| 02/10/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 2/9/2026 11:38:55 AM
2/9/2026 11:38 AM Gordon Galbraith
1st floor z-clips prior to spray fireproofing
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
2/10/2026 2:36:57 PM
RGH FRAME - ( PARTIAL) LOOKED AT 1ST FLOOR AT Z- CLIPS FIRST FLOOR TOP OF WALL STUD CONNECTIONS BEFORE FIREPROOFING.
|
|
| 02/26/2026 | B:DRYWALL | BRETT LONGNECKER | NOT APPROVED | Consult Inspection | 2/25/2026 1:13:41 PM
2/25/2026 1:13 PM Braden Frey
Drywall Top-out for interior first floor hallways
Contact Name: Braden Frey
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035183298
e-Mail: bmfrey@tcco.com
2/26/2026 1:00:29 PM
Consult inspection only.
Discussed one siding top portions of interior walls for MEP trades to begin installing along walls.
Drywall inspections only needed for fire rated walls.
|
|
| 03/03/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/2/2026 1:20:06 PM
3/2/2026 1:20 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/3/2026 3:42:47 PM
FIRST FLOOR FRAME—
1) STAFF ROOM 112- EAST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
2) BARIATRIC 117 - NORTH WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
3) EXAM ROOM 125 - NORTH & SOUTH INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
4) TRAUNA 127- NORTH & SOUTH INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
5) AMBULANCE VESTIBULE 128- NORTH & SOUTH INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
6) X - RAY ROOM 126 - NORTH & SOUTH INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
7) CONTROL ROOM 121 - NORTH, SOUTH & EAST WALL, NORTH & SOUTH INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
8) CT ROOM 115 - EAST, NORTH WALL, INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
9) STORAGE 111 - EAST & WEST WALL, INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
10) SLEEP 109 - WEST WALL, INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
FIRST FLOOR FRAME— PAGE 2
11) CT TLT 115A - NORTH & SOUTH WALLS, 1) STAFF ROOM 112- EAST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
12) MGR OFFICE 159 - NORTH WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
13) EVS 157A - SOUTH & WEST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
14) CORRIDOR 144 EAST SIDE ONLY - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
15) WAITING 101 - SOUTH & WEST WALLS MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
16) CORRIDOR 108 - NORTH , SOUTH , EAST & WEST WALLS - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
17) CORRIDOR 116 - EAST & WEST WALLS (EXCLUDING FIRE RATED ROOM 116) - OK.
NOTE: RATED WALLS TO BE CHECKED AT FUTURE INSPECTION.
12) MGR OFFICE 159 - NORTH WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
13) EVS 157A - SOUTH & WEST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
14) CORRIDOR 144 EAST SIDE ONLY - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
15) WAITING 101 - SOUTH & WEST WALLS MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
16) CORRIDOR 108 - NORTH , SOUTH , EAST & WEST WALLS - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
17) CORRIDOR 116 - EAST & WEST WALLS (EXCLUDING FIRE RATED ROOM 116) - OK.
NOTE: RATED WALLS TO BE CHECKED AT FUTURE INSPECTION.
3/3/2026 3:52:18 PM
FIRST FLOOR ROOF FRAME? PAGE 2
11) CT TLT 115A - NORTH & SOUTH WALLS, 1) STAFF ROOM 112- EAST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
12) MGR OFFICE 159 - NORTH WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
13) EVS 157A - SOUTH & WEST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
14) CORRIDOR 144 EAST SIDE ONLY - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
15) WAITING 101 - SOUTH & WEST WALLS MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
16) CORRIDOR 108 - NORTH , SOUTH , EAST & WEST WALLS - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK.
17) CORRIDOR 116 - EAST & WEST WALLS (EXCLUDING FIRE RATED ROOM 116) - OK.
NOTE: RATED WALLS TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 03/05/2026 | B:RGH MECH | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 3/4/2026 2:18:37 PM
3/4/2026 2:18 PM Gordon Galbraith
Contact Name: Patrick Hughes
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035197973
e-Mail: ggalbraith@tcco.com
3/5/2026 2:21:14 PM
Fire dampers in 1 st floor as marked in pink on plans M2.11B.1 and M2.11A.1
|
|
| 03/05/2026 | B:RGH FRAME | MARTIN MAGERS | PARTIAL | | 3/5/2026 2:21:17 PM
Fire damper framing as marked in green on plans M2.11B.1 and M2.11A.1
|
|
| 03/09/2026 | B:RGH MECH | MARTIN MAGERS | PARTIAL | Fire Damper Framing Inspection | 3/6/2026 11:21:46 AM
3/6/2026 11:21 AM COLORADO MECHANICAL SYSTEMS LLC
Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035197973
e-Mail: AR@COLORADOMECH.COM
|
|
| 03/10/2026 | B:DRYWALL | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 3/9/2026 3:24:20 PM
3/9/2026 3:24 PM Gordon Galbraith
1st floor, one side screw inspection rated walls.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/10/2026 2:06:15 PM
(TOP OF WALL DRYWALL) SCREW INSCRIPTION AT RATED WALLS (ONE SIDE ONLY.)
INTERIOR DRYWALL SCREW INSPECTION EXTERIOR SIDE OF WALLS
1) WAITING 101 , RECEPTION 102- OK.
INTERIOR DRYWALL SCREW INSPECTION INSIDE OF 1 HR RATED WALLS OF CT ROOM- OK.
1) TLT 155A, CT 115 - OK.
2) BARIATRIC 117 NORTH FACE 1HR RATED WALL - OK.
3) X-RAY 126 EAST TOW -OK.
1) CORRIDOR 116 NORTH FACE HALLWAY 1HR RATED WALL- OK.
2) CORRIDOR SIDE OF EQUIPMENT ROOM 157 -OK..
3) CORRIDOR 144 EXTERIOR/ WEST SIDE- PATCH HOLE AT ED LAB 147, ( ITEM TO BE CORRECTED).
4) CORRIDOR 137 SOUTH WALL - OK.
5) CORRIDOR, 116 EAST FACE WALL - TI - OK.
NOTE: GREEN HIGHLIGHTED INDICATES WHICH SIDE OF INTERIOR RATED WALL WAS LOOKED AT & RED HIGHLIGHTED AREA NOTED CORRECTION.
|
|
| 03/11/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/10/2026 4:10:34 PM
3/10/2026 4:10 PM Gordon Galbraith
1st floor Frame - Rated Walls
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/11/2026 3:04:40 PM
1 HR SMOKEBARRIER 1Ab FRAMING HEAD OF WALL FOR 1 HR FIRE RATED TI INSPECTION
1) EXAM/TRIAGE 156 & WAITING 101- OK.
2) MGR OFFICE 159 TO CT TLT 115A EAST WALL- OK.
3) CT TLT 115A / WORK 104 SOUTH WALL – OK.
4) WORK 104 / CT 115 WALL – OK.
5) CT 115 / CORRIDOR 105 – MISSING SCREWS AT TOP OF WALL.
6) CT 115/ CORRIDOR 108 – OK.
7) BARIATRIC 117 / STORAGE 114 & STAFF TLT 113 – OK.
1 HR FIRE BARRIER 1Aa FRAMING HEAD OF WALL FOR 1 HR FIRE RATED TI INSPECTION
1) EQPT/LINEN 157 – ALL WALLS - NORTH,SOUTH,EAST & WEST WALLS – OK.
1 HR FIRE BARRIER 1Aa FRAMING HEAD OF WALL FOR 1 HR FIRE RATED TI INSPECTION
1) CORRIDOR 144 AT SOILED 145 , PAT TLT 146 & ED LAB 147 – OK.
2) ED LAB 147 / PAT TLT 146 MID WALL – OK. Note: SEPERATION WALL BETWEEN PAT TLT 146 & SOILED 145 TO BE INSPECTED AT FUTURE INSPECTION.
3) ED LAB 147 / CLEAN 135 WALL – OK.
4) ED LAB 147 / CLEAN 135 , PAT TLT 146 / CLEAN 135, CLEAN 135 / SOILED 145 WALL – OK.
5) CORRIDOR 137 / SOILED 145, CLEAN 135 & MED PREP 134 – OK.
6) CORRIDOR 116 & MED PREP 134 WALL – OK.
3/11/2026 3:10:05 PM
(TOP OF WALL DRYWALL) FRAMING INSECTION AT RATED WALLS (ONE SIDE ONLY.)
|
|
| 03/13/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/12/2026 3:42:39 PM
3/12/2026 3:42 PM Gordon Galbraith
2nd floor TI - non-rated top of wall frame inspection
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/13/2026 2:07:02 PM
(TOP OF WALL FRAME 2nd FLOOR SOUND WALLS)
1) SHELL SPACE 1 - OK.
2) CORRIDOR, 233 EAST WALL - OK.
3) LAD TLT 235 & LAB 234 SOUTH & WEST WALL - OK.
4) CORRIDOR 233 NORTH WALL TO WAITING ROOM 202 - OK.
5) WAITING ROOM 202 / EXAM 232 SEPARATION WALL- OK.
6) RECEPTION 204 / EXAM 232 SEPARATION WALL - OK.
7) RECEPTION 204 / ADMIN WORK 205 - OK.
8) CORRIDOR 206 NORTH & SOUTH WALL - OK.
9) CORRIDOR 216 WEST WALL - OK
10) CORRIDOR 216 SOUTH END WALL - OK.
11) CORRIDOR 216 EAST WALL & MA STATION 223 EAST - OK - TOP MINERAL WOOL INSTALLED.
12) PHONE BANK 213 ALL WALLS - OK.
13) EXAM 225 ALL WALLS - OK.
14) CLEAN SUPPLY 249 , SOILED 253 & EXAM 247 SEPARATION WALL - OK.
15) EXAM 244 SEPARATION WALL & CORRIDOR 233 SEPARATION WALL - OK.
16) CORRIDOR 224 NORTH WALL - OK.
|
|
| 03/18/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/17/2026 7:44:19 PM
3/17/2026 7:44 PM Gordon Galbraith
Witness head of wall UL install - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/18/2026 3:57:04 PM
TOP OF WALL CLIPS BEFORE SFRM - PARTIAL-
1) DETAIL HEAD OF WALL HW-D-0652 - CORRIDOR - 105 - OK.
