11/21/2026
10:53 PM
 
Permit No. 25-2082 Permit Type   COMMERCIAL TI Site Address   4141 PLUM CREEK BLVD
CASTLE ROCK, CO 80104
Applied   06/13/2025 Applicant   Andrew Holcomb
Approved   01/26/2026 Owner   PORTERCARE ADVENTIST HEALTH SYSTEM
Issued   02/09/2026 Contractor  
Parent Permit No.   25-1611 Description   ADVENTHEALTH MOB EMERGENCY DEPT & CLINIC
  Notes   This is the T.I. for the Advent Health MOB, 1st floor emergency department & 2nd floor primary care clinic.
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 02/10/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request2/9/2026 11:38:55 AM 2/9/2026 11:38 AM Gordon Galbraith 1st floor z-clips prior to spray fireproofing Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 2/10/2026 2:36:57 PM RGH FRAME - ( PARTIAL) LOOKED AT 1ST FLOOR AT Z- CLIPS FIRST FLOOR TOP OF WALL STUD CONNECTIONS BEFORE FIREPROOFING.

 02/26/2026B:DRYWALLBRETT LONGNECKERNOT APPROVEDConsult Inspection2/25/2026 1:13:41 PM 2/25/2026 1:13 PM Braden Frey Drywall Top-out for interior first floor hallways Contact Name: Braden Frey Site Address: 4141 PLUM CREEK BLVD Phone: 3035183298 e-Mail: bmfrey@tcco.com 2/26/2026 1:00:29 PM Consult inspection only. Discussed one siding top portions of interior walls for MEP trades to begin installing along walls. Drywall inspections only needed for fire rated walls.

 03/03/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/2/2026 1:20:06 PM 3/2/2026 1:20 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/3/2026 3:42:47 PM FIRST FLOOR FRAME— 1) STAFF ROOM 112- EAST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 2) BARIATRIC 117 - NORTH WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 3) EXAM ROOM 125 - NORTH & SOUTH INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 4) TRAUNA 127- NORTH & SOUTH INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 5) AMBULANCE VESTIBULE 128- NORTH & SOUTH INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 6) X - RAY ROOM 126 - NORTH & SOUTH INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 7) CONTROL ROOM 121 - NORTH, SOUTH & EAST WALL, NORTH & SOUTH INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 8) CT ROOM 115 - EAST, NORTH WALL, INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 9) STORAGE 111 - EAST & WEST WALL, INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 10) SLEEP 109 - WEST WALL, INTERIOR WALLS, MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. FIRST FLOOR FRAME— PAGE 2 11) CT TLT 115A - NORTH & SOUTH WALLS, 1) STAFF ROOM 112- EAST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 12) MGR OFFICE 159 - NORTH WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 13) EVS 157A - SOUTH & WEST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 14) CORRIDOR 144 EAST SIDE ONLY - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 15) WAITING 101 - SOUTH & WEST WALLS MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 16) CORRIDOR 108 - NORTH , SOUTH , EAST & WEST WALLS - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 17) CORRIDOR 116 - EAST & WEST WALLS (EXCLUDING FIRE RATED ROOM 116) - OK. NOTE: RATED WALLS TO BE CHECKED AT FUTURE INSPECTION. 12) MGR OFFICE 159 - NORTH WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 13) EVS 157A - SOUTH & WEST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 14) CORRIDOR 144 EAST SIDE ONLY - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 15) WAITING 101 - SOUTH & WEST WALLS MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 16) CORRIDOR 108 - NORTH , SOUTH , EAST & WEST WALLS - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 17) CORRIDOR 116 - EAST & WEST WALLS (EXCLUDING FIRE RATED ROOM 116) - OK. NOTE: RATED WALLS TO BE CHECKED AT FUTURE INSPECTION. 3/3/2026 3:52:18 PM FIRST FLOOR ROOF FRAME? PAGE 2 11) CT TLT 115A - NORTH & SOUTH WALLS, 1) STAFF ROOM 112- EAST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 12) MGR OFFICE 159 - NORTH WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 13) EVS 157A - SOUTH & WEST WALL MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 14) CORRIDOR 144 EAST SIDE ONLY - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 15) WAITING 101 - SOUTH & WEST WALLS MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 16) CORRIDOR 108 - NORTH , SOUTH , EAST & WEST WALLS - MINERAL WOOL INSULATION ABOVE TOP PLATE, FRAMED FLOATING WALLS & CONNECTIONS- OK. 17) CORRIDOR 116 - EAST & WEST WALLS (EXCLUDING FIRE RATED ROOM 116) - OK. NOTE: RATED WALLS TO BE CHECKED AT FUTURE INSPECTION.

 03/05/2026B:RGH MECHMARTIN MAGERSPARTIALeTRAKiT Inspection Request3/4/2026 2:18:37 PM 3/4/2026 2:18 PM Gordon Galbraith Contact Name: Patrick Hughes Site Address: 4141 PLUM CREEK BLVD Phone: 3035197973 e-Mail: ggalbraith@tcco.com 3/5/2026 2:21:14 PM Fire dampers in 1 st floor as marked in pink on plans M2.11B.1 and M2.11A.1

 03/05/2026B:RGH FRAMEMARTIN MAGERSPARTIAL3/5/2026 2:21:17 PM Fire damper framing as marked in green on plans M2.11B.1 and M2.11A.1

 03/09/2026B:RGH MECHMARTIN MAGERSPARTIALFire Damper Framing Inspection3/6/2026 11:21:46 AM 3/6/2026 11:21 AM COLORADO MECHANICAL SYSTEMS LLC Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3035197973 e-Mail: AR@COLORADOMECH.COM

 03/10/2026B:DRYWALLJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request3/9/2026 3:24:20 PM 3/9/2026 3:24 PM Gordon Galbraith 1st floor, one side screw inspection rated walls. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/10/2026 2:06:15 PM (TOP OF WALL DRYWALL) SCREW INSCRIPTION AT RATED WALLS (ONE SIDE ONLY.) INTERIOR DRYWALL SCREW INSPECTION EXTERIOR SIDE OF WALLS 1) WAITING 101 , RECEPTION 102- OK. INTERIOR DRYWALL SCREW INSPECTION INSIDE OF 1 HR RATED WALLS OF CT ROOM- OK. 1) TLT 155A, CT 115 - OK. 2) BARIATRIC 117 NORTH FACE 1HR RATED WALL - OK. 3) X-RAY 126 EAST TOW -OK. 1) CORRIDOR 116 NORTH FACE HALLWAY 1HR RATED WALL- OK. 2) CORRIDOR SIDE OF EQUIPMENT ROOM 157 -OK.. 3) CORRIDOR 144 EXTERIOR/ WEST SIDE- PATCH HOLE AT ED LAB 147, ( ITEM TO BE CORRECTED). 4) CORRIDOR 137 SOUTH WALL - OK. 5) CORRIDOR, 116 EAST FACE WALL - TI - OK. NOTE: GREEN HIGHLIGHTED INDICATES WHICH SIDE OF INTERIOR RATED WALL WAS LOOKED AT & RED HIGHLIGHTED AREA NOTED CORRECTION.

 03/11/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/10/2026 4:10:34 PM 3/10/2026 4:10 PM Gordon Galbraith 1st floor Frame - Rated Walls Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/11/2026 3:04:40 PM 1 HR SMOKEBARRIER 1Ab FRAMING HEAD OF WALL FOR 1 HR FIRE RATED TI INSPECTION 1) EXAM/TRIAGE 156 & WAITING 101- OK. 2) MGR OFFICE 159 TO CT TLT 115A EAST WALL- OK. 3) CT TLT 115A / WORK 104 SOUTH WALL – OK. 4) WORK 104 / CT 115 WALL – OK. 5) CT 115 / CORRIDOR 105 – MISSING SCREWS AT TOP OF WALL. 6) CT 115/ CORRIDOR 108 – OK. 7) BARIATRIC 117 / STORAGE 114 & STAFF TLT 113 – OK. 1 HR FIRE BARRIER 1Aa FRAMING HEAD OF WALL FOR 1 HR FIRE RATED TI INSPECTION 1) EQPT/LINEN 157 – ALL WALLS - NORTH,SOUTH,EAST & WEST WALLS – OK. 1 HR FIRE BARRIER 1Aa FRAMING HEAD OF WALL FOR 1 HR FIRE RATED TI INSPECTION 1) CORRIDOR 144 AT SOILED 145 , PAT TLT 146 & ED LAB 147 – OK. 2) ED LAB 147 / PAT TLT 146 MID WALL – OK. Note: SEPERATION WALL BETWEEN PAT TLT 146 & SOILED 145 TO BE INSPECTED AT FUTURE INSPECTION. 3) ED LAB 147 / CLEAN 135 WALL – OK. 4) ED LAB 147 / CLEAN 135 , PAT TLT 146 / CLEAN 135, CLEAN 135 / SOILED 145 WALL – OK. 5) CORRIDOR 137 / SOILED 145, CLEAN 135 & MED PREP 134 – OK. 6) CORRIDOR 116 & MED PREP 134 WALL – OK. 3/11/2026 3:10:05 PM (TOP OF WALL DRYWALL) FRAMING INSECTION AT RATED WALLS (ONE SIDE ONLY.)

