insulation) inspection
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
8/17/2026 10:08:56 AM
NOT APPROVED-
NOT READY AT TIME OF INSPECTION.
|
|
| 08/19/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 8/18/2026 8:03:47 AM
8/18/2026 8:03 AM Blake Daldegan
G42, G44 top out screw
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
8/19/2026 11:07:07 AM
PARTIAL-
DRYWALL & SCREW INSPECTION
1) HEAD OF WALL SECOND LAYER 5/8 TYPE X AT G42 CT ROOM - OK.
2) HEAD OF WALL / G44 CLEAN SUPPLY - OK.
|
|
| 04/29/2026 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | | 8/20/2026 9:58:51 AM
MARTIN MAGERS
B:UNGRD PLUMB
Partial called in for 26-0238
Ground plumbing for Exam rooms G26, 24,23,22,and 10A and unity sink in G25 as marked in green on Temp P1 see picture.
4/29/2026 2:03:20 PM
Inspection Transferred from permit 26-0220
|
|
| 05/05/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | | 8/21/2026 8:17:18 AM
5/5/2026 12:16:25 PM (MARTIN MAGERS)
Partial Underground Waste and Vent for north of grid line 6 except G35 sink. See P1 0 0.
Note this is for permit 26-0238 and was moved from 26-0220.
|
|
| 05/19/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | | 8/21/2026 8:21:19 AM
5/19/2026 2:45:53 PM (MARTIN MAGERS)
This inspection is correlated with permit 26-0238.
Inspected bath area ground plumbing at reception and floor drain in EVS closet. Marked in green on P 1.0.0
6" and 4" existing drains are to be replaced and supported as shown on P1.0.0
This inspection was tranfered from permit 26-0220
|
|
| 06/03/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | | 8/21/2026 8:24:49 AM
6/3/2026 11:54:37 AM (MARTIN MAGERS)
Note this is for permit 26-0238 6" main sewer on east side, 4" branch at line 8 marked in pink on page P1.0.0
This inspection was transferred from permit 26-0220
|
|
| 08/24/2026 | B:RGH PLUMB | COLBY RIGGINS | PARTIAL | Rough Plumbing Inspection | 8/20/2026 10:05:56 AM
8/20/2026 10:05 AM COLORADO MECHANICAL SYSTEMS LLC
Rough inspection for Domestic Water and Domestic Waste & Vent
Contact Name: Ben Harris
Site Address: 2360 MEADOWS BLVD
Phone: 7203477147
e-Mail: mrutherfurd@coloradomech.com
8/24/2026 12:41:20 PM
P 1.1.1 marked in yellow domestic waste and vents
P1 .2.1 marked in green water lines and recirculating lines
M2.2.0 marked in yellow hydronic line
|
|
| 08/25/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | G40B, G42 drywall top out | 8/24/2026 7:56:31 AM
8/24/2026 7:56 AM Blake Daldegan
G40B, G42 drywall top out
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
8/25/2026 9:31:46 AM
PARTIAL-
1) G40B, G42 drywall top out- OK, HIGHLIGHTED IN PINK & DATED ON ONSITE PLANS.
|
|
| 09/01/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | Overhead Rough HVAC Inspection | 8/31/2026 2:16:46 PM
8/31/2026 2:16 PM COLORADO MECHANICAL SYSTEMS LLC
Please call 10-15 minutes before arrival
Contact Name: Josh Livingston
Site Address: 2360 MEADOWS BLVD
Phone: 7208770061
e-Mail: mrutherfurd@coloradomech.com
9/1/2026 1:58:07 PM
PARTIAL-
1) OVER HEAD SEAL & SUPPORTS FOR AREA GRID LINE 0.1 to GRID LINE 6 - OK. MARKED IN GREEN 9/1/26 M2.1.0
|
|
| 09/02/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/1/2026 2:40:21 PM
9/1/2026 2:40 PM Emmanuel Santana
vault soffits and west side walls of rad onc space
Contact Name: Emmanuel Santana
Site Address: 2360 MEADOWS BLVD
Phone: 7207995953
e-Mail: emmanuel.santana@laytonconstruction.com
9/2/2026 8:44:49 AM
Rough electrical inspection partial approved
Linca vault g51 hard lid inspection only. Highlighted on provided stamped plans what was inspected
|
|
| 09/02/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/1/2026 11:35:47 AM
9/1/2026 11:35 AM Blake Daldegan
Fire rated walls insulation G25, G44, G60
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
9/2/2026 10:15:16 AM
PARTIAL-
1) MINERAL WOOL AT HEAD OF WALL DECKING - STORAGE G50, CLEANING SUPPLY G44 & CT SIM G42- OK.