2) DETAIL HEAD OF WALL HW-D-0652 - CT TLT 115A - OK.
****3) CLIPS - DETAILS HW-D-0252 & HW-D- 0617 - EQPT/LINEN 157 - EJ- NOT APPROVED- PENDING ENGINEERING & TOWN REVIEW. *****
****4) CLIPS - DETAILS HW-D-0252 & HW-D- 0617 - CORRIDOR 144, 137,& 116. EJ- NOT APPROVED- PENDING ENGINEERING & TOWN REVIEW. *****
|
|
| 03/19/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | NOT APPROVED | TOP OF WALL CLIPS BEFORE SFRM | 3/18/2026 2:25:09 PM
3/18/2026 2:25 PM Gordon Galbraith
Head of wall UL conditions - 1st floor - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/19/2026 2:54:51 PM
1) ***** CORRIDOR 108 1HR RATED CLIPS AT TOP OF WALL OF CT 115 WEST WALL- (EJ- NOT APPROVED- PENDING ENGINEERING & TOWN REVIEW.) *****
|
|
| 03/19/2026 | B:RGH FRAME | JOE CARBAUGH | NOT APPROVED | FRAME FOR TOP OF WALLS | 3/18/2026 2:24:14 PM
3/18/2026 2:24 PM Gordon Galbraith
Remaining in-fill framing - 1st floor - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/19/2026 2:54:54 PM
1) ISO EXAM 118 NORTH & SOUTH TOP OF WALL RGH FRAME - OK.
2) ISO TLT 119 EAST WALL TOP OF WALL RGH FRAME - OK.
3) MATERIALS MANAGEMENT RECEIVING 132 NORTH WALL -OK.
4) EMS LOUNGE 129 & STAFF TLT 131 PARTITION WALL-OK.
5) PAT TLT 146 & SOILED 245 PARTITION WALL - OK
6) EXAM 148- EXAM 152 - TOP OF WALL OF DEMISE WALLS - OK.
7) OBSERVATION ROOM 153 - TOP OF WALL OF DEMISE WALLS - OK.
8) EXAM 154 - EXAM ROOM 156 - TOP OF WALL OF DEMISE WALLS - OK.
9) PAT TLT 158 & MGR OFFICE 159 - TOP OF WALL OF DEMISE WALLS - OK.
NOTE: MINERAL WOOL ABOVE TOP OF INSPECTION WALLS ABOVE - OK.
|
|
| 03/24/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/23/2026 6:15:53 PM
3/23/2026 6:15 PM Gordon Galbraith
Top of wall UL & screws on rated assemblies - 1st floor - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/24/2026 2:55:07 PM
1)BARIATRIC 117 - BEAM POCKET- OK PER HW-D-0594.
2) BARIATRIC 117 - HEAD OF WALL - OK PER HW- D-0587.
3) BARIATRIC 117 - JOINT SYSTEMS - OK PER HW-D-0420.
1)STAFF TLT 113/ STORAGE 114 T.O.W U465 DRYWALL/ SCREW INSPECTION OPPOSITE SIDE- OK.
2)CORRIDOR 108 NORTH DOORS DRYWALL/SCREW INSPECTION & ANGLER SPACE FOR AIR DUCT- OK.
3) CORRIDOR 108/ 105 & WORK 104 WEST & SOUTH WALLS - OK.
4) *****EQPT/LINEN 157 HEAD OF WALL DRYWALL SCREW INSPECTION- OK S/E , N/E CORNERS & BEAM POCKET TO BE CHECKED AT FUTURE INSPECTION.****
4)SOILS 145 HEAD OF WALL OPPOSITE SIDE DRYWALL SCREW INSPECTION- OK.
5) PAT TLT 146 HEAD OF WALL DRYWALL SCREW INSPECTION ALL WALLS - OK.
6)***** (TI) PORTION OF ED LAB 147 NORTH & EAST SIDE HEAD OF WALL - OK. *****
7) ***** (TI) PORTION OF MED PREP 134 / CLEAN 135 - OK. *****
|
|
| 03/25/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 3/24/2026 2:20:07 PM
3/24/2026 2:20 PM Gordon Galbraith
Top of wall UL - 1st Floor - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/25/2026 11:38:45 AM
(LISTING XHBN.HW-D-0587 HEAD OF WALL / BEAM POCKET MINERAL WOOL& DRYWALL)
1) X-RAY 126 / EQPT/LINEN 157 HEAD OF WALL / BEAM POCKET MINERAL WOOL - OK.
2) MEP PREP 134, CLEAN 135 , SOILED 145, PAT TLT 146 & ED LAB 147 HEAD OF WALL / BEAM POCKET MINERAL WOOL - OK.
3) PAT TLT 146 HEAD OF WALL / BEAM POCKETS MINERAL WOOL - OK.
4) CORRIDOR 144 N/E & N/W CORNER HEAD OF WALL / BEAM POCKETS MINERAL WOOL - OK.
HW-D-0377 WAITING 101 SOUTH HEAD OF WALL MINERAL WOOL - OK.
1) 3B & 3C AT HEAD OF WALL , AS200 ELASTOMERIC SPRAY- OK PER HW-D-0377.
3/25/2026 1:57:20 PM
DUPLICATE INSPECTION.
|
|
| 03/26/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 3/25/2026 3:09:52 PM
3/25/2026 3:09 PM Gordon Galbraith
1st floor top of wall UL systems - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/26/2026 9:08:45 AM
HW-D-0252, HW-D-0617 HEAD OF WALL MINERAL WOOL & AS 200 SRAY WITNESSES INSPECTION.
1) CORRIDOR 144 at EQPT/LINEN 157
2) SOILED 145 - NORTH & EAST HEAD OF WALLS- OK.
1) BARIATRIC 117- NORTH & EAST ROUGH FINISHED HEAD OF WALL & BEAM POCKET - OK.
|
|
| 03/27/2026 | B:FIRE SMOKE RESIST | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 3/26/2026 3:18:05 PM
3/26/2026 3:18 PM Gordon Galbraith
1st Floor Head of wall UL - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/27/2026 1:18:51 PM
1st floor head of wall at med prep and clean room, and soiled and pat toilet, and med lab rooms and surrounding corridors .
A. Inspected mineral wool forming material as described in #5 HW-D-0252, HW-D-0617..
B FAS strap at clean room 135, mineral wool at flutes HW-D-0420
|
|
| 03/31/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/30/2026 3:36:28 PM
3/30/2026 3:36 PM Kelly Sherman
First Floor RC Channel - Brian E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
3/31/2026 9:05:57 AM
RC CHANNEL 24" ON CENTER OAF- FULL HEIGHT SOUND PARTITION F-
1) CORRIDOR 144 EAST SIDE RC CHANNEL-OK EXAM 148 - EXAM 152
2) EXAM 148- OBSERVATION ROOM 153- OK.
3) EXAM 154- EXAM/TRIAGE 156- OK.
4) ISO EXAM 118 - OK.
5) EXAM - 125 - OK.
3/31/2026 9:53:37 AM
RC CHANNEL 24" ON CENTER OAF- FULL HEIGHT SOUND PARTITION F-
1) CORRIDOR 144 EAST SIDE RC CHANNEL-OK EXAM 148 - EXAM 152
2) EXAM 148- OBSERVATION ROOM 153- OK.
3) EXAM 154- EXAM/TRIAGE 156- OK.
4) ISO EXAM 118 - OK.
5) EXAM - 125 - OK.
|
|
| 03/31/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/30/2026 3:35:20 PM
3/30/2026 3:35 PM Kelly Sherman
Level 1 Head of Wall UL System - Brian E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
3/31/2026 9:06:00 AM
SPEC SEAL AS 200 SRAY
1) CORRIDOR 144, 137& 116- OK.
2) MED PREP 134/ CLEAN 135 / ED LAB 147 - OK.
3/31/2026 9:53:40 AM
SPEC SEAL AS 200 SRAY
1) CORRIDOR 144, 137& 116- OK.
2) MED PREP 134/ CLEAN 135 / ED LAB 147 - OK.
|
|
| 04/02/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/1/2026 3:28:12 PM
4/1/2026 3:28 PM Gordon Galbraith
2nd Floor top of sound wall spray - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/2/2026 2:29:33 PM
2ND FLOOR - HEAD OF WALL DRYWALL , R13 & MINERAL WOOL INSULATION INSPECTION
1) CORRIDOR 206, 216 -OK.
|
|
| 04/03/2026 | B:RGH PLUMB | BRETT LONGNECKER | PARTIAL | L1 Domestic & DWV, In-wall & Overhead | 4/2/2026 10:09:24 AM
4/2/2026 10:09 AM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
4/3/2026 10:09:49 AM
DWV test and supports ok for 1st floor exam rooms on east side only highlighted in blue on P2.21A.1 and P2.21B.1. Photos uploaded.
Domestic water test and supports ok for 1st floor exam rooms on east and west side highlighted yellow on P2.11A.1 and P2.11B.1. Photos uploaded.
|
|
| 04/06/2026 | B:RGH PLUMB | BRETT LONGNECKER | CANCEL | eTRAKiT Inspection Request | 4/3/2026 2:30:58 PM
4/3/2026 2:30 PM Gordon Galbraith
DWV in-wall & OH - plan north - Fabian w/CMS
Contact Name: Fabian Mendez
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: ggalbraith@tcco.com
4/6/2026 9:41:25 AM
Cancel per conversation with contractor.
|
|
| 04/06/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 4/3/2026 10:14:48 AM
4/3/2026 10:14 AM Gordon Galbraith
In-wall conduit & back box rough - 1st Floor
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/6/2026 11:02:43 AM
Partial rough electrical approved
Walls only on first floor/corridor (see photo) east side of first floor. Middle of first floor
Please call in rough electrical to finish first floor rough walls. West side of 1st floor and corridor
|
|
| 04/06/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | DRYWALL & SCREW INSPECTION | 4/3/2026 2:33:01 PM
4/3/2026 2:33 PM Gordon Galbraith
1st floor screw inspection - rated walls - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/6/2026 2:49:07 PM
DRYWALL & SCREW INSPECTION -
1) MED PREP 134 DRY WALL 8" EDGE & "12 FEILD - OK.
