| 08/27/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | Freshline U/G Plumbing Main | 8/26/2026 7:35:22 AM
8/26/2026 7:35 AM Brad Wiggs
Freshline U/G Plumbing Main
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
8/27/2026 11:34:37 AM
Grease main drains and demo area for fresh area approved. No other branches installed. Marked in green on 9 2 2.
|
|
| 08/31/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | electrical underground | 8/28/2026 2:54:32 PM
8/28/2026 2:54 PM TRICO TWO-TWENTY LLC dba TRICO ELECTRIC
underground electrical
Contact Name: TRICO TWO-TWENTY LLC dba TRICO ELECTRIC
Site Address: 404 COSTCO LN
Phone: 8174445371
e-Mail: TREAVES@TRICOELECTRIC.NET
8/31/2026 12:44:05 PM
Main electrical to electrical #2 trench
4 - 3" pvc 2 pipes to T-2 transformer and 2 pipes to panel H7
1 - 2-1/2" panel H2
1 - 2" panel H8
Okay to bury trench only
Schedule underground when these pipes are stubbed up at both ends
|
|
| 08/31/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 8/28/2026 6:52:49 PM
8/28/2026 6:52 PM Brad Wiggs
Office Core restrooms, employee breakroom and Recieving U/G Waste and Drain partial
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
8/31/2026 2:33:14 PM
Main bath, family bath, office, optical and pharmacy. Approved , marked in green on P 2.1,except for the last 5 ft to the north, marked in dashed orange.
Sand waste under Ground for scrubber pit and water raiser room, marked in pink, approved up GP 5 ft from grid line 10. Marked in pink on P2.2
|
|
| 09/03/2026 | B:RE ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | MSB and switchgear underground rough-in | 9/1/2026 12:55:27 PM
9/1/2026 12:55 PM Brad Wiggs
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/2/2026 11:58:49 AM
9/2/2026 11:58 AM Brad Wiggs
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/3/2026 1:49:12 PM
MSB to MDP
Electrical underground approved
See electrical online on stamped set of prints
|
|
| 09/09/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | Room #145 U/G Electrical Rough-in | 9/8/2026 1:32:47 PM
9/8/2026 1:32 PM Brad Wiggs
Front-of-House Electrical Room Rough-in
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/9/2026 2:16:14 PM
Electrical room
Low volt stubs - it room
Low volt - AT&T stubs into electrical room 3 - 3"
Panels H2 H7 H8 C C1
Transfer T3 feeds C and C1
T2 feeds SD-1
P9A and P9B food service panels
P8 - 2-1/2"
See one line page for highlights
|
|
| 09/10/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | Freshline U/G Plumbing Waste Rough-in | 9/9/2026 6:17:51 PM
9/9/2026 6:17 PM Brad Wiggs
Meat Dept, Rotisserie, Chicken Prep, and Deli U/G
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/10/2026 12:54:57 PM
Lateral stub ups for deli, Rotisserie, Chicken Prep, Meet Dept (vent for hand sink incomplete, Hand sink and floor drain for the bakery, marked in BLE on P 2.2
|
|
| 09/11/2026 | B:GROUND PLUMBING | COLBY RIGGINS | PARTIAL | Bakery U/G Waste Lateral Rough-in | 9/11/2026 6:15:52 AM
9/11/2026 6:15 AM Brad Wiggs
PM inspection request if schedule allows
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/11/2026 12:54:47 PM
Lateral stub ups for bakery, Hand sink and floor drain for the bakery, marked in yellow on P 2.2
|
|
| 09/14/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | In-wall Electrical Rough-In | 9/13/2026 5:34:37 PM
9/13/2026 5:34 PM Brad Wiggs
Loading Dock and Trash Compactor CIP in wall electrical rough-in
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/14/2026 1:30:10 PM
In wall electrical loading dock - 4 lights
2 - 3" sleeves for ex fans
1- 1"sleeve disconnect
|
|
| 09/14/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | U/G Plumbing Rough-in | 9/13/2026 5:38:52 PM
9/13/2026 5:38 PM Brad Wiggs
Receiving Restrooms and Tire Center U/G Plumbing Rough-in
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/14/2026 2:09:27 PM
Tire area bath floor drain and 4" stack to mezzanine under ground plumbing approved, marked on P2.2 in orange.