 03/13/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/12/2026 3:42:39 PM 3/12/2026 3:42 PM Gordon Galbraith 2nd floor TI - non-rated top of wall frame inspection Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/13/2026 2:07:02 PM (TOP OF WALL FRAME 2nd FLOOR SOUND WALLS) 1) SHELL SPACE 1 - OK. 2) CORRIDOR, 233 EAST WALL - OK. 3) LAD TLT 235 & LAB 234 SOUTH & WEST WALL - OK. 4) CORRIDOR 233 NORTH WALL TO WAITING ROOM 202 - OK. 5) WAITING ROOM 202 / EXAM 232 SEPARATION WALL- OK. 6) RECEPTION 204 / EXAM 232 SEPARATION WALL - OK. 7) RECEPTION 204 / ADMIN WORK 205 - OK. 8) CORRIDOR 206 NORTH & SOUTH WALL - OK. 9) CORRIDOR 216 WEST WALL - OK 10) CORRIDOR 216 SOUTH END WALL - OK. 11) CORRIDOR 216 EAST WALL & MA STATION 223 EAST - OK - TOP MINERAL WOOL INSTALLED. 12) PHONE BANK 213 ALL WALLS - OK. 13) EXAM 225 ALL WALLS - OK. 14) CLEAN SUPPLY 249 , SOILED 253 & EXAM 247 SEPARATION WALL - OK. 15) EXAM 244 SEPARATION WALL & CORRIDOR 233 SEPARATION WALL - OK. 16) CORRIDOR 224 NORTH WALL - OK.

 03/18/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/17/2026 7:44:19 PM 3/17/2026 7:44 PM Gordon Galbraith Witness head of wall UL install - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/18/2026 3:57:04 PM TOP OF WALL CLIPS BEFORE SFRM - PARTIAL- 1) DETAIL HEAD OF WALL HW-D-0652 - CORRIDOR - 105 - OK. 2) DETAIL HEAD OF WALL HW-D-0652 - CT TLT 115A - OK. ****3) CLIPS - DETAILS HW-D-0252 & HW-D- 0617 - EQPT/LINEN 157 - EJ- NOT APPROVED- PENDING ENGINEERING & TOWN REVIEW. ***** ****4) CLIPS - DETAILS HW-D-0252 & HW-D- 0617 - CORRIDOR 144, 137,& 116. EJ- NOT APPROVED- PENDING ENGINEERING & TOWN REVIEW. *****

 03/19/2026B:FIRE SMOKE RESISTJOE CARBAUGHNOT APPROVEDTOP OF WALL CLIPS BEFORE SFRM3/18/2026 2:25:09 PM 3/18/2026 2:25 PM Gordon Galbraith Head of wall UL conditions - 1st floor - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/19/2026 2:54:51 PM 1) ***** CORRIDOR 108 1HR RATED CLIPS AT TOP OF WALL OF CT 115 WEST WALL- (EJ- NOT APPROVED- PENDING ENGINEERING & TOWN REVIEW.) *****

 03/19/2026B:RGH FRAMEJOE CARBAUGHNOT APPROVEDFRAME FOR TOP OF WALLS3/18/2026 2:24:14 PM 3/18/2026 2:24 PM Gordon Galbraith Remaining in-fill framing - 1st floor - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/19/2026 2:54:54 PM 1) ISO EXAM 118 NORTH & SOUTH TOP OF WALL RGH FRAME - OK. 2) ISO TLT 119 EAST WALL TOP OF WALL RGH FRAME - OK. 3) MATERIALS MANAGEMENT RECEIVING 132 NORTH WALL -OK. 4) EMS LOUNGE 129 & STAFF TLT 131 PARTITION WALL-OK. 5) PAT TLT 146 & SOILED 245 PARTITION WALL - OK 6) EXAM 148- EXAM 152 - TOP OF WALL OF DEMISE WALLS - OK. 7) OBSERVATION ROOM 153 - TOP OF WALL OF DEMISE WALLS - OK. 8) EXAM 154 - EXAM ROOM 156 - TOP OF WALL OF DEMISE WALLS - OK. 9) PAT TLT 158 & MGR OFFICE 159 - TOP OF WALL OF DEMISE WALLS - OK. NOTE: MINERAL WOOL ABOVE TOP OF INSPECTION WALLS ABOVE - OK.

 03/24/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/23/2026 6:15:53 PM 3/23/2026 6:15 PM Gordon Galbraith Top of wall UL & screws on rated assemblies - 1st floor - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/24/2026 2:55:07 PM 1)BARIATRIC 117 - BEAM POCKET- OK PER HW-D-0594. 2) BARIATRIC 117 - HEAD OF WALL - OK PER HW- D-0587. 3) BARIATRIC 117 - JOINT SYSTEMS - OK PER HW-D-0420. 1)STAFF TLT 113/ STORAGE 114 T.O.W U465 DRYWALL/ SCREW INSPECTION OPPOSITE SIDE- OK. 2)CORRIDOR 108 NORTH DOORS DRYWALL/SCREW INSPECTION & ANGLER SPACE FOR AIR DUCT- OK. 3) CORRIDOR 108/ 105 & WORK 104 WEST & SOUTH WALLS - OK. 4) *****EQPT/LINEN 157 HEAD OF WALL DRYWALL SCREW INSPECTION- OK S/E , N/E CORNERS & BEAM POCKET TO BE CHECKED AT FUTURE INSPECTION.**** 4)SOILS 145 HEAD OF WALL OPPOSITE SIDE DRYWALL SCREW INSPECTION- OK. 5) PAT TLT 146 HEAD OF WALL DRYWALL SCREW INSPECTION ALL WALLS - OK. 6)***** (TI) PORTION OF ED LAB 147 NORTH & EAST SIDE HEAD OF WALL - OK. ***** 7) ***** (TI) PORTION OF MED PREP 134 / CLEAN 135 - OK. *****

 03/25/2026B:FIRE SMOKE RESISTJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request3/24/2026 2:20:07 PM 3/24/2026 2:20 PM Gordon Galbraith Top of wall UL - 1st Floor - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/25/2026 11:38:45 AM (LISTING XHBN.HW-D-0587 HEAD OF WALL / BEAM POCKET MINERAL WOOL& DRYWALL) 1) X-RAY 126 / EQPT/LINEN 157 HEAD OF WALL / BEAM POCKET MINERAL WOOL - OK. 2) MEP PREP 134, CLEAN 135 , SOILED 145, PAT TLT 146 & ED LAB 147 HEAD OF WALL / BEAM POCKET MINERAL WOOL - OK. 3) PAT TLT 146 HEAD OF WALL / BEAM POCKETS MINERAL WOOL - OK. 4) CORRIDOR 144 N/E & N/W CORNER HEAD OF WALL / BEAM POCKETS MINERAL WOOL - OK. HW-D-0377 WAITING 101 SOUTH HEAD OF WALL MINERAL WOOL - OK. 1) 3B & 3C AT HEAD OF WALL , AS200 ELASTOMERIC SPRAY- OK PER HW-D-0377. 3/25/2026 1:57:20 PM DUPLICATE INSPECTION.

 03/26/2026B:FIRE SMOKE RESISTJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request3/25/2026 3:09:52 PM 3/25/2026 3:09 PM Gordon Galbraith 1st floor top of wall UL systems - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/26/2026 9:08:45 AM HW-D-0252, HW-D-0617 HEAD OF WALL MINERAL WOOL & AS 200 SRAY WITNESSES INSPECTION. 1) CORRIDOR 144 at EQPT/LINEN 157 2) SOILED 145 - NORTH & EAST HEAD OF WALLS- OK. 1) BARIATRIC 117- NORTH & EAST ROUGH FINISHED HEAD OF WALL & BEAM POCKET - OK.

 03/27/2026B:FIRE SMOKE RESISTMARTIN MAGERSPARTIALeTRAKiT Inspection Request3/26/2026 3:18:05 PM 3/26/2026 3:18 PM Gordon Galbraith 1st Floor Head of wall UL - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/27/2026 1:18:51 PM 1st floor head of wall at med prep and clean room, and soiled and pat toilet, and med lab rooms and surrounding corridors . A. Inspected mineral wool forming material as described in #5 HW-D-0252, HW-D-0617.. B FAS strap at clean room 135, mineral wool at flutes HW-D-0420

 03/31/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/30/2026 3:36:28 PM 3/30/2026 3:36 PM Kelly Sherman First Floor RC Channel - Brian E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 3/31/2026 9:05:57 AM RC CHANNEL 24" ON CENTER OAF- FULL HEIGHT SOUND PARTITION F- 1) CORRIDOR 144 EAST SIDE RC CHANNEL-OK EXAM 148 - EXAM 152 2) EXAM 148- OBSERVATION ROOM 153- OK. 3) EXAM 154- EXAM/TRIAGE 156- OK. 4) ISO EXAM 118 - OK. 5) EXAM - 125 - OK. 3/31/2026 9:53:37 AM RC CHANNEL 24" ON CENTER OAF- FULL HEIGHT SOUND PARTITION F- 1) CORRIDOR 144 EAST SIDE RC CHANNEL-OK EXAM 148 - EXAM 152 2) EXAM 148- OBSERVATION ROOM 153- OK. 3) EXAM 154- EXAM/TRIAGE 156- OK. 4) ISO EXAM 118 - OK. 5) EXAM - 125 - OK.