NOTE: MISS LOCATED SINK DRAIN PIPE AT SAME WALL AS NOTED ABOVE TO BE INSPECTED BE FORE CLOSE OF WALL.
|
|
| 04/06/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | 2ND FLOOR HEAD OF WALL | 4/3/2026 2:32:26 PM
4/3/2026 2:32 PM Gordon Galbraith
2nd floor top out - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/6/2026 2:49:10 PM
2ND FLOOR HEAD OF WALL-
1) CORRIDOR 233/ SHELL SPACE DEMISING WALL- OK.
2) CONSULT / BH 242 DEMISING WALL EAST SIDE THROUGH LAB 234 - OK.
3) MD/APP 251 DEMISING WALL WEST SIDE THROUGH MP/APP 215/ STAFF LOUNGE- OK.
|
|
| 04/07/2026 | B:RGH PLUMB | BRETT LONGNECKER | PARTIAL | 1st floor DWV | 4/6/2026 3:31:33 PM
4/6/2026 3:31 PM Gordon Galbraith
Waste & Vent 1st Floor - water test
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/7/2026 3:20:17 PM
DWV and water ok as highlighted in yellow on town approved plans P2.21.A.1 and P2.21.B.1.
|
|
| 04/09/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 4/8/2026 3:27:02 PM
4/8/2026 3:27 PM Gordon Galbraith
in-wall rough 1st floor - Dan w/Duro
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/9/2026 10:57:55 AM
1st floor TI rooms for wall rough electrical
106, 109, 111, 112, 113, 114, 118, 119, 123, 127, 128, 129, 131, 132, 133 ok for drywall
117 125 101 waiting for framing to be installed ****not ok to drywall****
|
|
| 04/09/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/8/2026 2:55:23 PM
4/8/2026 2:55 PM Gordon Galbraith
Drywall 1st Floor - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/9/2026 3:13:50 PM
DRYWALL SCREW INSPECTION-
1) CT TLT 115A- EAST WALL - OK.
|
|
| 04/10/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | Level 1 Plumbing Insulation | 4/9/2026 10:22:12 AM
4/9/2026 10:22 AM COLORADO MECHANICAL SYSTEMS LLC
Please contact Jeremy Phillips (720)392-3146. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 7203923146
e-Mail: AR@COLORADOMECH.COM
4/10/2026 3:15:12 PM
PARTIAL-
1) SECOND FLOOR EDGED OF SLAB INSULATION (WEST WALL) / GRID LINES 4-6 MINERAL WOOL INSULATION (WITNESS) INSPECTION- 711119a HILTI - OK.
|
|
| 04/13/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | DRYWALL SCREW TOP ROCK & FIRE RIP | 4/10/2026 6:08:22 PM
4/10/2026 6:08 PM Gordon Galbraith
Drywall 1st floor - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/13/2026 4:13:53 PM
DRYWALL SCREW TOP ROCK & FIRE RIP INSPECTION
1) MGR OFFICE 159 DRYWALL INTERIOR SIDE NORTH EAST WALL - OK.
2) CORRIDOR 144 / NORTH & EAST PARTITION / EXAM TRIAGE 156 INTERIOR NORTH WALL & UL 377 - OK.
3) EQUIPMENT 157 ALL HEAD OF WALLS & FIRE RIP - OK.
4) PAT TLT 158 - ALL WALLS - OK.
5) EVS 157A - INTERIOR NORTH HEAD OF WALL-OK.
NOTE: CMI FOR MEMBRANE AND THROUGH PENETRATIONS
|
|
| 04/13/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | WALL FRAME FIRST FLOOR | 4/10/2026 6:06:39 PM
4/10/2026 6:06 PM Gordon Galbraith
Close wall frame inspection - 1st Floor - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/13/2026 4:13:56 PM
WALL FRAME & CHANNEL TRACK FIRST FLOOR
1) EXAM 148 - EXAM TRIAGE 156 ALL WALLS - OK.
2) CORRIDOR- 144 EAST WALL- OK.
3) CORRIDOR 144 WEST / ALL ROOMS EXCEPT ED LAB 147;/ CORRIDOR 137 SOUTH & ED LAB 147/ CORRIDOR 116 EAST WALLS & ROOMS -
3a) **** ED LAB 147 (2) REPAIR STUDS N/E & INTER NORTH CORNER DAMAGED. *****
|
|
| 04/13/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | Pre-Insulation & Damper Openings | 4/10/2026 1:20:34 PM
4/10/2026 1:20 PM COLORADO MECHANICAL SYSTEMS LLC
Exam rooms, 148,149,151,152,153,154,155,&156
Nurses station 141
CT 115
Waiting 101
Fire dampers throughout 1
Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035197973
e-Mail: AR@COLORADOMECH.COM
4/13/2026 4:13:58 PM
PARTIAL-
1) JOINT / SEALED CONNECTIONS & SUPPORT - EXAM 148 - EXAM/ TRIAGE 156 - OK
2)JOINT / SEALED CONNECTIONS & SUPPORT - EAST WALLS OF ED LAB 147 - SOILED / - EVS 157a -OK.
3) JOINT / SEALED CONNECTIONS & SUPPORT - CORRIDOR 143 / NURSE STATION 141 / EQPT ALCOVE 139/ CORRIDOR 137 & NOURISH 142 - OK.
|
|
| 04/14/2026 | B:INSULATION | JOE CARBAUGH | CANCEL | eTRAKiT Inspection Request | 4/13/2026 5:35:40 PM
4/13/2026 5:35 PM Gordon Galbraith
1st floor sound insulation - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/14/2026 11:12:29 AM
CANCELED-
1) CANCELED BY CONTRACTOR.
|
|
| 04/14/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | RGH FRAME WALLS | 4/13/2026 5:35:10 PM
4/13/2026 5:35 PM Gordon Galbraith
frame 1st & 2nd floor - Brian E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/14/2026 11:12:25 AM
PARTIAL-
ROUGH FRAME WALLS FOR TOP OUT TI 2ND FLOOR
1) THE AMAZING WALLS BETWEEN EXAM 232-227 MANAGERS OFFICE 208& PHONE BANK 213 - OK
2) EXAM 247 & EXAM 245 DEMISE WALL- OK.
|
|
| 04/14/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/13/2026 5:38:33 PM
4/13/2026 5:38 PM Gordon Galbraith
OH Rough - Rooms 109, 111-126
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/14/2026 11:12:22 AM
PARTIAL -
DUCT ATTACHMENTS & JOINT CONNECTIONS INSPECTION BEFORE INSULATE.
1) ****SUPPORTS GREAT THAN 8' O.C. AT ISO EXAM 118 & ISO TLT 119 ****
2) EXAM 125 - STAFF LOUNGE 112- OK.
3) X-RAY 126- CT 115 - OK.
|
|
| 04/14/2026 | B:RGH PLUMB | BRETT LONGNECKER | NOT APPROVED | Partial plumbing inspection in-wall | 4/13/2026 3:37:07 PM
4/13/2026 3:37 PM COLORADO MECHANICAL SYSTEMS LLC
Domestic water. Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
4/14/2026 4:41:08 PM
In wall rough for remaining 1st floor fixtures except for sw corner and drinking fountains.
|
|
| 04/15/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | CLOSE WALL RGH FRAMING INSPECTION | 4/14/2026 3:52:07 PM
4/14/2026 3:52 PM Gordon Galbraith
1st & 2nd Floor Frame - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/15/2026 3:01:34 PM
PARTIAL-
CLOSE WALL RGH FRAMING INSPECTION HIGHLIGHTED AREAS ON ATTACHMENT FOR A & B -
CORRECTIONS -
1) MISSING PUTTY PADS FOR ELECTRICAL BOXES/MATERIALS MANAGEMENT/RECEIVING 132 EMS LOUNGE 129 AND STAFF TLT 131.
2) MISSING PUTTY PADS FOR ELECTRICAL BOXES/ BARIATRIC 117 / STAFF TLT 113 & STORAGE 114
NOTE: REST OF CLOSE WALL FRAMING HIGHLIGHTED IN ORANGE ON THE ATTACHMENT TO BE INSPECTED AT FUTURE INSPECTION.
|
|
| 04/15/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/14/2026 5:48:25 PM
4/14/2026 5:48 PM Gordon Galbraith
1st floor - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/15/2026 3:01:32 PM
PARTIAL-
IST FLOOR TOP OUT R13 INSULATION INSPECTION
1) AREA's B & A HIGHLIGHTED IN GREEN FOR ATTACHED PLAN - OK.
|
|
| 04/16/2026 | B:RGH PLUMB | BRETT LONGNECKER | PARTIAL | in wall pipe insulation | 4/15/2026 4:09:54 PM
4/15/2026 4:09 PM Gordon Galbraith
1st floor domestic water insulation - Fabian w/CMS
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/16/2026 9:44:20 AM
1st floor in wall domestic water pipe insulation ok.
|
|
| 04/16/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | 2nd FLOOR TOP OUT FRAMING | 4/15/2026 4:11:12 PM
4/15/2026 4:11 PM Gordon Galbraith
2nd floor frame - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/16/2026 9:55:48 AM
PARTIAL-
2nd FLOOR TOP OUT HEAD OF WALL FRAMING
1) STORAGE 220, EVS 226, PATTLT 228, MA STATION 237, PAT TLT 246 & EXAM 248 - OK.
|
|
| 04/17/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | FIRST FLOOR INSULATION R13 INSPECTION. | 4/16/2026 4:18:32 PM
4/16/2026 4:18 PM Gordon Galbraith
1st floor insulation - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/17/2026 3:03:13 PM
PARTIAL-
FIRST FLOOR R13 INSULATION INSPECTION FOR EXAM ROOM 148 THROUGH EXAM TRIAGE - OK .
|
|
| 04/17/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/16/2026 4:17:48 PM
4/16/2026 4:17 PM Gordon Galbraith
1st floor frame - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/17/2026 3:03:15 PM
PARTIAL-
FIRST FLOOR
ITEMS CORRECTED BELOW-
1) MISSING PUTTY PADS FOR ELECTRICAL BOXES/MATERIALS MANAGEMENT/RECEIVING 132 EMS LOUNGE 129 AND STAFF TLT 131.