2 delivery baths and drinking fountain underground plumbing approved, marked on page P2.2 in orange.
|
|
| 09/16/2026 | B:GROUND PLUMBING | COLBY RIGGINS | PARTIAL | Food Service UG Plumbing Rough-in | 9/15/2026 5:07:04 PM
9/15/2026 5:07 PM Brad Wiggs
Food Service UG Plumbing Rough-in
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/16/2026 2:56:57 PM
Service section area includes drains, clean outs, and hand sinks marked in dark blue on pg P 2.1.
Domestic cold water stub up, 3 inch pipe marked in dark blue on pg P 1.1
|
|
| 09/21/2026 | B:UFER | SHAWN VALENZUELA | NOT APPROVED | Ufer Ground (MSB Room GL-11) | 9/17/2026 4:53:45 PM
9/17/2026 4:53 PM Brad Wiggs
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/21/2026 11:51:40 AM
Ufer inspection not approved
1. Ufer is incomplete not ready at time of inspection
Reschedule inspection when ready
|
|
| 09/22/2026 | B:UFER | VINCE RAPONE | APPROVED | Ufer Ground Inspection Request | 9/21/2026 2:39:56 PM
9/21/2026 2:39 PM Brad Wiggs
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/22/2026 1:27:15 PM
Ufer ground approved
See detail E8-17
|
|
| 09/23/2026 | B:GROUND PLUMBING | MARTIN MAGERS | APPROVED | | 9/22/2026 10:34:33 AM
9/22/2026 10:34 AM Brad Wiggs
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/23/2026 10:36:55 AM
Underground plumbing for scrub pit area, approved.
Marked in green on P2.2.
|
|
| 09/23/2026 | PRE CON INSPECTION | JON WHITE | APPROVED | 8:00am at Site Trailer | 9/2/2026 1:37:37 PM
9/2/2026 1:37 PM Brad Wiggs
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/23/2026 11:31:18 AM
Pre-Con Completed
|
|
| 09/23/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | CIP Loading Dock In-Wall Rough-in | 9/22/2026 6:42:05 PM
9/22/2026 6:42 PM Brad Wiggs
P.M. Inspection request if schedule allows
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
9/23/2026 12:37:47 PM
Rough electrical inspection partial
Loading dock, in wall dock indicator lights and raceways
3/4 pvc conduit
5 in wall boxes exterior facing
|
|
| 10/16/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | U/G Serpentine piping for POS freezers | 10/16/2026 6:19:03 AM
10/16/2026 6:19 AM Brad Wiggs
PM inspection request if schedule allows
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
10/16/2026 2:55:32 PM
Serpentine piping for warming of the freezers approved.
|
|
| 10/19/2026 | B:GROUND PLUMBING | BRETT LONGNECKER | PARTIAL | Remaining WHSE U/G Plumbing and RD Tiein | 10/16/2026 6:18:16 PM
10/16/2026 6:18 PM Brad Wiggs
Bakery U/G Waste, Remaining Office Core Waste, GL 11 Roof Drain Tie In
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
10/19/2026 10:15:41 AM
All interior underground plumbing within building footprint complete.
|
|
| 10/20/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | GL 11 Roof Drain Utility Tie-in | 10/19/2026 4:16:55 PM
10/19/2026 4:16 PM Brad Wiggs
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
10/20/2026 11:55:12 AM
10" Storm water tie in. Marked in green on P 1.1
|
|
| 10/22/2026 | B:GROUND PLUMBING | MARTIN MAGERS | APPROVED | East Roof Drain Utility Tie-In | 10/21/2026 8:00:57 PM
10/21/2026 8:00 PM Brad Wiggs
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
10/22/2026 1:46:50 PM
all east side storm drains complete.