 03/31/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/30/2026 3:35:20 PM 3/30/2026 3:35 PM Kelly Sherman Level 1 Head of Wall UL System - Brian E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 3/31/2026 9:06:00 AM SPEC SEAL AS 200 SRAY 1) CORRIDOR 144, 137& 116- OK. 2) MED PREP 134/ CLEAN 135 / ED LAB 147 - OK. 3/31/2026 9:53:40 AM SPEC SEAL AS 200 SRAY 1) CORRIDOR 144, 137& 116- OK. 2) MED PREP 134/ CLEAN 135 / ED LAB 147 - OK.

 04/02/2026B:DRYWALLJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/1/2026 3:28:12 PM 4/1/2026 3:28 PM Gordon Galbraith 2nd Floor top of sound wall spray - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/2/2026 2:29:33 PM 2ND FLOOR - HEAD OF WALL DRYWALL , R13 & MINERAL WOOL INSULATION INSPECTION 1) CORRIDOR 206, 216 -OK.

 04/03/2026B:RGH PLUMBBRETT LONGNECKERPARTIALL1 Domestic & DWV, In-wall & Overhead4/2/2026 10:09:24 AM 4/2/2026 10:09 AM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 4/3/2026 10:09:49 AM DWV test and supports ok for 1st floor exam rooms on east side only highlighted in blue on P2.21A.1 and P2.21B.1. Photos uploaded. Domestic water test and supports ok for 1st floor exam rooms on east and west side highlighted yellow on P2.11A.1 and P2.11B.1. Photos uploaded.

 04/06/2026B:RGH PLUMBBRETT LONGNECKERCANCELeTRAKiT Inspection Request4/3/2026 2:30:58 PM 4/3/2026 2:30 PM Gordon Galbraith DWV in-wall & OH - plan north - Fabian w/CMS Contact Name: Fabian Mendez Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: ggalbraith@tcco.com 4/6/2026 9:41:25 AM Cancel per conversation with contractor.

 04/06/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request4/3/2026 10:14:48 AM 4/3/2026 10:14 AM Gordon Galbraith In-wall conduit & back box rough - 1st Floor Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/6/2026 11:02:43 AM Partial rough electrical approved Walls only on first floor/corridor (see photo) east side of first floor. Middle of first floor Please call in rough electrical to finish first floor rough walls. West side of 1st floor and corridor

 04/06/2026B:DRYWALLJOE CARBAUGHPARTIALDRYWALL & SCREW INSPECTION4/3/2026 2:33:01 PM 4/3/2026 2:33 PM Gordon Galbraith 1st floor screw inspection - rated walls - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/6/2026 2:49:07 PM DRYWALL & SCREW INSPECTION - 1) MED PREP 134 DRY WALL 8" EDGE & "12 FEILD - OK. NOTE: MISS LOCATED SINK DRAIN PIPE AT SAME WALL AS NOTED ABOVE TO BE INSPECTED BE FORE CLOSE OF WALL.

 04/06/2026B:RGH FRAMEJOE CARBAUGHPARTIAL2ND FLOOR HEAD OF WALL4/3/2026 2:32:26 PM 4/3/2026 2:32 PM Gordon Galbraith 2nd floor top out - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/6/2026 2:49:10 PM 2ND FLOOR HEAD OF WALL- 1) CORRIDOR 233/ SHELL SPACE DEMISING WALL- OK. 2) CONSULT / BH 242 DEMISING WALL EAST SIDE THROUGH LAB 234 - OK. 3) MD/APP 251 DEMISING WALL WEST SIDE THROUGH MP/APP 215/ STAFF LOUNGE- OK.

 04/07/2026B:RGH PLUMBBRETT LONGNECKERPARTIAL1st floor DWV4/6/2026 3:31:33 PM 4/6/2026 3:31 PM Gordon Galbraith Waste & Vent 1st Floor - water test Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/7/2026 3:20:17 PM DWV and water ok as highlighted in yellow on town approved plans P2.21.A.1 and P2.21.B.1.

 04/09/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request4/8/2026 3:27:02 PM 4/8/2026 3:27 PM Gordon Galbraith in-wall rough 1st floor - Dan w/Duro Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/9/2026 10:57:55 AM 1st floor TI rooms for wall rough electrical 106, 109, 111, 112, 113, 114, 118, 119, 123, 127, 128, 129, 131, 132, 133 ok for drywall 117 125 101 waiting for framing to be installed ****not ok to drywall****

 04/09/2026B:DRYWALLJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/8/2026 2:55:23 PM 4/8/2026 2:55 PM Gordon Galbraith Drywall 1st Floor - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/9/2026 3:13:50 PM DRYWALL SCREW INSPECTION- 1) CT TLT 115A- EAST WALL - OK.

 04/10/2026B:INSULATIONJOE CARBAUGHPARTIALLevel 1 Plumbing Insulation4/9/2026 10:22:12 AM 4/9/2026 10:22 AM COLORADO MECHANICAL SYSTEMS LLC Please contact Jeremy Phillips (720)392-3146. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 7203923146 e-Mail: AR@COLORADOMECH.COM 4/10/2026 3:15:12 PM PARTIAL- 1) SECOND FLOOR EDGED OF SLAB INSULATION (WEST WALL) / GRID LINES 4-6 MINERAL WOOL INSULATION (WITNESS) INSPECTION- 711119a HILTI - OK.

 04/13/2026B:DRYWALLJOE CARBAUGHPARTIALDRYWALL SCREW TOP ROCK & FIRE RIP4/10/2026 6:08:22 PM 4/10/2026 6:08 PM Gordon Galbraith Drywall 1st floor - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/13/2026 4:13:53 PM DRYWALL SCREW TOP ROCK & FIRE RIP INSPECTION 1) MGR OFFICE 159 DRYWALL INTERIOR SIDE NORTH EAST WALL - OK. 2) CORRIDOR 144 / NORTH & EAST PARTITION / EXAM TRIAGE 156 INTERIOR NORTH WALL & UL 377 - OK. 3) EQUIPMENT 157 ALL HEAD OF WALLS & FIRE RIP - OK. 4) PAT TLT 158 - ALL WALLS - OK. 5) EVS 157A - INTERIOR NORTH HEAD OF WALL-OK. NOTE: CMI FOR MEMBRANE AND THROUGH PENETRATIONS

 04/13/2026B:RGH FRAMEJOE CARBAUGHPARTIALWALL FRAME FIRST FLOOR4/10/2026 6:06:39 PM 4/10/2026 6:06 PM Gordon Galbraith Close wall frame inspection - 1st Floor - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/13/2026 4:13:56 PM WALL FRAME & CHANNEL TRACK FIRST FLOOR 1) EXAM 148 - EXAM TRIAGE 156 ALL WALLS - OK. 2) CORRIDOR- 144 EAST WALL- OK. 3) CORRIDOR 144 WEST / ALL ROOMS EXCEPT ED LAB 147;/ CORRIDOR 137 SOUTH & ED LAB 147/ CORRIDOR 116 EAST WALLS & ROOMS - 3a) **** ED LAB 147 (2) REPAIR STUDS N/E & INTER NORTH CORNER DAMAGED. *****

 04/13/2026B:RGH MECHJOE CARBAUGHPARTIALPre-Insulation & Damper Openings4/10/2026 1:20:34 PM 4/10/2026 1:20 PM COLORADO MECHANICAL SYSTEMS LLC Exam rooms, 148,149,151,152,153,154,155,&156 Nurses station 141 CT 115 Waiting 101 Fire dampers throughout 1 Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3035197973 e-Mail: AR@COLORADOMECH.COM 4/13/2026 4:13:58 PM PARTIAL- 1) JOINT / SEALED CONNECTIONS & SUPPORT - EXAM 148 - EXAM/ TRIAGE 156 - OK 2)JOINT / SEALED CONNECTIONS & SUPPORT - EAST WALLS OF ED LAB 147 - SOILED / - EVS 157a -OK. 3) JOINT / SEALED CONNECTIONS & SUPPORT - CORRIDOR 143 / NURSE STATION 141 / EQPT ALCOVE 139/ CORRIDOR 137 & NOURISH 142 - OK.