|
|
| 09/03/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/2/2026 2:11:27 PM
9/2/2026 2:11 PM ANDREW SCOTT - LAYTON
Screw inspection for Vault
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
9/3/2026 11:34:30 AM
PARTIAL-
1) 5/8 TYPE X GYP & MOISTURE RESISTANCE IN LINAC G51- OK.
|
|
| 04/29/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | | 8/21/2026 8:13:05 AM
4/29/2026 2:03:20 PM (MARTIN MAGERS)
Partial called in for 26-0238
Ground plumbing for Exam rooms G26, 24,23,22, and 10A and unity sink in G25 as marked in green on Temp P1 see picture. This inspection was moved from 26-0220
|
|
| 09/11/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/10/2026 10:33:17 AM
9/10/2026 10:33 AM ANDREW SCOTT - LAYTON
State inspection for same scheduled for 9am on 9/11/26
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
9/11/2026 9:17:29 AM
PARTIAL-
1) RGH FRAME ALL ( WALLS) ONLY & RATED BACKING - OK.
|
|
| 09/11/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | Inwall Inspection | 9/10/2026 2:41:46 PM
9/10/2026 2:41 PM COLORADO MECHANICAL SYSTEMS LLC
Inwall Domestic Water Insulation Inspection - 1:00pm
Contact Name: Andrew Scott
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: mrutherfurd@coloradomech.com
9/11/2026 2:04:53 PM
In wall insulation approved.
|
|
| 09/14/2026 | B:RGH MECH | MARTIN MAGERS | PARTIAL | Rough Duct Inspection | 9/11/2026 7:53:56 AM
9/11/2026 7:53 AM COLORADO MECHANICAL SYSTEMS LLC
Rough Duct Inspection
Contact Name: Josh Livingston
Site Address: 2360 MEADOWS BLVD
Phone: 7208770061
e-Mail: mrutherfurd@coloradomech.com
9/14/2026 10:30:53 AM
Istpected and approved duct work k through J9 6-9 marked in blue.
|
|
| 09/17/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/15/2026 10:07:27 AM
9/15/2026 10:07 AM Blake Daldegan
Rough Frame inspection low wall girds H-L
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
9/17/2026 1:23:00 PM
PARTIAL-
1) DRYWALL & SCREW INSPECTION 1 LAYER,
STORAGE G38, CORRIDOR G20B, G35,G35A, G33, G28, G29,G27,G25- OK.
2) 1st LAYER OF TWO LAYERS,
G 32, G34, G36, G37,G41, G42, G26,G24 & G22- OK.
|
|
| 09/17/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/15/2026 10:07:27 AM
9/15/2026 10:07 AM Blake Daldegan
Rough Frame inspection low wall girds H-L
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
9/17/2026 1:23:03 PM
PARTIAL-
1) DRYWALL & SCREW INSPECTION 1 LAYER,
STORAGE G38, CORRIDOR G20B, G35,G35A, G33, G28, G29,G27,G25- OK.
2) 1st LAYER OF TWO LAYERS,
G 32, G34, G36, G37,G41, G42, G26,G24 & G22- OK.