2) MISSING PUTTY PADS FOR ELECTRICAL BOXES/ BARIATRIC 117 / STAFF TLT 113 & STORAGE 114
|
|
| 04/20/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | 1st FLOOR WALL INSULATION MAP | 4/17/2026 3:07:31 PM
4/17/2026 3:07 PM Gordon Galbraith
Insulation 1st floor - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/20/2026 3:16:14 PM
PARTIAL-
1) EXAM 148 THROUGH EXAM/ TRIAGE 156 - OK.
2) EQPT/ LINEN 157 THROUGH MGR OFFICE 159 - OK.
3) CORRIDOR 137 (SOUTH) WALL - OK.
|
|
| 04/20/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | WALL FRAME COLUMNS D-C, 4-5.5 | 4/17/2026 3:06:57 PM
4/17/2026 3:06 PM Gordon Galbraith
Frame 1st floor - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/20/2026 3:16:17 PM
PARTIAL-
WALL FRAME COLUMNS D-C, 4-5.5
1) EVS 157A THROUGH CT TLT 115A - OK
**** WORK 104 / ELECTRICAL PENETRATION AT BOTTOM OF WALL N/ E CORNER****
2) X-RAY 126 - CT 115 - OK.
NOTE: 16 GAGE FRAMING IN X-RAY 126 & CT 115.
|
|
| 04/21/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | WALL INSULATION MAP 4/21/26 | 4/20/2026 3:38:45 PM
4/20/2026 3:38 PM Gordon Galbraith
1st floor insulation - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/21/2026 10:50:55 AM
PARTIAL-
1) ED LAB 147 R13 INSULATION- OK.
|
|
| 04/21/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/20/2026 3:40:32 PM
4/20/2026 3:40 PM Gordon Galbraith
2nd floor stuff & spray top of wall - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/21/2026 10:50:53 AM
PARTIAL-
1) 2ND FLOOR HEAD OF WALL INSULATION & SOUND SPRAY HILTI CP 572 - (EXCLUDING LAB 234). - OK.
|
|
| 04/23/2026 | B:INSULATION | JOE CARBAUGH | CANCEL | INTERIOR WALL R13 INSULATION | 4/22/2026 2:52:17 PM
4/22/2026 2:52 PM Kelly Sherman
1st Floor Insulation Inspection - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/23/2026 1:53:49 PM
CANCELED - INSPECTION PER CONTRACTOR
|
|
| 04/24/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 4/23/2026 2:41:07 PM
4/23/2026 2:41 PM Kelly Sherman
1st Floor Electrical Wall Rough TI - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/24/2026 9:36:09 AM
Rough wall electrical partial approved
Room 125, 117 on first floor wall rough only approved
Notes
Still waiting to inspect first floor lobby/ waiting room area. Walls are incomplete at this time of inspection
|
|
| 04/27/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | SOFFIT FRAMING | 4/24/2026 2:01:34 PM
4/24/2026 2:01 PM Kelly Sherman
Frame inspection 1st Floor - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/27/2026 1:41:16 PM
PARTIAL-
SOFFIT FRAMING
1) EXAM 149 THROUGH EXAM/ TRIAGE 156 - OK.
|
|
| 04/27/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | INSULATION | 4/24/2026 2:01:34 PM
4/24/2026 2:01 PM Kelly Sherman
Frame inspection 1st Floor - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/27/2026 1:41:19 PM
PARTIAL-
INSULATION INSPECTION -OK AS NOTED ON PICTURE ATTACHMENT.
|
|
| 04/27/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | DRYWALL SCREW INSPECTION | 4/24/2026 2:01:34 PM
4/24/2026 2:01 PM Kelly Sherman
Frame inspection 1st Floor - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/27/2026 1:41:21 PM
PARTIAL-
DRYWALL SCREW INSPECTION
1) EQPT/ LINEN 157 ALL WALLS $ OUTSIDE EAST WALL -OK.
2) EVS 157a NORTH WALL - OK.
3) CORRIDOR 144 WEST WALL ED LAB 147 THROUGH SOILED 145 - OK
4) CORRIDOR 137 SOILED 145 THROUGH MED PREP 134 NORTH WALL - OK.
5) MED PREP 134 INSIDE & OUTSIDE NORTH & WEST WALLS AT GRID LINE 2.5 - OK.
6) CLEAN 135 - OK.
7) ED LAB 147 ALL WALLS - OK.
8) BOTH SIDES OF MATERIALS MANAGEMENT / RECEIVING 132 / STAFF TLT 131 & EMS LOUNGE 129 GRID LINES F 1.5 THROUGH 2.2 - OK.
|
|
| 04/28/2026 | B:RGH PLUMB | BRETT LONGNECKER | PARTIAL | in wall rough 1st floor P2.11B.1 | 4/27/2026 4:04:21 PM
4/27/2026 4:04 PM Kelly Sherman
Partial plumbing for L1 - Fabian w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/28/2026 11:47:18 AM
In wall domestic water rough ok as highlighted on P2.11B.1 in blue.
|
|
| 04/28/2026 | B:INSULATION | JOE CARBAUGH | CANCEL | eTRAKiT Inspection Request | 4/27/2026 4:07:17 PM
4/27/2026 4:07 PM Kelly Sherman
Insulation & Firestopping 1st Floor - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/28/2026 12:33:28 PM
CANCELED.
|
|
| 04/28/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/27/2026 4:07:17 PM
4/27/2026 4:07 PM Kelly Sherman
Insulation & Firestopping 1st Floor - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/28/2026 12:33:31 PM
PARTIAL-
1) WITNESS FIRE STOP STI/JF 120-01 AT HEAD OF WALL 4a & 4b MED PREP 134 , SOILED 145 & ED LAB 147 - OK.
( packing material is mineral fiber insulation for compression and joint openings.)
|
|
| 04/29/2026 | B:RGH PLUMB | BRETT LONGNECKER | PARTIAL | pipe insulation | 4/28/2026 4:22:27 PM
4/28/2026 4:22 PM Kelly Sherman
In Wall Copper - Fabian w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/29/2026 11:40:49 AM
In wall pipe insulation for pipe inspected 4/28/26.
|
|
| 04/29/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | FIRST LAYER 5/8 GYP TYPE X FOR 2nd FLOOR IT ROOM | PARTIAL | 4/29/2026 3:01:30 PM
PARTIAL-
1) FIRST LAYER 5/8 TYPE X GYP FOR 2nd FLOOR IT ROOM ALL WALLS - OK.
|
|
| 04/29/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | TI FRAME FURRED OUT WALLS | 4/28/2026 4:21:39 PM
4/28/2026 4:21 PM Kelly Sherman
1st Floor - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/29/2026 3:00:51 PM
PARTIAL-
(TI FRAME FURRED OUT WALLS)
1) PUBLIC TLT 106 EAST WALL FRAME - OK.
2) SOILS 145 SOUTH WALL FRAMING AROUND PLUMBING- OK.
3) CORRIDOR 144 SOUTH END WALL - OK
4) EXAM 148 SOUTH WALL & FIRE RATED BACKING - OK.
|
|
| 05/04/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 4/30/2026 2:21:26 PM
4/30/2026 2:21 PM Kelly Sherman
1st Floor TI Wall Rough - Dan w/ Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/4/2026 9:47:29 AM
Rough electrical partial approved
Rough electrical for walls only
1st floor rough electrical for TI is complete please recall inspection when 2nd floor TI is ready.
|
|
| 05/04/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/30/2026 2:30:30 PM
4/30/2026 2:30 PM Kelly Sherman
Framing 1st Floor TI - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/4/2026 10:48:23 AM
PARTIAL-
SOFFIT FRAMING
1) ED LAB 147 - OK.
2) ISO EXAM 118 - OK.
3) BARIATRIC 117 - OK.
|
|
| 05/04/2026 | B:RGH PLUMB | BRETT LONGNECKER | CANCEL | Partial Overhead Domestic & In-wall | 4/30/2026 1:13:18 PM
4/30/2026 1:13 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
5/4/2026 1:46:55 PM
Cancel per conversation with Fabian.
|
|
| 05/06/2026 | B:RGH PLUMB | MARTIN MAGERS | CANCEL | Partial Overhead Domestic Water | 5/5/2026 1:27:30 PM
5/5/2026 1:27 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
5/6/2026 12:36:53 PM
Canceled per call with Gordon. He told me the site was closed today. Please cancel inspections that will not be ready.
|
|
| 05/07/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 5/6/2026 7:29:15 PM
5/6/2026 7:29 PM Gordon Galbraith
1st floor domestic water - Fabian w/CMS - reinspection for failed inspection on 5/4
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
5/7/2026 12:16:08 PM
In wall and over head as marked on P2.11A1 and P2.11B.1
|
|
| 05/11/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 5/8/2026 3:57:58 PM
5/8/2026 3:57 PM Kelly Sherman
FIrst Floor South MP Square & Round - Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/11/2026 2:27:08 PM
CANCELED-
See 5/11/2026 INSULATION INSPECTION.
UPDATED NOTES: INSPECTOR JOE CARBAUGH , 5/11/26 -
MEDIUM PRESS 144 SOILED 145 - OK.
LOW PRESS SQUARE - TB-E 1-07 - OK.