 04/14/2026B:INSULATIONJOE CARBAUGHCANCELeTRAKiT Inspection Request4/13/2026 5:35:40 PM 4/13/2026 5:35 PM Gordon Galbraith 1st floor sound insulation - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/14/2026 11:12:29 AM CANCELED- 1) CANCELED BY CONTRACTOR.

 04/14/2026B:RGH FRAMEJOE CARBAUGHPARTIALRGH FRAME WALLS4/13/2026 5:35:10 PM 4/13/2026 5:35 PM Gordon Galbraith frame 1st & 2nd floor - Brian E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/14/2026 11:12:25 AM PARTIAL- ROUGH FRAME WALLS FOR TOP OUT TI 2ND FLOOR 1) THE AMAZING WALLS BETWEEN EXAM 232-227 MANAGERS OFFICE 208& PHONE BANK 213 - OK 2) EXAM 247 & EXAM 245 DEMISE WALL- OK.

 04/14/2026B:RGH MECHJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/13/2026 5:38:33 PM 4/13/2026 5:38 PM Gordon Galbraith OH Rough - Rooms 109, 111-126 Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/14/2026 11:12:22 AM PARTIAL - DUCT ATTACHMENTS & JOINT CONNECTIONS INSPECTION BEFORE INSULATE. 1) ****SUPPORTS GREAT THAN 8' O.C. AT ISO EXAM 118 & ISO TLT 119 **** 2) EXAM 125 - STAFF LOUNGE 112- OK. 3) X-RAY 126- CT 115 - OK.

 04/14/2026B:RGH PLUMBBRETT LONGNECKERNOT APPROVEDPartial plumbing inspection in-wall4/13/2026 3:37:07 PM 4/13/2026 3:37 PM COLORADO MECHANICAL SYSTEMS LLC Domestic water. Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 4/14/2026 4:41:08 PM In wall rough for remaining 1st floor fixtures except for sw corner and drinking fountains.

 04/15/2026B:RGH FRAMEJOE CARBAUGHPARTIALCLOSE WALL RGH FRAMING INSPECTION4/14/2026 3:52:07 PM 4/14/2026 3:52 PM Gordon Galbraith 1st & 2nd Floor Frame - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/15/2026 3:01:34 PM PARTIAL- CLOSE WALL RGH FRAMING INSPECTION HIGHLIGHTED AREAS ON ATTACHMENT FOR A & B - CORRECTIONS - 1) MISSING PUTTY PADS FOR ELECTRICAL BOXES/MATERIALS MANAGEMENT/RECEIVING 132 EMS LOUNGE 129 AND STAFF TLT 131. 2) MISSING PUTTY PADS FOR ELECTRICAL BOXES/ BARIATRIC 117 / STAFF TLT 113 & STORAGE 114 NOTE: REST OF CLOSE WALL FRAMING HIGHLIGHTED IN ORANGE ON THE ATTACHMENT TO BE INSPECTED AT FUTURE INSPECTION.

 04/15/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/14/2026 5:48:25 PM 4/14/2026 5:48 PM Gordon Galbraith 1st floor - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/15/2026 3:01:32 PM PARTIAL- IST FLOOR TOP OUT R13 INSULATION INSPECTION 1) AREA's B & A HIGHLIGHTED IN GREEN FOR ATTACHED PLAN - OK.

 04/16/2026B:RGH PLUMBBRETT LONGNECKERPARTIALin wall pipe insulation4/15/2026 4:09:54 PM 4/15/2026 4:09 PM Gordon Galbraith 1st floor domestic water insulation - Fabian w/CMS Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/16/2026 9:44:20 AM 1st floor in wall domestic water pipe insulation ok.

 04/16/2026B:RGH FRAMEJOE CARBAUGHPARTIAL2nd FLOOR TOP OUT FRAMING4/15/2026 4:11:12 PM 4/15/2026 4:11 PM Gordon Galbraith 2nd floor frame - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/16/2026 9:55:48 AM PARTIAL- 2nd FLOOR TOP OUT HEAD OF WALL FRAMING 1) STORAGE 220, EVS 226, PATTLT 228, MA STATION 237, PAT TLT 246 & EXAM 248 - OK.

 04/17/2026B:INSULATIONJOE CARBAUGHPARTIALFIRST FLOOR INSULATION R13 INSPECTION.4/16/2026 4:18:32 PM 4/16/2026 4:18 PM Gordon Galbraith 1st floor insulation - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/17/2026 3:03:13 PM PARTIAL- FIRST FLOOR R13 INSULATION INSPECTION FOR EXAM ROOM 148 THROUGH EXAM TRIAGE - OK .

 04/17/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/16/2026 4:17:48 PM 4/16/2026 4:17 PM Gordon Galbraith 1st floor frame - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/17/2026 3:03:15 PM PARTIAL- FIRST FLOOR ITEMS CORRECTED BELOW- 1) MISSING PUTTY PADS FOR ELECTRICAL BOXES/MATERIALS MANAGEMENT/RECEIVING 132 EMS LOUNGE 129 AND STAFF TLT 131. 2) MISSING PUTTY PADS FOR ELECTRICAL BOXES/ BARIATRIC 117 / STAFF TLT 113 & STORAGE 114

 04/20/2026B:INSULATIONJOE CARBAUGHPARTIAL1st FLOOR WALL INSULATION MAP4/17/2026 3:07:31 PM 4/17/2026 3:07 PM Gordon Galbraith Insulation 1st floor - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/20/2026 3:16:14 PM PARTIAL- 1) EXAM 148 THROUGH EXAM/ TRIAGE 156 - OK. 2) EQPT/ LINEN 157 THROUGH MGR OFFICE 159 - OK. 3) CORRIDOR 137 (SOUTH) WALL - OK.

 04/20/2026B:RGH FRAMEJOE CARBAUGHPARTIALWALL FRAME COLUMNS D-C, 4-5.54/17/2026 3:06:57 PM 4/17/2026 3:06 PM Gordon Galbraith Frame 1st floor - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/20/2026 3:16:17 PM PARTIAL- WALL FRAME COLUMNS D-C, 4-5.5 1) EVS 157A THROUGH CT TLT 115A - OK **** WORK 104 / ELECTRICAL PENETRATION AT BOTTOM OF WALL N/ E CORNER**** 2) X-RAY 126 - CT 115 - OK. NOTE: 16 GAGE FRAMING IN X-RAY 126 & CT 115.

 04/21/2026B:INSULATIONJOE CARBAUGHPARTIALWALL INSULATION MAP 4/21/264/20/2026 3:38:45 PM 4/20/2026 3:38 PM Gordon Galbraith 1st floor insulation - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/21/2026 10:50:55 AM PARTIAL- 1) ED LAB 147 R13 INSULATION- OK.

 04/21/2026B:DRYWALLJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/20/2026 3:40:32 PM 4/20/2026 3:40 PM Gordon Galbraith 2nd floor stuff & spray top of wall - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/21/2026 10:50:53 AM PARTIAL- 1) 2ND FLOOR HEAD OF WALL INSULATION & SOUND SPRAY HILTI CP 572 - (EXCLUDING LAB 234). - OK.

 04/23/2026B:INSULATIONJOE CARBAUGHCANCELINTERIOR WALL R13 INSULATION4/22/2026 2:52:17 PM 4/22/2026 2:52 PM Kelly Sherman 1st Floor Insulation Inspection - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/23/2026 1:53:49 PM CANCELED - INSPECTION PER CONTRACTOR

 04/24/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request4/23/2026 2:41:07 PM 4/23/2026 2:41 PM Kelly Sherman 1st Floor Electrical Wall Rough TI - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/24/2026 9:36:09 AM Rough wall electrical partial approved Room 125, 117 on first floor wall rough only approved Notes Still waiting to inspect first floor lobby/ waiting room area. Walls are incomplete at this time of inspection

 04/27/2026B:RGH FRAMEJOE CARBAUGHPARTIALSOFFIT FRAMING4/24/2026 2:01:34 PM 4/24/2026 2:01 PM Kelly Sherman Frame inspection 1st Floor - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/27/2026 1:41:16 PM PARTIAL- SOFFIT FRAMING 1) EXAM 149 THROUGH EXAM/ TRIAGE 156 - OK.

 04/27/2026B:INSULATIONJOE CARBAUGHPARTIALINSULATION4/24/2026 2:01:34 PM 4/24/2026 2:01 PM Kelly Sherman Frame inspection 1st Floor - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/27/2026 1:41:19 PM PARTIAL- INSULATION INSPECTION -OK AS NOTED ON PICTURE ATTACHMENT.