|
|
| 09/18/2026 | B:RGH MECH | MARTIN MAGERS | PARTIAL | Final Rough Duct Inspection | 9/17/2026 2:04:01 PM
9/17/2026 2:04 PM COLORADO MECHANICAL SYSTEMS LLC
Rough duct work inspection
Contact Name: Josh Livingston
Site Address: 2360 MEADOWS BLVD
Phone: 7208770061
e-Mail: mrutherfurd@coloradomech.com
9/18/2026 1:00:57 PM
Ducts in Lin 9-14 k-F approved as marketed in blue on M2.1.0
|
|
| 09/23/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Screw inspection & puddy pad inspection | 9/21/2026 2:56:42 PM
9/21/2026 2:56 PM Blake Daldegan
looking at inwall puddy pads in rated walls G44, G60,
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
9/23/2026 11:11:42 AM
G44 electrical boxes puddy pads verified 1 hr rated wall
G60 6 electrical boxes puddy pads approved
G25 - 2 electrical boxes puddy pads approved
|
|
| 09/23/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | Screw inspection & puddy pad inspection | 9/21/2026 2:56:42 PM
9/21/2026 2:56 PM Blake Daldegan
looking at inwall puddy pads in rated walls G44, G60,
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
9/23/2026 12:07:53 PM
PARTIAL-
1) DRYWALL/ SCREW INSPECTION 1 LAYER G44, G10, G30, G43, G60 -OK.
2) DRYWALL/ SCREW 2 LAYERS - G22, G24 & G26- OK.
3) PUTTY PAD FOR RATED ELECTRICAL BOX PROTECTION , G25,G44 & G 60- OK.
|
|
| 09/25/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | Rough Duct Inspection | 9/24/2026 10:22:57 AM
9/24/2026 10:22 AM COLORADO MECHANICAL SYSTEMS LLC
Inspection of the remainder of duct work
Contact Name: Chris Fergin
Site Address: 2360 MEADOWS BLVD
Phone: 2242805105
e-Mail: mrutherfurd@coloradomech.com
9/25/2026 1:14:25 PM
PARTIAL-
1) SEAL & SUPPORT- OK AS MARKED ON PLANS & ATTACHMENT.
|
|
| 09/29/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/28/2026 8:07:41 AM
9/28/2026 8:07 AM Blake Daldegan
Remaining wall screw inspection
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
9/29/2026 10:19:51 AM
PARTIAL-
DRYWALL & SCREW INSPECTION G40 1LAYER - OK.
DRYWALL & SCREW INSPECTION 2ND LAYER CT SIM G 42 - OK.
|
|
| 09/29/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 9/28/2026 1:22:32 PM
9/28/2026 1:22 PM Emmanuel Santana
Hardlids and soffits
Contact Name: Emmanuel Santana
Site Address: 2360 MEADOWS BLVD
Phone: 7207995953
e-Mail: emmanuel.santana@laytonconstruction.com
9/29/2026 2:20:00 PM
Rough electrical hard lids and soffits approved
See electrical reflected ceiling print
|
|
| 09/02/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/1/2026 11:35:47 AM
9/1/2026 11:35 AM Blake Daldegan
Fire rated walls insulation G25, G44, G60
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
10/1/2026 7:20:15 AM
PARTIAL-
1) SECOND LAYER 5/8 TYPE X GYP AT HEAD OF WALL STORAGE G50, CLEANING SUPPLY G44 & CT SIM G42- OK PER DETAIL 38 PAGE A9.2.3
Update: Joe Carbaugh 10/01/26 changed Approved to Partial to correct status of inspection.
|
|
| 10/01/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | Soffit rough frame to close | 9/30/2026 2:56:51 PM
9/30/2026 2:56 PM Blake Daldegan
Soffits only at non-rated partitions
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
10/1/2026 11:31:47 AM
PARTIAL-
1) ALL SOFFITS WITH (NON FIRE SPRINKLERS) - OK.
NOTE: SOFFITS WITH SPRINKLES TO BE INSPECTED AT FUTURE INSPECTION & MUST REMAIN OPEN UNTIL ALL RGH MEP'S, CASTLE ROCK FIRE HAVE BEEN APPROVED & BUILDING INSPECTION CARD HAS BEEN SIGNED.