|
|
| 10/23/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 10/22/2026 9:19:58 AM
10/22/2026 9:19 AM TRICO TWO-TWENTY LLC dba TRICO ELECTRIC
Walker Duct
Contact Name: TRICO TWO-TWENTY LLC dba TRICO ELECTRIC
Site Address: 404 COSTCO LN
Phone: 8174445371
e-Mail: TREAVES@TRICOELECTRIC.NET
10/23/2026 12:01:00 PM
Rough electrical partial approved
Note
Walker duct inspection
Walker duct feeding cash wrap from grid line C .75 to grid line D noted on plans which walker duct was inspected at this time to be extended and further inspected. Walker duct enters 2 junction boxes west side of grid line C .75 three raceways are part of Walker duck inspection 2 are for power one is for data to be encased in concrete.
|
|
| 10/28/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 10/27/2026 11:37:22 AM
10/27/2026 11:37 AM TRICO TWO-TWENTY LLC dba TRICO ELECTRIC
WALKER DUCT
Contact Name: TRICO TWO-TWENTY LLC dba TRICO ELECTRIC
Site Address: 404 COSTCO LN
Phone: 8174445371
e-Mail: TREAVES@TRICOELECTRIC.NET
10/28/2026 2:34:09 PM
Rough electrical partial inspection approved
Notes
Walker duct inspection grid line B .75 to D cash registers
Walker duct inspection grid line B.5 to B.2 member services counter 2 pvc to be extended up wall 1 power 1 data
Highlighting on plans e-2 what was inspected at this time
|
|
| 10/29/2026 | B:GROUND PLUMBING | BRETT LONGNECKER | PARTIAL | Tire Center and Office Core Sewer Tie-in | 10/28/2026 6:59:27 PM
10/28/2026 6:59 PM Brad Wiggs
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
10/29/2026 4:55:20 PM
Storm drain tie in's outside of building on west side ok.
|
|
| 11/04/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 11/3/2026 7:05:01 AM
11/3/2026 7:05 AM TRICO TWO-TWENTY LLC dba TRICO ELECTRIC
Floor boxes in Optical
Contact Name: TRICO TWO-TWENTY LLC dba TRICO ELECTRIC
Site Address: 404 COSTCO LN
Phone: 8174445371
e-Mail: TREAVES@TRICOELECTRIC.NET
11/4/2026 11:33:12 AM
Rough electrical inspection partial approved
Notes
Floor boxes for optical kiosk power and data 7 floor boxes total 1 1/4 power conduit 1in data conduit
Highlighted on plans e-4 what was inspected at this inspection
|
|
| 11/09/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | NOT APPROVED | Courtesy Consultation | 11/7/2026 2:56:16 PM
11/7/2026 2:56 PM Clark Scholl
Electrical
Contact Name: Clark Scholl
Site Address: 404 COSTCO LN
Phone: 5097241386
e-Mail: cscholl@lydig.com
11/9/2026 12:21:21 PM
Courtesy inspection only
Discussed where relock can be ran in ceiling due to building not being fully dried in
Discussed with general contractor and electrical contractor stay 30 feet away from any opening of wall
South wall is still incomplete highlighted on plans e-2 where relock can not be installed from grid line c to 7.6
Discussed with general contractor and electrical contractor wire from main electrical room cannot be pulled until electrical room is fully dried in if wire is rated for a wet location in this note does not apply
Please note at end of each day if temporary plastic has been removed from walls that are open to elements plastic walls be reinstalled by end of day
|
|
| 11/09/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Framing at Machine Room | 11/7/2026 2:57:17 PM
11/7/2026 2:57 PM Clark Scholl
For top out sheetrock application
Contact Name: Clark Scholl
Site Address: 404 COSTCO LN
Phone: 5097241386
e-Mail: cscholl@lydig.com
11/9/2026 1:55:02 PM
PARTIAL-
1) RGH WALL FRAMING FOR GRID LINE 10 THROUGH D.8 & RGH FRAME ONLY FOR MECH PLATFORM WALLS.