 04/27/2026B:DRYWALLJOE CARBAUGHPARTIALDRYWALL SCREW INSPECTION4/24/2026 2:01:34 PM 4/24/2026 2:01 PM Kelly Sherman Frame inspection 1st Floor - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/27/2026 1:41:21 PM PARTIAL- DRYWALL SCREW INSPECTION 1) EQPT/ LINEN 157 ALL WALLS $ OUTSIDE EAST WALL -OK. 2) EVS 157a NORTH WALL - OK. 3) CORRIDOR 144 WEST WALL ED LAB 147 THROUGH SOILED 145 - OK 4) CORRIDOR 137 SOILED 145 THROUGH MED PREP 134 NORTH WALL - OK. 5) MED PREP 134 INSIDE & OUTSIDE NORTH & WEST WALLS AT GRID LINE 2.5 - OK. 6) CLEAN 135 - OK. 7) ED LAB 147 ALL WALLS - OK. 8) BOTH SIDES OF MATERIALS MANAGEMENT / RECEIVING 132 / STAFF TLT 131 & EMS LOUNGE 129 GRID LINES F 1.5 THROUGH 2.2 - OK.

 04/28/2026B:RGH PLUMBBRETT LONGNECKERPARTIALin wall rough 1st floor P2.11B.14/27/2026 4:04:21 PM 4/27/2026 4:04 PM Kelly Sherman Partial plumbing for L1 - Fabian w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/28/2026 11:47:18 AM In wall domestic water rough ok as highlighted on P2.11B.1 in blue.

 04/28/2026B:INSULATIONJOE CARBAUGHCANCELeTRAKiT Inspection Request4/27/2026 4:07:17 PM 4/27/2026 4:07 PM Kelly Sherman Insulation & Firestopping 1st Floor - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/28/2026 12:33:28 PM CANCELED.

 04/28/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/27/2026 4:07:17 PM 4/27/2026 4:07 PM Kelly Sherman Insulation & Firestopping 1st Floor - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/28/2026 12:33:31 PM PARTIAL- 1) WITNESS FIRE STOP STI/JF 120-01 AT HEAD OF WALL 4a & 4b MED PREP 134 , SOILED 145 & ED LAB 147 - OK. ( packing material is mineral fiber insulation for compression and joint openings.)

 04/29/2026B:RGH PLUMBBRETT LONGNECKERPARTIALpipe insulation4/28/2026 4:22:27 PM 4/28/2026 4:22 PM Kelly Sherman In Wall Copper - Fabian w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/29/2026 11:40:49 AM In wall pipe insulation for pipe inspected 4/28/26.

 04/29/2026B:FIRE SMOKE RESISTJOE CARBAUGHFIRST LAYER 5/8 GYP TYPE X FOR 2nd FLOOR IT ROOMPARTIAL4/29/2026 3:01:30 PM PARTIAL- 1) FIRST LAYER 5/8 TYPE X GYP FOR 2nd FLOOR IT ROOM ALL WALLS - OK.

 04/29/2026B:RGH FRAMEJOE CARBAUGHPARTIALTI FRAME FURRED OUT WALLS4/28/2026 4:21:39 PM 4/28/2026 4:21 PM Kelly Sherman 1st Floor - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/29/2026 3:00:51 PM PARTIAL- (TI FRAME FURRED OUT WALLS) 1) PUBLIC TLT 106 EAST WALL FRAME - OK. 2) SOILS 145 SOUTH WALL FRAMING AROUND PLUMBING- OK. 3) CORRIDOR 144 SOUTH END WALL - OK 4) EXAM 148 SOUTH WALL & FIRE RATED BACKING - OK.

 05/04/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request4/30/2026 2:21:26 PM 4/30/2026 2:21 PM Kelly Sherman 1st Floor TI Wall Rough - Dan w/ Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/4/2026 9:47:29 AM Rough electrical partial approved Rough electrical for walls only 1st floor rough electrical for TI is complete please recall inspection when 2nd floor TI is ready.

 05/04/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/30/2026 2:30:30 PM 4/30/2026 2:30 PM Kelly Sherman Framing 1st Floor TI - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/4/2026 10:48:23 AM PARTIAL- SOFFIT FRAMING 1) ED LAB 147 - OK. 2) ISO EXAM 118 - OK. 3) BARIATRIC 117 - OK.

 05/04/2026B:RGH PLUMBBRETT LONGNECKERCANCELPartial Overhead Domestic & In-wall4/30/2026 1:13:18 PM 4/30/2026 1:13 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 5/4/2026 1:46:55 PM Cancel per conversation with Fabian.

 05/06/2026B:RGH PLUMBMARTIN MAGERSCANCELPartial Overhead Domestic Water5/5/2026 1:27:30 PM 5/5/2026 1:27 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 5/6/2026 12:36:53 PM Canceled per call with Gordon. He told me the site was closed today. Please cancel inspections that will not be ready.

 05/07/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request5/6/2026 7:29:15 PM 5/6/2026 7:29 PM Gordon Galbraith 1st floor domestic water - Fabian w/CMS - reinspection for failed inspection on 5/4 Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 5/7/2026 12:16:08 PM In wall and over head as marked on P2.11A1 and P2.11B.1

 05/11/2026B:RGH MECHJOE CARBAUGHPARTIALeTRAKiT Inspection Request5/8/2026 3:57:58 PM 5/8/2026 3:57 PM Kelly Sherman FIrst Floor South MP Square & Round - Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/11/2026 2:27:08 PM CANCELED- See 5/11/2026 INSULATION INSPECTION. UPDATED NOTES: INSPECTOR JOE CARBAUGH , 5/11/26 - MEDIUM PRESS 144 SOILED 145 - OK. LOW PRESS SQUARE - TB-E 1-07 - OK. NOTE: SEE CLOUDED AREA FOR INSPECTION ATTACHMENT .

 05/11/2026B:INSULATIONJOE CARBAUGHPARTIALLevel 1 Domestic Water Insulation5/8/2026 11:42:50 AM 5/8/2026 11:42 AM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 5/11/2026 2:27:10 PM PARTIAL- 1) PIPE INSULATION INSPECTION FOR HIGHLIGHTED AREAS FIRST FLOOR AREA'S A & B .

 05/12/2026B:RGH PLUMBMARTIN MAGERSCANCELLevel 2 In-Wall Rough5/8/2026 11:42:50 AM 5/8/2026 11:42 AM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 5/8/2026 4:03:32 PM 5/8/2026 4:03 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 5/12/2026 2:03:50 PM Canceled per call with Fabian. Site not ready.

 05/13/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request5/12/2026 1:57:24 PM 5/12/2026 1:57 PM Kelly Sherman 2nd Floor Wall Rough TI Electrical - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/13/2026 10:45:42 AM Rough electrical partial approved walls only Rooms wall rough that are approved 238 239 241 242 244 245 247 249 253 236 235 234 231 232 229 228 246 248 226 220 227 225 213 208 205 Notes Ok to drywall if all other inspections are approved Please call in rough inspection when ready to finish 2nd floor walls Millwork on second floor will need a rough electrical inspection when millworkers installed

 05/13/2026B:RGH FRAMEJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request5/12/2026 2:12:24 PM 5/12/2026 2:12 PM Kelly Sherman 2nd Floor Frame - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/13/2026 1:29:14 PM APPROVED- 1) SOUND SEPARATION FOR RFI 32 a) EXAM ROOMS - 245,247 - OK. b) PAT TLT 228 & EVS 226 - OK. c) EXAM ROOMS 229 & 227 - OK. d) ADMIN WORK 205 & MANAGER OFFICE 208 - OK.

 05/13/2026B:RGH PLUMBMARTIN MAGERSCANCELeTRAKiT Inspection Request5/12/2026 1:58:02 PM 5/12/2026 1:58 PM Kelly Sherman Mechanical - Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/13/2026 2:44:22 PM Site not ready per Fabio

 05/14/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request5/13/2026 5:19:48 PM 5/13/2026 5:19 PM Kelly Sherman TI Wall Rough - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/14/2026 10:00:28 AM Rough electrical inspection partial approved Rooms approved ***walls only*** 222 221 219 218 217 215 214 211 mdapp Ok to drywall

 05/14/2026B:RGH MECHJOE CARBAUGHPARTIALeTRAKiT Inspection Request5/13/2026 5:20:37 PM 5/13/2026 5:20 PM Kelly Sherman HVAC First Floor Fire Dampers Room 134 - Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/14/2026 12:12:33 PM PARTIAL- ANGLER SPACE , SUPPORT & SEAL INSPECTION. 1) PAT TLT 146, SOILED 145, CLEAN 135 & MED PREP 134 - OK.

 05/14/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request5/13/2026 2:06:22 PM 5/13/2026 2:06 PM Kelly Sherman 2nd Floor Wall Frame, Non Plumbing Walls Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/14/2026 12:12:36 PM PARTIAL- 2nd FLOOR WALL FRAMING 1) SHELL SPACE THROUGH LAB 234 FRAME - OK. NOTE: HLTI DOC FLOOR PENETRATIONS TO BE CHECKED AT FUTURE INSPECTION.

 05/14/2026B:RGH PLUMBMARTIN MAGERSPARTIALeTRAKiT Inspection Request5/13/2026 5:21:15 PM 5/13/2026 5:21 PM Kelly Sherman In Wall Plumbing Level 2 - Fabian w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/14/2026 12:28:42 PM 2nd Floor walls DWV and water as marked on P2 pages.