|
|
| 10/02/2026 | B:ELECTRICAL SERVICE | VINCE RAPONE | APPROVED | eTRAKiT Inspection Request | 10/1/2026 2:05:05 PM
10/1/2026 2:05 PM Mario Mares
Transformers and panels
Contact Name: Mario Mares
Site Address: 2360 MEADOWS BLVD
Phone: 3034827131
e-Mail: mario.mares@duroelectric.com
10/2/2026 10:30:01 AM
Electrical service approved
Panel NHLA fed from SDPL
panel NLLA fed from transformer
Panel CT fed from SDPL
Power conditioner fed from SDPL
Panel and transformer CRLL Fed from CRH
|
|
| 10/07/2026 | B:RGH MECH | MARTIN MAGERS | NOT APPROVED | eTRAKiT Inspection Request | 10/6/2026 2:55:13 PM
10/6/2026 2:55 PM Emmanuel Santana
Hydrolines/chilled water
Contact Name: Emmanuel Santana
Site Address: 2360 MEADOWS BLVD
Phone: 7207995953
e-Mail: emmanuel.santana@laytonconstruction.com
10/7/2026 2:04:13 PM
Inspected chiller lines to the roof units. Pressure must be at 1 1/2 times and not less than 100 psi.
|
|
| 10/08/2026 | B:RGH MECH | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 10/7/2026 2:04:18 PM
10/7/2026 2:04 PM Emmanuel Santana
Hydronic/Chiller
Contact Name: Emmanuel Santana
Site Address: 2360 MEADOWS BLVD
Phone: 7207995953
e-Mail: emmanuel.santana@laytonconstruction.com
10/8/2026 10:36:53 AM
Supply and Return for chiller. All chiller lines compete. Marked in green on M2.2.0
|
|
| 10/14/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 10/13/2026 8:23:39 AM
10/13/2026 8:23 AM Emmanuel Santana
Fire smoke damper frame out
Contact Name: Emmanuel Santana
Site Address: 2360 MEADOWS BLVD
Phone: 7207995953
e-Mail: emmanuel.santana@laytonconstruction.com
10/14/2026 11:16:54 AM
PARTIAL-
1) FRAMING FOR FIRE/ SMOKE DAMPER- OK.
NOTE: PLEASE ATTACH UPDATE / RFI DAMPER FRAMING CHANGES.
|
|
| 10/14/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 10/13/2026 9:50:04 AM
10/13/2026 9:50 AM Emmanuel Santana
Steam and Condensate Lines
Contact Name: Emmanuel Santana
Site Address: 2360 MEADOWS BLVD
Phone: 7207995953
e-Mail: emmanuel.santana@laytonconstruction.com
10/14/2026 2:20:22 PM
Steam and condensate line marked in pink on M2.2.0
Also looked at insulation and labeling of all hard ceilings. Approved and ok to cover.
|
|
| 10/16/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 10/15/2026 12:46:08 PM
10/15/2026 12:46 PM Emmanuel Santana
Line set pressure inspection
Contact Name: Emmanuel Santana
Site Address: 2360 MEADOWS BLVD
Phone: 7207995953
e-Mail: emmanuel.santana@laytonconstruction.com
10/16/2026 12:50:45 PM
All line set pressure tests approved. Marked in orange in M2.2.0
|
|
| 10/20/2026 | B:RGH FRAME | BRETT LONGNECKER | PARTIAL | MEP rough in hardlid framing | 10/19/2026 7:39:10 AM
10/19/2026 7:39 AM Blake Daldegan
Inspection of above ceiling hardlid G41, G37, G36, G34, G43, G25, G10
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
10/20/2026 1:39:22 PM
Hardlids only ok as highlighted in yellow on Town approved plans in A2.1.0.
G37, G36, G34, G25, G43, G12, G11, G41
Hard lid Soffit only in waiting area G10
|
|
| 10/21/2026 | B:RGH MECH | BRETT LONGNECKER | PARTIAL | Above Ceiling HVAC | 10/20/2026 3:21:06 PM
10/20/2026 3:21 PM COLORADO MECHANICAL SYSTEMS LLC
Above Ceiling HVAC inspection for Hardlid areas
Contact Name: Josh Livingston
Site Address: 2360 MEADOWS BLVD
Phone: 7208770061
e-Mail: mrutherfurd@coloradomech.com
10/21/2026 1:11:24 PM
Rough mechanical in hard lids with the following units/areas ok:
Hardlids only ok as highlighted in yellow on Town approved plans in A2.1.0. G37, G36, G34, G25, G43, G12, G11, G41 Hard lid Soffit only in waiting area G10
|
|
| 10/23/2026 | B:RGH FRAME | JON WHITE | CANCEL | eTRAKiT Inspection Request | 10/21/2026 3:20:55 PM
10/21/2026 3:20 PM ANDREW SCOTT - LAYTON
This will be an above ceiling grid inspection for the linac vault and linac control room only. Room G50 and G51
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
10/23/2026 9:32:37 AM
ANDREW CALLED TO CANCEL
|
|
| 10/23/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 10/22/2026 12:34:05 PM
10/22/2026 12:34 PM ANDREW SCOTT - LAYTON
Screw inspection on drywall hard lids in all hard lid rooms (bathrooms and changing rooms).