NOTE: FIRE RATED ASSEMBLIES TO BE LOOKED AT FUTURE INSPECTION.
|
|
| 11/10/2026 | B:DRYWALL | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 11/9/2026 12:19:49 PM
11/9/2026 12:19 PM Clark Scholl
Inspection request if for screw pattern and spacing fro the rated wall assembly on the east side of 10 Line separation wall
Contact Name: Clark Scholl
Site Address: 404 COSTCO LN
Phone: 5097241386
e-Mail: cscholl@lydig.com
11/10/2026 3:24:15 PM
NOT APPROVED-
1) NEED CLARIFICATION FROM ARCHITECT OF RECORD WHETHER MECHANICAL ROOM & FIRE ROOM TO MAIN WAREHOUSE IS A RATED WALL OR JUST THE SEPARATION WALL BETWEEN THE TWO ROOMS IS RATED?
|
|
| 11/12/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Core electrical wall framing | 11/11/2026 5:50:35 PM
11/11/2026 5:50 PM Brad Wiggs
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
11/12/2026 10:18:17 AM
PARTIAL-
1) ELECTRICAL ROOM 145 OK , SEE NOTE BELOW. DEMISING WALL AT GEID LINE D .4 , COOLER 183 / MPU 154 & GRID LINE 10 G THROUGH D.4 - OK.
NOTE: HOLD DOWNS & HEADER FRAMING IN ELECTRICAL ROOM 145 TO BE CHECKED AT FUTURE RGH FRAME INSPECTION.
|
|
| 11/12/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | Screw Pattern for Food Service | 11/12/2026 10:18:20 AM
PARTIAL-
1) DRYWALL & SCREW INSPECTION FOR DEMIZING WALL AT MPU 154, FOOD PREP 184 & GRID LINE 10 - OK.
NOTE: PLAN PAGE A512 NEEDS TO BE UPDATED & SUBMITTED FOR TOWN REVIEWED FOR REMOVAL OF NOTATION 1-HOUR FIRE-RATED WALLS UL LISTING 419.
|
|
| 11/16/2026 | B:ROUGH FRAME | JOE CARBAUGH | NOT APPROVED | Office Restrooms, Tire Center, GL 10 | 11/13/2026 12:05:05 PM
11/13/2026 12:05 PM Brad Wiggs
-Office core gang restrooms, janitors, and family restroom
-Tire Center demising wall and restroom
-Sales floor GL 10 demising wall screw pattern
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
11/16/2026 1:51:13 PM
NOT APPROVED-
1) MISSING BOTTOM STUD CONNECTION TO BOTTOM TRAC. / TIRE STORAGE AREA 166, TIRE INSTALLATION 162 & BARRIER RESTROOM 165.
2) MISSING BOTTOM TRAC CONNECTION/ TIRE STORAGE AREA 166, TIRE INSTALLATION 162 & BARRIER RESTROOM 165.
3) RGH FRAME FOR WOMEN'S/ MEN'S RESTROOM, VESTIBULE 141, JANITOR 144 & VESTIBULE 141 RGH FRAME -OK.
4) L FLOOR CHANNEL CONNECTION FOR COOLER PANELS- OK.
|
|
| 11/18/2026 | B:RE ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 11/17/2026 7:28:30 AM
11/17/2026 7:28 AM TRICO TWO-TWENTY LLC dba TRICO ELECTRIC
ROUGH IN WALLS RR TO TIRE SHOP
Contact Name: TRICO TWO-TWENTY LLC dba TRICO ELECTRIC
Site Address: 404 COSTCO LN
Phone: 8174445371
e-Mail: TREAVES@TRICOELECTRIC.NET
11/18/2026 11:01:44 AM
Rough electrical inspection partial approved
Notes
Restrooms' walls and ceiling, family restrooms' walls and ceiling. Mpu room walls and ceiling highlighted on plans e4
Junction boxes to be accessible above restrooms ceiling verify at final. Bathroom exhaust fan power located on the rooftop.
Approved with conditions continue at own risk
Provide clarification of note on plan set E7 note one. What conduits are required to be rigid. in wall, surface mount, and height requirements
Tire center east wall, 6in wall with 6 1in conduits and 1 3/4 conduit to be extended into 4 in wall recall inspection when ready.
Highlighted on plans e7
|
|
| 11/18/2026 | B:RE ROUGH FRAME | JOE CARBAUGH | PARTIAL | Rough Frame | 11/18/2026 5:32:41 AM
11/18/2026 5:32 AM Brad Wiggs
Tire Install Demising Wall, GL 10 Insulation/Pre-Rock, Fire Pump room/Mechanical room demising wall and Fire Pump/MSB room demising wall rough frame
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
11/18/2026 12:35:23 PM
PARTIAL-
1) RE-ROUGH FRAME FOR TIRE CENTER- OK.