 05/19/2026B:RGH FRAMEJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request5/18/2026 2:27:37 PM 5/18/2026 2:27 PM Kelly Sherman 2nd Floor Frame - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/19/2026 12:00:23 PM NOT APPROVED- SEE ITEM 2) 2ND FLOOR WALL FRAMING & FIRES-TOP 1) PLUMBING HLTI FLOOR SLEEVES EXAM/ PROCEDURE 241 THROUGH LAB TLT 235- OK. 2) **** MISSING HLTI SLEEVE FOR PLUMBING FLOOR PENETRATION IN EXAM 244 / EXAM 245 **** 3) **** MISSING HLTI SLEEVE FOR ELECTRICAL PENETRATION IN ADMIN WORKS 205 SOUTH WALL TI. 4) **** MISSING HLTI SLEEVE FOR ELECTION PENETRATION IN LAB 234**** 1) 2ND FLOOR FRAMING COMPLETE - OK SEE ATTACHMENT.

 05/19/2026B:RGH PLUMBMARTIN MAGERSPARTIALLevel 2 In-wall Inspection5/18/2026 2:10:23 PM 5/18/2026 2:10 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745 Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 5/19/2026 2:45:51 PM In wall water and drain for 2nd. East exam room and water for South central exam rooms. Water Marked in green on page P2.12A.1 and P2.12B1 . DWV on PP2.22A.1 and P2.22B.1 in yellow.

 05/20/2026B:INSULATIONMARTIN MAGERSPARTIALLvl 1 Overhead Plumbing Insulation5/19/2026 2:50:17 PM 5/19/2026 2:50 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM

 05/22/2026B:INSULATIONJOE CARBAUGHNOT APPROVEDLvl 2 Plumbing Insulation5/21/2026 1:18:15 PM 5/21/2026 1:18 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303) 704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 5/22/2026 11:37:23 AM NOT APPROVED- SOUND WALL INSULATION INSPECTION NOT REQUIRED.

 05/22/2026B:RGH MECHJOE CARBAUGHPARTIALLvl 2 Duct Inspection5/21/2026 1:17:19 PM 5/21/2026 1:17 PM COLORADO MECHANICAL SYSTEMS LLC Core & Shell and TI level 2 duct inspection. Please contact Nick Padrevita (303) 859-9954. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3038599954 e-Mail: AR@COLORADOMECH.COM 5/22/2026 11:37:25 AM PARTIAL 1) LVL DUCT SEAL & SUPORT FOR CORRIDOR 206 & CORRIDOR 216 & MANAGERS OFFICE 208 - OK.

 05/22/2026B:RGH PLUMBMARTIN MAGERSPARTIALLvl 2 In-Wall Inspection5/21/2026 9:33:56 AM 5/21/2026 9:33 AM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303) 704-9745. Crew is offsite at 3:30pm Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 5/22/2026 2:13:20 PM Water in wall as marked in green on P2.12A1 and DWV as marked in yellow on P2.22A1 all second floor walls ok except drinking fountain.

 05/27/2026B:RGH MECHJOE CARBAUGHPARTIALHVAC Inspection Level 1 & 25/26/2026 1:51:24 PM 5/26/2026 1:51 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Nick Padrevita (303)859-9954. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3038599954 e-Mail: AR@COLORADOMECH.COM 5/27/2026 3:21:58 PM PARTIAL- 1) 1st FLOOR- SEAL & SUPPORT - ED LAB 147 - SOILED 145 / CORRIDOR 144 -OK . 2) 2nd FLOOR SEAL & SUPPORT- GRID LINE C TO B & WAITING 202 / CORRIDOR 233 - OK.

 05/28/2026B:RGH MECHJOE CARBAUGHPARTIALeTRAKiT Inspection Request5/27/2026 2:36:11 PM 5/27/2026 2:36 PM Gordon Galbraith Second Floor, East & West perimeter rooms - CMS Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 5/28/2026 12:57:43 PM PARTIAL- SEAL & SUPPORT- 2nd FLOOR. 1) MD/APP 251 THROUGH MD/ APP 215 - OK.

 06/01/2026B:FIRE SMOKE RESISTJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request5/29/2026 12:52:49 PM 5/29/2026 12:52 PM Kelly Sherman Firestopping with CMI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/1/2026 1:19:48 PM NOT APPROVED- NOTE: COURTESY MEETING WITH CMI & CONTRACTOR REVIEW & DISCUSSION FOR HORIZONTAL FIRE-STOP SYSTEM INSPECTIONS.

 06/02/2026B:RGH MECHMARTIN MAGERSCANCELeTRAKiT Inspection Request6/1/2026 8:38:13 AM 6/1/2026 8:38 AM Kelly Sherman 1st & 2nd Floor Low Press Square - Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/2/2026 7:15:24 AM CANCELED- NOTE: DUPLICATE INSPECTION.

 06/02/2026B:RGH PLUMBMARTIN MAGERSPARTIAL1st floor domestic overhead6/1/2026 2:48:16 PM 6/1/2026 2:48 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 6/2/2026 11:39:17 AM First for domestic water piping complete. Needs insulation. 6/2/2026 1:12:35 PM Drinking fountain DWV and water for first floor approve. Still needs insulation.

 06/02/2026B:RGH MECHMARTIN MAGERSPARTIAL1st floor steam piping6/1/2026 2:48:17 PM 6/1/2026 2:48 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 6/2/2026 1:12:38 PM All steam piping approve on first floor. Still needs insulation.

 06/03/2026B:RGH MECHJOE CARBAUGHPARTIAL2nd Floor Low Pressure6/2/2026 2:02:09 PM 6/2/2026 2:02 PM COLORADO MECHANICAL SYSTEMS LLC Please call Nick Padrevita (303)859-9954. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3038599954 e-Mail: AR@COLORADOMECH.COM 6/3/2026 11:28:11 AM PARTIAL- 1) SEAL and SUPPORT SECOND FLOOR AS MARKED- OK.

 06/05/2026B:DRYWALLJOE CARBAUGHPARTIALeTRAKiT Inspection Request6/4/2026 3:06:12 PM 6/4/2026 3:06 PM Gordon Galbraith Screw inspection for lead lined drywall in 1st floor CT & XRay procedure rooms - Brian with E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/5/2026 11:21:03 AM PARTIAL- 1) DRYWALL & SCREW INSPECTION FOR X-RAY 122 & CT 115 - OK.

 06/09/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request6/8/2026 4:13:03 PM 6/8/2026 4:13 PM Gordon Galbraith hardlid frame inspection - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/9/2026 11:01:35 AM PARTIAL- 1st FLOOR DROP CEILING FRAMING CORRIDOR 237, NOURISH 142 EQPT ALCOVE 139 - OK. NOTE: OK OFR DRYWALL PENDING RGH ELECTRICAL.

 06/09/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request6/8/2026 4:16:54 PM 6/8/2026 4:16 PM Gordon Galbraith hard lid rough to allow rock 1st floor - Dan w/Duro Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/9/2026 11:44:17 AM Rough electrical inspection partial approved for hard lids only on first floor TI bathroom hard lids. Location 1. South/ West side of building. Location 2 south/east bathroom x2 Corridor soffits in first floor hallways Please call the rest of hard lids inspections when ready

 06/10/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request6/9/2026 8:40:02 PM 6/9/2026 8:40 PM Gordon Galbraith Complete TI hard lid rough inspection, 1st floor - Dan with Duro Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/10/2026 8:57:39 AM Rough electrical ceiling partial inspection approved hard lids only on TI first floor Rooms 158, 113, 119 hard lid inspection

 06/10/2026B:FIRE SMOKE RESISTJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request6/9/2026 8:39:07 PM 6/9/2026 8:39 PM Gordon Galbraith Inspection to coordinate with State fire inspector Christian Morales with respect to rated wall inspections performed by Joe Carbaugh. Request is for 9:30am to conincide with State inspector''s hard lid fire sprinkler inspection. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/10/2026 2:26:20 PM NOT APPROVED- MEETING WITH CASTLE ROCK FIRE, STATE & BUILDER FOR FIRE RESIST. 6/10/2026 3:15:19 PM NOT APPROVED- MEETING WITH CASTLE ROCK FIRE, STATE & BUILDER FOR FIRE RESIST.

 06/10/2026B:RGH MECHJOE CARBAUGHPARTIAL2nd Floor Low Pressure Round6/9/2026 1:32:41 PM 6/9/2026 1:32 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Nick Padrevita (303)859-9954. Crew is offsite at 3:30pm Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3038599954 e-Mail: AR@COLORADOMECH.COM 6/10/2026 2:26:25 PM PARTIAL- 1) SEAL AND SUPPORT IN MARKED AREAS- OK. 6/10/2026 3:15:25 PM PARTIAL- 1) SEAL AND SUPPORT IN MARKED AREAS- OK.