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
10/23/2026 10:23:09 AM
PARTIAL
1) DRYWALL - OK FOR ALL HARD LIDS.
|
|
| 10/26/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 10/23/2026 10:03:47 AM
10/23/2026 10:03 AM ANDREW SCOTT - LAYTON
This is a reschedule for the above ceiling grid scope in the linac vault and linac control room (rooms G50 and G51). The inspection will review ceiling grid supports as well as any applicable caulking of penetrations, though both rooms are not fire rated. The local fire department is inspecting at 10am. The frame
Contact Name: ANDREW SCOTT - LAYTON
Site Address: 2360 MEADOWS BLVD
Phone: 3093638200
e-Mail: ascott@laytonconstruction.com
10/26/2026 11:16:33 AM
PARTIAL -
1) ABOVE GRID & GRID SUPPORT IN VAULT & LINAC - OK.
NOTE: ALL RGH MEP's , STATE FIRE & CASTLE FIRE HAVE BEEN APPROVED FOR THESE TWO AREAS (ONLY) REST OF GRID & ABOVE GRID TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 10/29/2026 | B:RGH MECH | JOE CARBAUGH | CANCEL | REQUESTED ON INCORRECT PERMIT | 10/28/2026 12:29:45 PM
10/28/2026 12:29 PM COLORADO MECHANICAL SYSTEMS LLC
Fire dampers
Contact Name: Josh Livingston
Site Address: 2360 MEADOWS BLVD
Phone: 7208770061
e-Mail: mrutherfurd@coloradomech.com
|
|
| 11/09/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | Garden Level Inspection | 11/6/2026 8:26:15 AM
11/6/2026 8:26 AM COLORADO MECHANICAL SYSTEMS LLC
Flex inspection and GRD Inspection
Contact Name: Josh Livingston
Site Address: 2360 MEADOWS BLVD
Phone: 7208770061
e-Mail: mrutherfurd@coloradomech.com
11/9/2026 9:07:14 AM
PARTIAL-
1) SUPPLY , RETURNS & FLEX DUCTS - OK HIGHLIGHTED ON PLANS ON SITE.
|
|
| REQUEST PRE CON MEETING | BRETT LONGNECKER | | Preliminary Above Ceiling Inspection | 11/18/2026 2:40:57 PM
11/18/2026 2:40 PM Blake Daldegan
Above Ceiling Inspection for ceiling tile drop
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
|
|
| B:DRYWALL | BRETT LONGNECKER | | Above Ceiling Inspection Ceiling Closure | 11/18/2026 2:40:57 PM
11/18/2026 2:40 PM Blake Daldegan
Above Ceiling Inspection for ceiling tile drop
Contact Name: Blake Daldegan
Site Address: 2360 MEADOWS BLVD
Phone: 7207010814
e-Mail: blake.daldegan@laytonconstruction.com
|
|
| 11/19/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 11/18/2026 1:44:35 PM
11/18/2026 1:44 PM Emmanuel Santana
Ceiling rough in inspection
Contact Name: Emmanuel Santana
Site Address: 2360 MEADOWS BLVD
Phone: 7207995953
e-Mail: emmanuel.santana@laytonconstruction.com
11/19/2026 1:08:12 PM
Above ceiling rough electrical approved
Still need corridor and storage above ceiling to complete rough electrical. ( see reflected ceiling print )
|
|
| B:RGH ELECT | BRETT LONGNECKER | | eTRAKiT Inspection Request | 11/20/2026 12:41:44 PM
11/20/2026 12:41 PM Emmanuel Santana
Overhead rough
Contact Name: Emmanuel Santana
Site Address: 2360 MEADOWS BLVD
Phone: 7207995953
e-Mail: emmanuel.santana@laytonconstruction.com
|
|