2) REST OF RGH FRAME HIGHLIGHTED ON PLANS FOR 11-18-26 ON PICTURE IN INSPECTION PHOTOS FILE.
|
|
| 11/18/2026 | B:ROUGH PLUMBING | BRETT LONGNECKER | PARTIAL | Office Core Restrooms In-wall/OH Rough | 11/18/2026 5:26:37 AM
11/18/2026 5:26 AM Brad Wiggs
Office Core Restrooms In-Wall/OH Rough
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
11/18/2026 2:53:00 PM
Verified support and piping of water and sanitary in wall rough within restrooms and office spaces.
Still need to inspect on test and hot water piping insulation.
|
|
| 11/19/2026 | B:RE ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | Office Core Restrooms | 11/19/2026 5:26:40 AM
11/19/2026 5:26 AM Brad Wiggs
Office Core Restrooms In-Wall and OH Rough
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
11/19/2026 2:38:04 PM
Bathroom area approved in wall and ceiling for water and DWV, pending insulation. Also water only to all areas to the east, including exam areas for eye center hearing center and pharmacy.. Marked in orange on P 5.1 Ms P 3.1 Note change in eye exam with future sing and only cold water to center sink.
|
|
| 11/20/2026 | B:ROUGH MECHANICAL | MARTIN MAGERS | CANCEL | Exhaust Fan Duct at Restrooms | 11/19/2026 5:08:44 PM
11/19/2026 5:08 PM Clark Scholl
At Hard Lid locations (Mens, Womens, Family)
Contact Name: Clark Scholl
Site Address: 404 COSTCO LN
Phone: 5097241386
e-Mail: cscholl@lydig.com
11/20/2026 1:02:18 PM
Work not ready.
|
|
| 11/20/2026 | B:DRYWALL | MARTIN MAGERS | PARTIAL | Screw pattern/spacing for sheetrock | 11/19/2026 5:06:53 PM
11/19/2026 5:06 PM Clark Scholl
Tire Center to Sales Floor sheetrock attachment
Contact Name: Clark Scholl
Site Address: 404 COSTCO LN
Phone: 5097241386
e-Mail: cscholl@lydig.com
11/20/2026 1:02:20 PM
High drywall above tire center bathroom approved. Marked on green on A101.
|
|
| 11/20/2026 | B:GAS PIPE AIR TEST | MARTIN MAGERS | PARTIAL | Gas Pressure Test for Green Tag | 11/19/2026 11:15:18 AM
11/19/2026 11:15 AM Brad Wiggs
Gas Pressure Test and Office Core Insulation Inspection
Contact Name: Brad Wiggs
Site Address: 404 COSTCO LN
Phone: 5092510811
e-Mail: bwiggs@lydig.com
11/20/2026 1:02:23 PM
Gas pipe air test and supports approved for main gas system. Ok to energize gas pipe and activate meter.
Only main pipes, still missing stub outs to all RTUs, and tire center and branches to front and dock heaters.
|
|
| B:ROUGH MECHANICAL | BRETT LONGNECKER | | eTRAKiT Inspection Request | 11/20/2026 2:25:37 PM
11/20/2026 2:25 PM Clark Scholl
In wall plumbing insulation at restrooms; Overhead duct at restroom hard lid locations - Early PM or late AM would be preferred if possible. Thank you
Contact Name: Clark Scholl
Site Address: 404 COSTCO LN
Phone: 5097241386
e-Mail: cscholl@lydig.com
|
|
| B:ROUGH PLUMBING | BRETT LONGNECKER | | eTRAKiT Inspection Request | 11/20/2026 2:25:37 PM
11/20/2026 2:25 PM Clark Scholl
In wall plumbing insulation at restrooms; Overhead duct at restroom hard lid locations - Early PM or late AM would be preferred if possible. Thank you
Contact Name: Clark Scholl
Site Address: 404 COSTCO LN
Phone: 5097241386
e-Mail: cscholl@lydig.com
|
|