NOTE: SEE CLOUDED AREA FOR INSPECTION ATTACHMENT .
|
|
| 05/11/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | Level 1 Domestic Water Insulation | 5/8/2026 11:42:50 AM
5/8/2026 11:42 AM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
5/11/2026 2:27:10 PM
PARTIAL-
1) PIPE INSULATION INSPECTION FOR HIGHLIGHTED AREAS FIRST FLOOR AREA'S A & B .
|
|
| 05/12/2026 | B:RGH PLUMB | MARTIN MAGERS | CANCEL | Level 2 In-Wall Rough | 5/8/2026 11:42:50 AM
5/8/2026 11:42 AM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
5/8/2026 4:03:32 PM
5/8/2026 4:03 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
5/12/2026 2:03:50 PM
Canceled per call with Fabian. Site not ready.
|
|
| 05/13/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 5/12/2026 1:57:24 PM
5/12/2026 1:57 PM Kelly Sherman
2nd Floor Wall Rough TI Electrical - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/13/2026 10:45:42 AM
Rough electrical partial approved walls only
Rooms wall rough that are approved
238 239 241 242 244 245 247 249 253 236 235 234 231 232 229 228 246 248 226 220 227 225 213 208 205
Notes
Ok to drywall if all other inspections are approved
Please call in rough inspection when ready to finish 2nd floor walls
Millwork on second floor will need a rough electrical inspection when millworkers installed
|
|
| 05/13/2026 | B:RGH FRAME | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 5/12/2026 2:12:24 PM
5/12/2026 2:12 PM Kelly Sherman
2nd Floor Frame - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/13/2026 1:29:14 PM
APPROVED-
1) SOUND SEPARATION FOR RFI 32
a) EXAM ROOMS - 245,247 - OK.
b) PAT TLT 228 & EVS 226 - OK.
c) EXAM ROOMS 229 & 227 - OK.
d) ADMIN WORK 205 & MANAGER OFFICE 208 - OK.
|
|
| 05/13/2026 | B:RGH PLUMB | MARTIN MAGERS | CANCEL | eTRAKiT Inspection Request | 5/12/2026 1:58:02 PM
5/12/2026 1:58 PM Kelly Sherman
Mechanical - Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/13/2026 2:44:22 PM
Site not ready per Fabio
|
|
| 05/14/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 5/13/2026 5:19:48 PM
5/13/2026 5:19 PM Kelly Sherman
TI Wall Rough - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/14/2026 10:00:28 AM
Rough electrical inspection partial approved
Rooms approved ***walls only***
222 221 219 218 217 215 214 211 mdapp
Ok to drywall
|
|
| 05/14/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 5/13/2026 5:20:37 PM
5/13/2026 5:20 PM Kelly Sherman
HVAC First Floor Fire Dampers Room 134 - Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/14/2026 12:12:33 PM
PARTIAL-
ANGLER SPACE , SUPPORT & SEAL INSPECTION.
1) PAT TLT 146, SOILED 145, CLEAN 135 & MED PREP 134 - OK.
|
|
| 05/14/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 5/13/2026 2:06:22 PM
5/13/2026 2:06 PM Kelly Sherman
2nd Floor Wall Frame, Non Plumbing Walls
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/14/2026 12:12:36 PM
PARTIAL-
2nd FLOOR WALL FRAMING
1) SHELL SPACE THROUGH LAB 234 FRAME - OK.
NOTE: HLTI DOC FLOOR PENETRATIONS TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 05/14/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 5/13/2026 5:21:15 PM
5/13/2026 5:21 PM Kelly Sherman
In Wall Plumbing Level 2 - Fabian w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/14/2026 12:28:42 PM
2nd Floor walls DWV and water as marked on P2 pages.
|
|
| 05/19/2026 | B:RGH FRAME | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 5/18/2026 2:27:37 PM
5/18/2026 2:27 PM Kelly Sherman
2nd Floor Frame - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/19/2026 12:00:23 PM
NOT APPROVED- SEE ITEM 2)
2ND FLOOR WALL FRAMING & FIRES-TOP
1) PLUMBING HLTI FLOOR SLEEVES EXAM/ PROCEDURE 241 THROUGH LAB TLT 235- OK.
2) **** MISSING HLTI SLEEVE FOR PLUMBING FLOOR PENETRATION IN EXAM 244 / EXAM 245 ****
3) **** MISSING HLTI SLEEVE FOR ELECTRICAL PENETRATION IN ADMIN WORKS 205 SOUTH WALL TI.
4) **** MISSING HLTI SLEEVE FOR ELECTION PENETRATION IN LAB 234****
1) 2ND FLOOR FRAMING COMPLETE - OK SEE ATTACHMENT.
|
|
| 05/19/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | Level 2 In-wall Inspection | 5/18/2026 2:10:23 PM
5/18/2026 2:10 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
5/19/2026 2:45:51 PM
In wall water and drain for 2nd. East exam room and water for South central exam rooms. Water Marked in green on page P2.12A.1 and P2.12B1 . DWV on PP2.22A.1 and P2.22B.1 in yellow.
|
|
| 05/20/2026 | B:INSULATION | MARTIN MAGERS | PARTIAL | Lvl 1 Overhead Plumbing Insulation | 5/19/2026 2:50:17 PM
5/19/2026 2:50 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
|
|
| 05/22/2026 | B:INSULATION | JOE CARBAUGH | NOT APPROVED | Lvl 2 Plumbing Insulation | 5/21/2026 1:18:15 PM
5/21/2026 1:18 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303) 704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
5/22/2026 11:37:23 AM
NOT APPROVED-
SOUND WALL INSULATION INSPECTION NOT REQUIRED.
|
|
| 05/22/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | Lvl 2 Duct Inspection | 5/21/2026 1:17:19 PM
5/21/2026 1:17 PM COLORADO MECHANICAL SYSTEMS LLC
Core & Shell and TI level 2 duct inspection. Please contact Nick Padrevita (303) 859-9954. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038599954
e-Mail: AR@COLORADOMECH.COM
5/22/2026 11:37:25 AM
PARTIAL
1) LVL DUCT SEAL & SUPORT FOR CORRIDOR 206 & CORRIDOR 216 & MANAGERS OFFICE 208 - OK.
|
|
| 05/22/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | Lvl 2 In-Wall Inspection | 5/21/2026 9:33:56 AM
5/21/2026 9:33 AM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303) 704-9745. Crew is offsite at 3:30pm
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
5/22/2026 2:13:20 PM
Water in wall as marked in green on P2.12A1 and DWV as marked in yellow on P2.22A1 all second floor walls ok except drinking fountain.
|
|
| 05/27/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | HVAC Inspection Level 1 & 2 | 5/26/2026 1:51:24 PM
5/26/2026 1:51 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Nick Padrevita (303)859-9954. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038599954
e-Mail: AR@COLORADOMECH.COM
5/27/2026 3:21:58 PM
PARTIAL-
1) 1st FLOOR- SEAL & SUPPORT - ED LAB 147 - SOILED 145 / CORRIDOR 144 -OK .
2) 2nd FLOOR SEAL & SUPPORT- GRID LINE C TO B & WAITING 202 / CORRIDOR 233 - OK.
|
|
| 05/28/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 5/27/2026 2:36:11 PM
5/27/2026 2:36 PM Gordon Galbraith
Second Floor, East & West perimeter rooms - CMS
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
5/28/2026 12:57:43 PM
PARTIAL-
SEAL & SUPPORT- 2nd FLOOR.
1) MD/APP 251 THROUGH MD/ APP 215 - OK.
|
|
| 06/01/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 5/29/2026 12:52:49 PM
5/29/2026 12:52 PM Kelly Sherman
Firestopping with CMI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/1/2026 1:19:48 PM
NOT APPROVED-
NOTE: COURTESY MEETING WITH CMI & CONTRACTOR REVIEW & DISCUSSION FOR HORIZONTAL FIRE-STOP SYSTEM INSPECTIONS.
|
|
| 06/02/2026 | B:RGH MECH | MARTIN MAGERS | CANCEL | eTRAKiT Inspection Request | 6/1/2026 8:38:13 AM
6/1/2026 8:38 AM Kelly Sherman
1st & 2nd Floor Low Press Square - Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/2/2026 7:15:24 AM
CANCELED-
NOTE: DUPLICATE INSPECTION.
|
|
| 06/02/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | 1st floor domestic overhead | 6/1/2026 2:48:16 PM
6/1/2026 2:48 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
6/2/2026 11:39:17 AM
First for domestic water piping complete. Needs insulation.
6/2/2026 1:12:35 PM
Drinking fountain DWV and water for first floor approve. Still needs insulation.
|
|
| 06/02/2026 | B:RGH MECH | MARTIN MAGERS | PARTIAL | 1st floor steam piping | 6/1/2026 2:48:17 PM
6/1/2026 2:48 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
6/2/2026 1:12:38 PM
All steam piping approve on first floor. Still needs insulation.
|
|
| 06/03/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | 2nd Floor Low Pressure | 6/2/2026 2:02:09 PM
6/2/2026 2:02 PM COLORADO MECHANICAL SYSTEMS LLC
Please call Nick Padrevita (303)859-9954. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038599954
e-Mail: AR@COLORADOMECH.COM
6/3/2026 11:28:11 AM
PARTIAL-
1) SEAL and SUPPORT SECOND FLOOR AS MARKED- OK.
|
|
| 06/05/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 6/4/2026 3:06:12 PM
6/4/2026 3:06 PM Gordon Galbraith
Screw inspection for lead lined drywall in 1st floor CT & XRay procedure rooms - Brian with E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/5/2026 11:21:03 AM
PARTIAL-
1) DRYWALL & SCREW INSPECTION FOR X-RAY 122 & CT 115 - OK.
|
|
| 06/09/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 6/8/2026 4:13:03 PM
6/8/2026 4:13 PM Gordon Galbraith
hardlid frame inspection - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/9/2026 11:01:35 AM
PARTIAL-
1st FLOOR DROP CEILING FRAMING CORRIDOR 237, NOURISH 142 EQPT ALCOVE 139 - OK.
NOTE: OK OFR DRYWALL PENDING RGH ELECTRICAL.
|
|
| 06/09/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 6/8/2026 4:16:54 PM
6/8/2026 4:16 PM Gordon Galbraith
hard lid rough to allow rock 1st floor - Dan w/Duro
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/9/2026 11:44:17 AM
Rough electrical inspection partial approved for hard lids only on first floor TI
bathroom hard lids. Location 1. South/ West side of building. Location 2 south/east bathroom x2
Corridor soffits in first floor hallways
Please call the rest of hard lids inspections when ready
|
|
| 06/10/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 6/9/2026 8:40:02 PM
6/9/2026 8:40 PM Gordon Galbraith
Complete TI hard lid rough inspection, 1st floor - Dan with Duro
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/10/2026 8:57:39 AM
Rough electrical ceiling partial inspection approved hard lids only on TI first floor
Rooms 158, 113, 119 hard lid inspection
|
|
| 06/10/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 6/9/2026 8:39:07 PM
6/9/2026 8:39 PM Gordon Galbraith
Inspection to coordinate with State fire inspector Christian Morales with respect to rated wall inspections performed by Joe Carbaugh. Request is for 9:30am to conincide with State inspector''s hard lid fire sprinkler inspection.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/10/2026 2:26:20 PM
NOT APPROVED-
MEETING WITH CASTLE ROCK FIRE, STATE & BUILDER FOR FIRE RESIST.