 06/15/2026B:RGH MECHJOE CARBAUGHPARTIAL1st floor RA FDs6/12/2026 1:03:41 PM 6/12/2026 1:03 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Nick Padrevita (303)859-9954. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3038599954 e-Mail: AR@COLORADOMECH.COM 6/15/2026 2:04:20 PM NOT APPROVED- 1) FIRST FLOOR SEAL, SUPPORT & ANGLE INSPECTION. 2) UNABLE TO VERIFY HORIZONTAL ANGEL SUPPORT DUE TO DRYWALL.

B:RGH PLUMBBRETT LONGNECKER1st Floor Hard-Lid Inspection6/16/2026 9:24:58 AM 6/16/2026 9:24 AM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM

 06/18/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request6/17/2026 3:49:29 PM 6/17/2026 3:49 PM Kelly Sherman Overhead Inspection Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/18/2026 2:30:06 PM Rough electrical inspection partial approved Hard lid inspections only 1. Room 133 verify 2 access panels at final electrical 2. Room 128 verify 3 access panels at final electrical 3. Room 115 a verify 1 access panel at final electrical inspection 4. Room 106 good

 06/18/2026B:RGH PLUMBMARTIN MAGERSPARTIAL1st Floor Hard-Lid Plumbing Inspection6/16/2026 1:47:37 PM 6/16/2026 1:47 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745 Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 6/18/2026 2:37:53 PM All hard rooms with hard lids have the insulation approved, and the labels are approved in all of these rooms except bathroom 106 is missing condensate labels. The condensate labels will be visible from an access panel.

 06/22/2026B:RGH MECHJOE CARBAUGHPARTIALeTRAKiT Inspection Request6/17/2026 3:50:22 PM 6/17/2026 3:50 PM Kelly Sherman Mechanical w/Nick CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/22/2026 6:49:13 AM

 06/22/2026B:RGH PLUMBMARTIN MAGERSPARTIAL2nd Floor Overhead Vent6/19/2026 1:25:53 PM 6/19/2026 1:25 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 6/22/2026 3:12:38 PM All drain waste and vent for 2nd Floor approved.

 06/22/2026B:RGH FRAMEJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request6/18/2026 3:03:19 PM 6/18/2026 3:03 PM Kelly Sherman Level 1 Hardlid Inspection Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/22/2026 3:20:28 PM NOT APPROVED. NOTE : RESCHEDULE ABOVE GRID FOR TOMORROW 6/23/26.

 06/23/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request6/22/2026 3:14:41 PM 6/22/2026 3:14 PM Kelly Sherman Level 1 Hardlid Inspection Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/23/2026 1:37:36 PM PARTIAL- 1) FIRST FLOOR ROUGH MEP'S ABOVE HARD LID (ONLY) - APPROVED. 2) FIRST FLOOR MINERAL WOOL AT HEAD OF WALL IN ALL HARD LID ROOMS - OK. 3) (E) STAIR SOUTH ES01 SECOND FLOOR HARD LID - OK. NOTE: CONFIRM CASTLE ROCK FIRE SPRINKLER ABOVE HARD LIDS ARE OK BEFORE CLOSE OF HARD LIDS.

 06/25/2026B:RGH PLUMBMARTIN MAGERSPARTIALeTRAKiT Inspection Request6/24/2026 2:40:49 PM 6/24/2026 2:40 PM Kelly Sherman 2nd Floor Overhead Domestic Water - Fabian w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/25/2026 2:51:05 PM All 2nd floor water lines approved and roof hydrant. Still needs insulation.

 06/15/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request6/12/2026 6:40:00 PM 6/12/2026 6:40 PM Gordon Galbraith Balance of level 1 hard lid inspections - Dan w/Duro Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/15/2026 10:19:56 AM Rough electrical inspection for hard lid ceilings only Rooms approved 125,118 Note. Will verify at final electrical inspection access panel to be installed in room 118.

 06/30/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request6/29/2026 2:59:24 PM 6/29/2026 2:59 PM Kelly Sherman Level 2 Hardlids - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/30/2026 10:35:13 AM 2nd floor Room 235 hard lid inspection only partial approved 1st floor TI hard lids complete

 06/30/2026B:RGH MECHJOE CARBAUGHPARTIALeTRAKiT Inspection Request6/29/2026 3:01:24 PM 6/29/2026 3:01 PM Kelly Sherman Lvl 1 Control Rm - Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/30/2026 2:52:04 PM PARTIAL- 1) FIRST FLOOR - SEAL & SUPPORT- OK. 2) FIRST FLOOR SEAL & SUPPORT AT CONTROL ROOM 121 SECOND FLOOR 1) SEAL, SUPPORT & ANGULAR SPACES- OK.

 07/01/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request6/30/2026 1:57:22 PM 6/30/2026 1:57 PM Kelly Sherman Level 2 Hardlid Inspection Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/1/2026 9:37:51 AM 2nd floor TI hard lid only inspection partial approved Hard lid rooms inspected 226, 246, 243, 203, 209, 224 corridor hard lid, 228, 246, 243 corridor hard lid

B:ELECT CONST METEReTRAKiT Inspection Request7/7/2026 8:41:14 AM 7/7/2026 8:41 AM Kelly Sherman All Gas Piping - Fabian w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com

 07/07/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request7/6/2026 1:51:04 PM 7/6/2026 1:51 PM Kelly Sherman Level 2 Hardlids - Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/7/2026 3:11:20 PM PARTIAL - 1) 2nd FLOOR HARD LID - OK (EXCEPT WAITING 102 OF FIRST FLOOR & WAITING 202 SECOND FLOOR. NOTE: WAITING 102 & WAITING 202

 07/08/2026B:GAS PIPE AIR TESTMARTIN MAGERSAPPROVEDeTRAKiT Inspection Request7/7/2026 8:44:17 AM 7/7/2026 8:44 AM Kelly Sherman All Gas Piping - Fabian w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/8/2026 3:26:29 PM No gas pipe on the TI

 07/09/2026B:RGH MECHJOE CARBAUGHPARTIALeTRAKiT Inspection Request7/8/2026 2:03:45 PM 7/8/2026 2:03 PM Kelly Sherman Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/9/2026 9:37:22 AM PARTIAL- 1) EXHAUST INSULATION FOR 2nd FLOOR SHELL SPACE- OK.

 07/22/2026B:INSULATIONJOE CARBAUGHNOT APPROVEDLabel Inspection7/21/2026 11:05:16 AM 7/21/2026 11:05 AM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-8745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 7/22/2026 11:04:23 AM NOT APPROVED. 1) MISSING LABELS ABOVE GRID IN ED Lab 147, EXAM ROOM 151 /152 , ROOM 154 & 155. 2) REST OF FIRST FLOOR ABOVE GRID LABELS- OK. NOTE: RECALL INSPECTION WHEN MISSING ITEMS HAVE BE COMPLETE. 7/22/2026 11:06:16 AM NOT APPROVED.

 07/24/2026B:RGH MECHJOE CARBAUGHPARTIALeTRAKiT Inspection Request7/23/2026 10:18:41 AM 7/23/2026 10:18 AM Kelly Sherman Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/24/2026 11:28:39 AM PARTIAL- 1) SEAL & SUPPORT SECOND FLOOR

 07/29/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request7/28/2026 3:06:22 PM 7/28/2026 3:06 PM Kelly Sherman 2nd Floor Hardlid - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/29/2026 9:45:13 AM Rough electrical inspection partial approved Notes 2nd floor hard lid inspection (waiting room) 2nd floor hard lids complete

 07/29/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request7/28/2026 3:05:46 PM 7/28/2026 3:05 PM Kelly Sherman Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/29/2026 11:28:33 AM PARTIAL- 1) RGH FRAMING OF HARD LID / EAST SIDE SECOND FLOOR WAITING 202 - OK. NOTE: RGH MECHANICAL TO BE INSPECTED BEFORE CLOSE OF HARD LID.

 07/30/2026B:RGH MECHJOE CARBAUGHPARTIALeTRAKiT Inspection Request7/29/2026 2:26:21 PM 7/29/2026 2:26 PM Kelly Sherman 2nd Floor Lobby - Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/30/2026 1:44:48 PM PARTIAL- 1) SEAL,SUPPORT & DUCT INSULATION -OK / SECOND YARD , WAITING 201

 08/04/2026B:ELECTRICAL SERVICEVINCE RAPONEPARTIALeTRAKiT Inspection Request8/3/2026 2:26:02 PM 8/3/2026 2:26 PM Gordon Galbraith Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: daniel.castro@duroelectric.com 8/4/2026 11:27:27 AM Transformer to userk cabinet approved Userk to mdp approved Okay to release meter Schedule electrical service when mdp is ready for inspection to complete electrical service

 08/04/2026B:ROUGH PLUMBINGMARTIN MAGERSAPPROVEDPlumbing Label & Insulation Inspection8/3/2026 3:26:47 PM 8/3/2026 3:26 PM COLORADO MECHANICAL SYSTEMS LLC Please call Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 8/4/2026 3:31:17 PM All labeling complete including all 2nd fl and ED room and 149 corrections. All rough plumbing complete.

