| 10/05/2026 | B:RGH ELECT | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 10/2/2026 2:50:24 PM
10/2/2026 2:50 PM LIGHTHOUSE TRANSPORTATION GROUP LLC
Contact Name: Reno
Site Address: 2655 N VALLEY DR
Phone: 7196660680
e-Mail: angela.alvarez@LIGHTHOUSETG.ORG
10/5/2026 12:44:39 PM
Rough electrical inspection not approved
1. One line diagram does not match what is currently installed. Revise and resubmit plans to the town of Castlerock when new plans are uploaded please contact front building counter to schedule this to be reviewed. Currently installed is 100 amp main breaker meter pedestal feeding a subpanel then feeding traffic control cabinet. On current one line shows 30 amp feeding traffic control cabinet 50 is installed. Also, a Lumineers circuit is being pulled out of subpanel, which does not show on the current plans.
2. No underground inspection was completed at this time please pothole three holes to verify depths of conduit from meter pedestal to subpanel to traffic control cabinet.
Notes
Rough electrical installed looks good plans just need to be revised and resubmitted
At next inspection, schedule a underground electrical and rough electrical inspection
Have meter address posted on meter housing at next inspection
|