6/10/2026 3:15:19 PM
NOT APPROVED-
MEETING WITH CASTLE ROCK FIRE, STATE & BUILDER FOR FIRE RESIST.
|
|
| 06/10/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | 2nd Floor Low Pressure Round | 6/9/2026 1:32:41 PM
6/9/2026 1:32 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Nick Padrevita (303)859-9954. Crew is offsite at 3:30pm
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038599954
e-Mail: AR@COLORADOMECH.COM
6/10/2026 2:26:25 PM
PARTIAL-
1) SEAL AND SUPPORT IN MARKED AREAS- OK.
6/10/2026 3:15:25 PM
PARTIAL-
1) SEAL AND SUPPORT IN MARKED AREAS- OK.
|
|
| 06/15/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | 1st floor RA FDs | 6/12/2026 1:03:41 PM
6/12/2026 1:03 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Nick Padrevita (303)859-9954. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038599954
e-Mail: AR@COLORADOMECH.COM
6/15/2026 2:04:20 PM
NOT APPROVED-
1) FIRST FLOOR SEAL, SUPPORT & ANGLE INSPECTION.
2) UNABLE TO VERIFY HORIZONTAL ANGEL SUPPORT DUE TO DRYWALL.
|
|
| B:RGH PLUMB | BRETT LONGNECKER | | 1st Floor Hard-Lid Inspection | 6/16/2026 9:24:58 AM
6/16/2026 9:24 AM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
|
|
| 06/18/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 6/17/2026 3:49:29 PM
6/17/2026 3:49 PM Kelly Sherman
Overhead Inspection
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/18/2026 2:30:06 PM
Rough electrical inspection partial approved
Hard lid inspections only
1. Room 133 verify 2 access panels at final electrical
2. Room 128 verify 3 access panels at final electrical
3. Room 115 a verify 1 access panel at final electrical inspection
4. Room 106 good
|
|
| 06/18/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | 1st Floor Hard-Lid Plumbing Inspection | 6/16/2026 1:47:37 PM
6/16/2026 1:47 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
6/18/2026 2:37:53 PM
All hard rooms with hard lids have the insulation approved, and the labels are approved in all of these rooms except bathroom 106 is missing condensate labels. The condensate labels will be visible from an access panel.
|
|
| 06/22/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 6/17/2026 3:50:22 PM
6/17/2026 3:50 PM Kelly Sherman
Mechanical w/Nick CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/22/2026 6:49:13 AM
|
|
| 06/22/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | 2nd Floor Overhead Vent | 6/19/2026 1:25:53 PM
6/19/2026 1:25 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
6/22/2026 3:12:38 PM
All drain waste and vent for 2nd Floor approved.
|
|
| 06/22/2026 | B:RGH FRAME | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 6/18/2026 3:03:19 PM
6/18/2026 3:03 PM Kelly Sherman
Level 1 Hardlid Inspection
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/22/2026 3:20:28 PM
NOT APPROVED.
NOTE : RESCHEDULE ABOVE GRID FOR TOMORROW 6/23/26.
|
|
| 06/23/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 6/22/2026 3:14:41 PM
6/22/2026 3:14 PM Kelly Sherman
Level 1 Hardlid Inspection
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/23/2026 1:37:36 PM
PARTIAL-
1) FIRST FLOOR ROUGH MEP'S ABOVE HARD LID (ONLY) - APPROVED.
2) FIRST FLOOR MINERAL WOOL AT HEAD OF WALL IN ALL HARD LID ROOMS - OK.
3) (E) STAIR SOUTH ES01 SECOND FLOOR HARD LID - OK.
NOTE: CONFIRM CASTLE ROCK FIRE SPRINKLER ABOVE HARD LIDS ARE OK BEFORE CLOSE OF HARD LIDS.
|
|
| 06/25/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 6/24/2026 2:40:49 PM
6/24/2026 2:40 PM Kelly Sherman
2nd Floor Overhead Domestic Water - Fabian w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/25/2026 2:51:05 PM
All 2nd floor water lines approved and roof hydrant. Still needs insulation.
|
|
| 06/15/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 6/12/2026 6:40:00 PM
6/12/2026 6:40 PM Gordon Galbraith
Balance of level 1 hard lid inspections - Dan w/Duro
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/15/2026 10:19:56 AM
Rough electrical inspection for hard lid ceilings only
Rooms approved 125,118
Note. Will verify at final electrical inspection access panel to be installed in room 118.
|
|
| 06/30/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 6/29/2026 2:59:24 PM
6/29/2026 2:59 PM Kelly Sherman
Level 2 Hardlids - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/30/2026 10:35:13 AM
2nd floor Room 235 hard lid inspection only partial approved
1st floor TI hard lids complete
|
|
| 06/30/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 6/29/2026 3:01:24 PM
6/29/2026 3:01 PM Kelly Sherman
Lvl 1 Control Rm - Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/30/2026 2:52:04 PM
PARTIAL-
1) FIRST FLOOR - SEAL & SUPPORT- OK.
2) FIRST FLOOR SEAL & SUPPORT AT CONTROL ROOM 121
SECOND FLOOR
1) SEAL, SUPPORT & ANGULAR SPACES- OK.
|
|
| 07/01/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 6/30/2026 1:57:22 PM
6/30/2026 1:57 PM Kelly Sherman
Level 2 Hardlid Inspection
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/1/2026 9:37:51 AM
2nd floor TI hard lid only inspection partial approved
Hard lid rooms inspected 226, 246, 243, 203, 209, 224 corridor hard lid, 228, 246, 243 corridor hard lid
|
|
| B:ELECT CONST METER | | | eTRAKiT Inspection Request | 7/7/2026 8:41:14 AM
7/7/2026 8:41 AM Kelly Sherman
All Gas Piping - Fabian w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
|
|
| 07/07/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/6/2026 1:51:04 PM
7/6/2026 1:51 PM Kelly Sherman
Level 2 Hardlids - Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/7/2026 3:11:20 PM
PARTIAL -
1) 2nd FLOOR HARD LID - OK (EXCEPT WAITING 102 OF FIRST FLOOR & WAITING 202 SECOND FLOOR.
NOTE: WAITING 102 & WAITING 202
|
|
| 07/08/2026 | B:GAS PIPE AIR TEST | MARTIN MAGERS | APPROVED | eTRAKiT Inspection Request | 7/7/2026 8:44:17 AM
7/7/2026 8:44 AM Kelly Sherman
All Gas Piping - Fabian w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/8/2026 3:26:29 PM
No gas pipe on the TI
|
|
| 07/09/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/8/2026 2:03:45 PM
7/8/2026 2:03 PM Kelly Sherman
Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/9/2026 9:37:22 AM
PARTIAL-
1) EXHAUST INSULATION FOR 2nd FLOOR SHELL SPACE- OK.
|
|
| 07/22/2026 | B:INSULATION | JOE CARBAUGH | NOT APPROVED | Label Inspection | 7/21/2026 11:05:16 AM
7/21/2026 11:05 AM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-8745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
7/22/2026 11:04:23 AM
NOT APPROVED.
1) MISSING LABELS ABOVE GRID IN ED Lab 147, EXAM ROOM 151 /152 , ROOM 154 & 155.
2) REST OF FIRST FLOOR ABOVE GRID LABELS- OK.
NOTE: RECALL INSPECTION WHEN MISSING ITEMS HAVE BE COMPLETE.
7/22/2026 11:06:16 AM
NOT APPROVED.
|
|
| 07/24/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/23/2026 10:18:41 AM
7/23/2026 10:18 AM Kelly Sherman
Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/24/2026 11:28:39 AM
PARTIAL-
1) SEAL & SUPPORT SECOND FLOOR
|
|
| 07/29/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 7/28/2026 3:06:22 PM
7/28/2026 3:06 PM Kelly Sherman
2nd Floor Hardlid - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/29/2026 9:45:13 AM
Rough electrical inspection partial approved
Notes
2nd floor hard lid inspection (waiting room)
2nd floor hard lids complete
|
|
| 07/29/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/28/2026 3:05:46 PM
7/28/2026 3:05 PM Kelly Sherman
Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/29/2026 11:28:33 AM
PARTIAL-
1) RGH FRAMING OF HARD LID / EAST SIDE SECOND FLOOR WAITING 202 - OK.
NOTE: RGH MECHANICAL TO BE INSPECTED BEFORE CLOSE OF HARD LID.
|
|
| 07/30/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/29/2026 2:26:21 PM
7/29/2026 2:26 PM Kelly Sherman
2nd Floor Lobby - Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/30/2026 1:44:48 PM
PARTIAL-
1) SEAL,SUPPORT & DUCT INSULATION -OK / SECOND YARD , WAITING 201
|
|
| 08/04/2026 | B:ELECTRICAL SERVICE | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 8/3/2026 2:26:02 PM
8/3/2026 2:26 PM Gordon Galbraith
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: daniel.castro@duroelectric.com
8/4/2026 11:27:27 AM
Transformer to userk cabinet approved
Userk to mdp approved
Okay to release meter
Schedule electrical service when mdp is ready for inspection to complete electrical service
|
|
| 08/04/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | APPROVED | Plumbing Label & Insulation Inspection | 8/3/2026 3:26:47 PM
8/3/2026 3:26 PM COLORADO MECHANICAL SYSTEMS LLC
Please call Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
8/4/2026 3:31:17 PM
All labeling complete including all 2nd fl and ED room and 149 corrections. All rough plumbing complete.
|
|
| 08/07/2026 | L: BACKFLOW SURVEY INSPECTION | ERIN SWEENEY | APPROVED | See notes. | 8/7/2026 11:09:38 AM
Appropriate backflow protection for use and level of hazard. Passing test reports required prior to issuance of C.O. or T.C.O. Any questions please contact Erin Sweeney at xconnection@crgov.com or 720-733-6020. Field notes attached.
|
|
| 08/11/2026 | U:METER SET COMM | GRANT TAYLOR | METER INSP FAIL 1 | | 8/11/2026 3:05:50 PM
Inspection fail fee needs to be added, standard notes won't work.
Water needs to be charged up to #2 shutoff on back flow for inspection to be valid
|
|
| 08/13/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 8/12/2026 3:20:44 PM
8/12/2026 3:20 PM Kelly Sherman
First Floor TI West - Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
8/13/2026 1:45:05 PM
PARTIAL-
FIRST FLOOR ABOVE GRID SEAL & SUPPORT. OK.
|
|
| 08/24/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 8/21/2026 2:40:39 PM
8/21/2026 2:40 PM Gordon Galbraith
Rated wall penetration inspection to close ceilings, 1st & 2nd Floor
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
8/24/2026 3:33:01 PM
NOT APPROVED-
1) INSPECTION WAS TURNED INTO A CONSULTATION ABOUT FIRE STOP SYSTEM INDUCTING THROUGH THROUGH PENETRATIONS.
|
|
| 08/24/2026 | B:RGH MECH | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 8/21/2026 2:07:55 PM
8/21/2026 2:07 PM Kelly Sherman
Above Ceiling - Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
8/24/2026 3:33:04 PM
NOT APPROVED-
1) MANUFACTURERS INSTALLATION INSTRUCTIONS FIRE DAMPERS TO BE ON SITE AT NEXT INSPECTION.
|
|
| 08/25/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 8/24/2026 7:43:00 PM
8/24/2026 7:43 PM Gordon Galbraith
Visual on ceiling grid, 1st floor. Looking to drop ceiling tiles in locations that correspond with passed above ceiling MEP inspections. ***Tiles will be left out along rated walls***
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
8/25/2026 3:12:52 PM
PARTIAL-
1) FIRST FLOOR GRID CEILING SUPPORT- OK.
X RAY 126
STORAGE 114
STAFF LOUNGE 112
STORAGE 111
SLEEP 109
ED LAB 147
|
|
| 08/25/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 8/24/2026 1:17:19 PM
8/24/2026 1:17 PM Gordon Galbraith
Above ceiling in ACT areas, 1st floor. Inspection to drop ceiling tiles.
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
8/25/2026 3:13:21 PM
Rough electrical inspection partial approved
1st floor drop ceiling inspection
114, 112, 111, 109, 126, 147 rooms approved
|
|
| 08/27/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 8/26/2026 2:02:23 PM
8/26/2026 2:02 PM Gordon Galbraith
Reinspection of 1st floor ceiling grid. Scheduling electrical inspection for same time. Please coordinate with Sean or Vince if possible.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
8/27/2026 2:37:42 PM
PARTIAL-
1) FIRST FLOOR GRID SUPPORTS FOR THE FOLLOWING- OK.
CORRIDORS 144, 137, 143 & 119
ROOMS 141, 159, 157, 157a, 115, 117 & 121
|
|
| 08/27/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 8/26/2026 2:04:39 PM
8/26/2026 2:04 PM Gordon Galbraith
Reinspection of 1st floor gird. Rough frame called for same time. Please coordinate with Joe if possible.
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
8/27/2026 3:22:29 PM
Rough electrical inspection partial approved 1st floor drop ceiling only
corridors 1st floor approved 144, 137, 143, 119
Rooms 1st floor 141, 159, 157 157a 115 117, 121
|
|
| 08/31/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 8/28/2026 7:36:02 AM
8/28/2026 7:36 AM Gordon Galbraith
rated wall firestopping. State Fire will be on site from 1-3pm.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/1/2026 6:56:31 AM
NOT APPROVED-
1) FIRE STOP & SMOKE RESIST PRE- WALK.
|
|
| 09/03/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 9/2/2026 6:38:12 PM
9/2/2026 6:38 PM Gordon Galbraith
1st floor OH
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
9/3/2026 12:51:22 PM
Above ceiling approved
Corridor west
|
|
| 09/04/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/3/2026 4:49:31 PM
9/3/2026 4:49 PM Gordon Galbraith
1st floor reception ceiling grid.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/4/2026 1:24:45 PM
PARTIAL-
1) FIRST FLOOR WAITING 101 CEILING GRID & WIRE - OK.
|
|
| 09/10/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 9/9/2026 10:57:08 PM
9/9/2026 10:57 PM Gordon Galbraith
state fire will be on site at 1pm. if inspections can conincide that would be preferable. rated wall penetrations, 1st & 2nd floors
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/10/2026 1:16:09 PM
NOT APPROVED-
1) PRE-WALK FOR FIRE SMOKE RESIST.
|
|
| 09/11/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/10/2026 11:49:14 AM
9/10/2026 11:49 AM Gordon Galbraith
Mat Mgmt / Receiving 132, EMS Lounge 129, 1st floor exam rooms, & as much of 2nd floor OH as there is time for.
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
9/11/2026 2:46:37 PM
Rough electrical partial inspection approved
2nd floor drop ceiling inspection rooms approved
234, 236, 238, 239, 241, 242
1st floor drop ceiling inspection rooms approved
155, 154, 153, 152, 151, 149, 148, 127, 129, 132, 155, 156
Notes
Ceiling tiles have been installed in room 135, 134 rough ceiling inspection has not been approved ceiling tiles need to be removed for inspection
|
|
| 09/11/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/10/2026 2:08:02 PM
9/10/2026 2:08 PM Gordon Galbraith
Rated wall penetrations on 1st & 2nd floor.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/11/2026 2:55:31 PM
PARTIAL-
1) TI ROOMS - APPROVED.
2) CORE & SHELL HORIZONTAL PENETRATION - APPROVED
Note: CORE & SHELL VERTICAL PENETRATIONS TO BE INSPECTED AT TIME OF STOCK & TRAIN INSPECTION.
|
|
| 09/11/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/10/2026 11:49:48 AM
9/10/2026 11:49 AM Gordon Galbraith
Mat Mgmt / Receiving 132, EMS Lounge 129, 1st floor exam rooms, & as much of 2nd floor OH as there is time for.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/11/2026 2:55:37 PM
PARTIAL-
2nd FLOOR GRID CEILING 243, 236,238,239,241 & 242 - OK.
1ST FLOOR GRID CEILING 155, 154,153,152,149,148,127,129,132,155 & 156 - OK.
NOTE: CORRIDORS TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 09/15/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/14/2026 11:53:11 AM
9/14/2026 11:53 AM Gordon Galbraith
2 missed rooms on the 1st floor and 2nd floor grid.
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
9/15/2026 3:28:19 PM
Rough electrical inspection partial approved drop ceilings
1st floor rooms approved 134, 135
2nd floor rooms approved 222, 251, 249, 253, 247, 245, 244, 215, 217, 218, 219, 221
2nd floor corridors partials south corridor 216. South corridor 233
|
|
| 09/15/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/14/2026 11:49:57 AM
9/14/2026 11:49 AM Gordon Galbraith
2 missed rooms on the 1st floor and 2nd floor grid.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/15/2026 3:36:55 PM
PARTIAL-
GRID SUPPORT - FIRST 134,135 - OK.
SECOND FLOOR 222, 251, SOUTH CORRIDOR 216, 249,253,247,245,244 & SOUTH CORRIDOR 233 215,217,218,219 & 221- OK.
|
|
| 09/16/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/15/2026 4:11:54 PM
9/15/2026 4:11 PM Gordon Galbraith
Grid inspection 2nd floor corridors & remaining rooms
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/16/2026 3:23:09 PM
PARTIAL-
1) SECOND FLOOR GRID SUPPORT IN 232,229,227,225,213,214,211- OK.
2) FIRST FLOOR GRID SUPPORT NURSE STATION 141, RECEPTION 102 -OK.
|
|
| 09/16/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/15/2026 4:14:41 PM
9/15/2026 4:14 PM Gordon Galbraith
1st floor nurse & reception casework boxes, 2nd floor OH corridors & remaining standalone rooms
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
9/16/2026 3:25:18 PM
Rough electrical inspection partial approved
2nd floor drop ceiling inspection
232, 229, 227, 225, 213, 214, 211.
Casework inspection 1st floor
Nurse station 141, reception 102
|
|
| 09/17/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/16/2026 6:16:09 PM
9/16/2026 6:16 PM Gordon Galbraith
Remainder of 2nd floor grid
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
9/17/2026 3:18:52 PM
Rough electrical inspection partial approved
Case work room 204 2nd floor
Middle south corridor 216 2nd floor drop ceiling
North corridor 206 2nd floor drop ceiling
|
|
| 09/17/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/16/2026 6:14:07 PM
9/16/2026 6:14 PM Gordon Galbraith
Remainder of 2nd floor grid
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/17/2026 3:32:53 PM
PARTIAL-
GRID SUPPORT 204,216,206 - OK.
|
|
| 09/18/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/17/2026 5:16:05 PM
9/17/2026 5:16 PM Gordon Galbraith
Remainder of level 2 OH
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
9/18/2026 2:15:44 PM
Rough electrical partial inspection approved Notes
2nd floor drop ceiling only rooms corridors approved
248, 220, 205, 208, nurse station 223, nurse station 237,
All Corridors 2nd floor complete
|
|
| 09/18/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/17/2026 5:15:01 PM
9/17/2026 5:15 PM Gordon Galbraith
Remainder of level 2 grid
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/18/2026 2:27:19 PM
PARTIAL-
1) 2nd FLOOR GRID SUPPORT - 248, 220, 205, 208, 223 & 237 - OK.
|
|
| 09/21/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/18/2026 5:51:21 PM
9/18/2026 5:51 PM Gordon Galbraith
Hoping for last ceiling grid inspection on level 2 reception & 1st floor elevator lobby
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
9/21/2026 2:54:05 PM
Rough electrical inspection partial approved
2nd floor lobby 201
1st floor elevator lobby e110
All drop ceiling completed 1st floor 2nd floor electrical only
|
|
| 09/21/2026 | B:RGH FRAME | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/18/2026 5:49:21 PM
9/18/2026 5:49 PM Gordon Galbraith
Hoping for last ceiling grid inspection on level 2 reception & 1st floor elevator lobby
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/21/2026 12:40:49 PM
Inspector JOCA changed the inspection assignment from JOCA to SHVA
9/21/2026 2:54:08 PM
Rough frame partial approved
Above ceiling grid supports areas approved
2nd floor lobby 201
1st floor elevator lobby e110
|
|
| 09/24/2026 | B:RGH PLUMB | MARTIN MAGERS | APPROVED | Final Rough Inspection, Stock Approval | 9/23/2026 3:35:15 PM
9/23/2026 3:35 PM COLORADO MECHANICAL SYSTEMS LLC
Final Rough Inspection for building dept. Stock inspection. Just need signature and inspection of any final items needed. Please contact Fabian Mendez (303)704-9745 or Nathan Kinder (720)877-0032 to discuss prior to arrival.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
9/24/2026 10:22:29 AM
All rough plumbing on 8/4.
Must call final plumbing and have hot water running to inspect for stock and train approval.
|
|
| 09/24/2026 | B:RGH ELECT | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 9/23/2026 3:21:26 PM
9/23/2026 3:21 PM Kelly Sherman
Casework Electrical - Dan
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
9/24/2026 10:49:40 AM
Rough electrical inspection approved
Note 2nd case work ma station 237, 223
Rough electrical inspection complete
|
|
| 09/24/2026 | B:RGH MECH | JOE CARBAUGH | APPROVED | Final Rough Inspection, Stock Approval | 9/23/2026 3:35:14 PM
9/23/2026 3:35 PM COLORADO MECHANICAL SYSTEMS LLC
Final Rough Inspection for building dept. Stock inspection. Just need signature and inspection of any final items needed. Please contact Fabian Mendez (303)704-9745 or Nathan Kinder (720)877-0032 to discuss prior to arrival.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
9/24/2026 12:27:18 PM
APPROVED. RGH MECH FOR WALLS & CEILING 1st & 2nd floor (IT 25-2082 ( ONLY) - OK.
|
|
| 09/25/2026 | B:RGH FRAME | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/24/2026 4:58:24 PM
9/24/2026 4:58 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/25/2026 3:09:10 PM
RGH FRAME FOR TI ( ONLY) APPROVED.
|
|
| 09/25/2026 | B:INSULATION | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/24/2026 4:58:55 PM
9/24/2026 4:58 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/25/2026 3:09:12 PM
INSULATION FOR TI -APPROVED.
|
|
| 09/28/2026 | B:DRYWALL | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/27/2026 7:35:36 PM
9/27/2026 7:35 PM Gordon Galbraith
FInal drywall to sign permit card
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/28/2026 11:58:14 AM
APPROVED- WHOLE BUILDING.
|
|
| 09/29/2026 | B:FINAL FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/28/2026 12:13:42 PM
9/28/2026 12:13 PM Gordon Galbraith
No Inspection Type listed for final frame on the TI permit.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/29/2026 3:46:37 PM
PARTIAL-
FIRE DAMPER INSPECTION E MECH/ FIRE - OK.
MISSING MECHANICAL ANGLE ON ONE SIDE & ELECTRIC E170- NEED REINSPECT WHEN CORRECTED.
NOTE: REST OF FIRE DAMPERS TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 09/30/2026 | B:ROUGH MECHANICAL | BRETT LONGNECKER | PARTIAL | eTRAKiT Inspection Request | 9/28/2026 12:11:56 PM
9/28/2026 12:11 PM Gordon Galbraith
Fire dampers. Fire AHJ''s will be on site from 12pm - 3pm for visual inspection of all fire dampers.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/30/2026 6:38:57 AM
All dampers checked ok. Still need to complete remaining fire damper rough inspections.
|
|
| 09/30/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/29/2026 4:23:43 PM
9/29/2026 4:23 PM Gordon Galbraith
CRFD will be on site at 9am to continue fire damper inspection.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/30/2026 11:08:17 AM
APPROVED-
1) ALL FIRE DAMPERS IN BUILDING HAVE BEEN INSPECTED & APPROVED FROM BUILDING & CASTLE ROCK FIRE.
|
|
| 10/01/2026 | B:FINAL BUILDING | BRETT LONGNECKER | NOT APPROVED | eTRAKiT Inspection Request | 9/30/2026 4:03:48 PM
9/30/2026 4:03 PM Gordon Galbraith
Stocking acceptance pending 1pm fire alarm annunciator panel replacement & inspection by CRFD.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/1/2026 3:58:52 PM
Ok FOR STOCK ONLY. NO EMPLOYEES ARE ALLOWED UNTIL A STOCK AND TRAIN HAS BEEN APPROVED BY TOWN OF CASTLE ROCK BUILDING DIVISION AND FIRE LIFE SAFETY DIVISION.
THIS INSPECTION WAS ONLY TO VERIFY GENERAL LIFE SAFETY ITEMS FOR STOCKING ONLY. A FULL FINAL BUILDING INSPECTION WILL BE PERFORMED ONCE READY FOR STOCK AND TRAIN AND TCO.
|
|
| 10/06/2026 | B:ELECTRICAL TRENCH | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 10/5/2026 10:14:08 AM
10/5/2026 10:14 AM Kelly Sherman
Underground Electrical C&S
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
10/6/2026 10:02:21 AM
No inspection conducted at this time scheduled under wrong permit number
|
|
| 10/14/2026 | B:FINAL ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 10/13/2026 2:28:25 PM
10/13/2026 2:28 PM Kelly Sherman
Dan
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
10/14/2026 2:53:29 PM
Final electrical inspection partial approved
TI final inspection only
All other rooms on 2nd floor approved
Rooms with corrections on 2nd floor
Room 241 receptacle with in 6 foot of sink requires gfci protection
Room 234 receptacle with in 6 foot of sink requires gfci protection
Room 211 missing floor box
Room 214 receptacle with in 6 foot of sink requires gfci protection
Room 253 receptacle within 6 foot of sink requires gfci protection
Room 249 receptacle within 6 foot of sink requires gfci protection
Room 248 receptacle within 6 foot of sink requires gfci protection
Lighting controls in hallways/corridors need to be programmed all of 2nd floor
Receptacle in hallways good
Highlighted on stamp plans page number A2.12A/B rooms approved
Did not check em/critical branch circuits powered off generator
|
|
| 10/15/2026 | B:FNL ELECTRIC | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 10/14/2026 2:16:07 PM
10/14/2026 2:16 PM Kelly Sherman
Dan
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
10/15/2026 3:23:50 PM
final electrical inspection partial approved
Rooms with corrections
Room 211 floor box not installed
All other rooms on TI only approved
Em lights and critical branch circuits, fed from generator not inspected/ tested at this time
Hallways/ corridors lighting controls not programmed at this time
Highlighted plans on page number A2.12A/B
|
|
| 10/19/2026 | B:FNL ELECTRIC | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 10/16/2026 4:06:00 PM
10/16/2026 4:06 PM Gordon Galbraith
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
10/19/2026 1:50:58 PM
Final electrical approved
102, 109, 111, 112, 114, 115, 117, 121, 122, 125, 126, 127, 132 133, 134, 135, 145, 147, 148, 149, 152, 153, 154, 155, 156, 158, 159, staff room, waiting area, corridors, nourish
Still need lounge room 129 - gfci behind refrigerator
|
|
| 10/22/2026 | B:FINAL PLUMBING | MARTIN MAGERS | NOT APPROVED | eTRAKiT Inspection Request | 10/19/2026 1:58:37 PM
10/19/2026 1:58 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/22/2026 1:46:47 PM
1. Right side Drinking fountain on 2nd floor inoperative.
2. Missing aerator at sink at exam 7 on second floor. Room 247.
3. Drinking fountains on first floor inoperative.
4. ED 147, lab eye wash inoperative.
5. Bathroom 123, is due to be remodeled, and is incomplete at this point.
|
|
| 10/22/2026 | B:FINAL MECHANICAL | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 10/19/2026 1:57:59 PM
10/19/2026 1:57 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/22/2026 1:55:16 PM
NOT APPROVED-
1) LINEAR SLOT AT 111 STORAGE DOES NOT MATCH LAY IN DIFFUSER PER PLAN.
REST OF TI MECHANICAL- OK.
|
|
| 10/26/2026 | B:FNL MECH | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 10/23/2026 4:25:20 PM
10/23/2026 4:25 PM Gordon Galbraith
Reinspection for to-do items.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/26/2026 2:09:13 PM
PARTIAL-
1) ITEMS CORRECTED FROM LAST INSPECTION.
2) TAB REPORT IS NEEDED TO GET CO.
|
|
| 10/26/2026 | B:FNL PLUMB | MARTIN MAGERS | APPROVED | eTRAKiT Inspection Request | 10/23/2026 9:01:57 AM
10/23/2026 9:01 AM Gordon Galbraith
Reinspection drinking fountains, eyewash in ED Lab, & aerator in 247.
Contact Name: Fabian Mendez
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: ggalbraith@tcco.com
10/26/2026 4:03:37 PM
Corrections made
|
|
| 10/27/2026 | B:ELECTRICAL SERVICE | SHAWN VALENZUELA | CANCEL | eTRAKiT Inspection Request | 10/23/2026 3:16:27 PM
10/23/2026 3:16 PM Gordon Galbraith
Pending submission of updated feeder schedule for change from aluminum back to copper for generator feeders.
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
10/27/2026 7:47:52 AM
Inspection canceled electrical service inspection scheduled on wrong permit
See permit number 25-1611 for schedule inspection
|
|
| 10/27/2026 | B:FINAL BUILDING | BRETT LONGNECKER | INC OK FOR TCO | eTRAKiT Inspection Request | 10/22/2026 7:15:50 PM
10/22/2026 7:15 PM Gordon Galbraith
Attempting to get DFPC, Castle Rock Fire, & Castle Rock Building all on site at 2pm for life safety & building TCO final.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/27/2026 3:46:14 PM
1. Reorient exit sign on west 1st floor exit out of building.
2. Handrails missing returns at north stair hand rails.
3. 2nd floor data room conduit for bda missing fire stopping.
4. Conduit through wall above 2nd floor data room door fire stopping damaged.
5. Complete final mechanical.
6. Complete final electrical.
7. Complete final fire.
|
|
| 11/12/2026 | B:FNL MECH | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 11/10/2026 12:10:23 PM
11/10/2026 12:10 PM Braden Frey
TAB report was uploaded to Etrackit
Contact Name: Braden Frey
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035183298
e-Mail: bmfrey@tcco.com
11/12/2026 10:34:14 AM
APPROVED.
|
|
| 11/12/2026 | B:FNL ELECTRIC | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 11/10/2026 12:10:23 PM
11/10/2026 12:10 PM Braden Frey
TAB report was uploaded to Etrackit
Contact Name: Braden Frey
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035183298
e-Mail: bmfrey@tcco.com
11/12/2026 11:54:02 AM
Final electrical inspection approved
All corrections have been completed
|
|