 08/07/2026L: BACKFLOW SURVEY INSPECTIONERIN SWEENEYAPPROVEDSee notes.8/7/2026 11:09:38 AM Appropriate backflow protection for use and level of hazard. Passing test reports required prior to issuance of C.O. or T.C.O. Any questions please contact Erin Sweeney at xconnection@crgov.com or 720-733-6020. Field notes attached.

 08/11/2026U:METER SET COMMGRANT TAYLORMETER INSP FAIL 18/11/2026 3:05:50 PM Inspection fail fee needs to be added, standard notes won't work. Water needs to be charged up to #2 shutoff on back flow for inspection to be valid

 08/13/2026B:RGH MECHJOE CARBAUGHPARTIALeTRAKiT Inspection Request8/12/2026 3:20:44 PM 8/12/2026 3:20 PM Kelly Sherman First Floor TI West - Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 8/13/2026 1:45:05 PM PARTIAL- FIRST FLOOR ABOVE GRID SEAL & SUPPORT. OK.

 08/24/2026B:FIRE SMOKE RESISTJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request8/21/2026 2:40:39 PM 8/21/2026 2:40 PM Gordon Galbraith Rated wall penetration inspection to close ceilings, 1st & 2nd Floor Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 8/24/2026 3:33:01 PM NOT APPROVED- 1) INSPECTION WAS TURNED INTO A CONSULTATION ABOUT FIRE STOP SYSTEM INDUCTING THROUGH THROUGH PENETRATIONS.

 08/24/2026B:RGH MECHJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request8/21/2026 2:07:55 PM 8/21/2026 2:07 PM Kelly Sherman Above Ceiling - Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 8/24/2026 3:33:04 PM NOT APPROVED- 1) MANUFACTURERS INSTALLATION INSTRUCTIONS FIRE DAMPERS TO BE ON SITE AT NEXT INSPECTION.

 08/25/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request8/24/2026 7:43:00 PM 8/24/2026 7:43 PM Gordon Galbraith Visual on ceiling grid, 1st floor. Looking to drop ceiling tiles in locations that correspond with passed above ceiling MEP inspections. ***Tiles will be left out along rated walls*** Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 8/25/2026 3:12:52 PM PARTIAL- 1) FIRST FLOOR GRID CEILING SUPPORT- OK. X RAY 126 STORAGE 114 STAFF LOUNGE 112 STORAGE 111 SLEEP 109 ED LAB 147

 08/25/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request8/24/2026 1:17:19 PM 8/24/2026 1:17 PM Gordon Galbraith Above ceiling in ACT areas, 1st floor. Inspection to drop ceiling tiles. Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 8/25/2026 3:13:21 PM Rough electrical inspection partial approved 1st floor drop ceiling inspection 114, 112, 111, 109, 126, 147 rooms approved

 08/27/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request8/26/2026 2:02:23 PM 8/26/2026 2:02 PM Gordon Galbraith Reinspection of 1st floor ceiling grid. Scheduling electrical inspection for same time. Please coordinate with Sean or Vince if possible. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 8/27/2026 2:37:42 PM PARTIAL- 1) FIRST FLOOR GRID SUPPORTS FOR THE FOLLOWING- OK. CORRIDORS 144, 137, 143 & 119 ROOMS 141, 159, 157, 157a, 115, 117 & 121

 08/27/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request8/26/2026 2:04:39 PM 8/26/2026 2:04 PM Gordon Galbraith Reinspection of 1st floor gird. Rough frame called for same time. Please coordinate with Joe if possible. Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 8/27/2026 3:22:29 PM Rough electrical inspection partial approved 1st floor drop ceiling only corridors 1st floor approved 144, 137, 143, 119 Rooms 1st floor 141, 159, 157 157a 115 117, 121

 08/31/2026B:FIRE SMOKE RESISTJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request8/28/2026 7:36:02 AM 8/28/2026 7:36 AM Gordon Galbraith rated wall firestopping. State Fire will be on site from 1-3pm. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/1/2026 6:56:31 AM NOT APPROVED- 1) FIRE STOP & SMOKE RESIST PRE- WALK.

 09/03/2026B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request9/2/2026 6:38:12 PM 9/2/2026 6:38 PM Gordon Galbraith 1st floor OH Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 9/3/2026 12:51:22 PM Above ceiling approved Corridor west

 09/04/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/3/2026 4:49:31 PM 9/3/2026 4:49 PM Gordon Galbraith 1st floor reception ceiling grid. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/4/2026 1:24:45 PM PARTIAL- 1) FIRST FLOOR WAITING 101 CEILING GRID & WIRE - OK.

 09/10/2026B:FIRE SMOKE RESISTJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request9/9/2026 10:57:08 PM 9/9/2026 10:57 PM Gordon Galbraith state fire will be on site at 1pm. if inspections can conincide that would be preferable. rated wall penetrations, 1st & 2nd floors Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/10/2026 1:16:09 PM NOT APPROVED- 1) PRE-WALK FOR FIRE SMOKE RESIST.

 09/11/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request9/10/2026 11:49:14 AM 9/10/2026 11:49 AM Gordon Galbraith Mat Mgmt / Receiving 132, EMS Lounge 129, 1st floor exam rooms, & as much of 2nd floor OH as there is time for. Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 9/11/2026 2:46:37 PM Rough electrical partial inspection approved 2nd floor drop ceiling inspection rooms approved 234, 236, 238, 239, 241, 242 1st floor drop ceiling inspection rooms approved 155, 154, 153, 152, 151, 149, 148, 127, 129, 132, 155, 156 Notes Ceiling tiles have been installed in room 135, 134 rough ceiling inspection has not been approved ceiling tiles need to be removed for inspection

 09/11/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/10/2026 2:08:02 PM 9/10/2026 2:08 PM Gordon Galbraith Rated wall penetrations on 1st & 2nd floor. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/11/2026 2:55:31 PM PARTIAL- 1) TI ROOMS - APPROVED. 2) CORE & SHELL HORIZONTAL PENETRATION - APPROVED Note: CORE & SHELL VERTICAL PENETRATIONS TO BE INSPECTED AT TIME OF STOCK & TRAIN INSPECTION.

 09/11/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/10/2026 11:49:48 AM 9/10/2026 11:49 AM Gordon Galbraith Mat Mgmt / Receiving 132, EMS Lounge 129, 1st floor exam rooms, & as much of 2nd floor OH as there is time for. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/11/2026 2:55:37 PM PARTIAL- 2nd FLOOR GRID CEILING 243, 236,238,239,241 & 242 - OK. 1ST FLOOR GRID CEILING 155, 154,153,152,149,148,127,129,132,155 & 156 - OK. NOTE: CORRIDORS TO BE CHECKED AT FUTURE INSPECTION.

 09/15/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request9/14/2026 11:53:11 AM 9/14/2026 11:53 AM Gordon Galbraith 2 missed rooms on the 1st floor and 2nd floor grid. Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 9/15/2026 3:28:19 PM Rough electrical inspection partial approved drop ceilings 1st floor rooms approved 134, 135 2nd floor rooms approved 222, 251, 249, 253, 247, 245, 244, 215, 217, 218, 219, 221 2nd floor corridors partials south corridor 216. South corridor 233

 09/15/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/14/2026 11:49:57 AM 9/14/2026 11:49 AM Gordon Galbraith 2 missed rooms on the 1st floor and 2nd floor grid. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/15/2026 3:36:55 PM PARTIAL- GRID SUPPORT - FIRST 134,135 - OK. SECOND FLOOR 222, 251, SOUTH CORRIDOR 216, 249,253,247,245,244 & SOUTH CORRIDOR 233 215,217,218,219 & 221- OK.

 09/16/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/15/2026 4:11:54 PM 9/15/2026 4:11 PM Gordon Galbraith Grid inspection 2nd floor corridors & remaining rooms Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/16/2026 3:23:09 PM PARTIAL- 1) SECOND FLOOR GRID SUPPORT IN 232,229,227,225,213,214,211- OK. 2) FIRST FLOOR GRID SUPPORT NURSE STATION 141, RECEPTION 102 -OK.

 09/16/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request9/15/2026 4:14:41 PM 9/15/2026 4:14 PM Gordon Galbraith 1st floor nurse & reception casework boxes, 2nd floor OH corridors & remaining standalone rooms Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 9/16/2026 3:25:18 PM Rough electrical inspection partial approved 2nd floor drop ceiling inspection 232, 229, 227, 225, 213, 214, 211. Casework inspection 1st floor Nurse station 141, reception 102

 09/17/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request9/16/2026 6:16:09 PM 9/16/2026 6:16 PM Gordon Galbraith Remainder of 2nd floor grid Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 9/17/2026 3:18:52 PM Rough electrical inspection partial approved Case work room 204 2nd floor Middle south corridor 216 2nd floor drop ceiling North corridor 206 2nd floor drop ceiling

 09/17/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/16/2026 6:14:07 PM 9/16/2026 6:14 PM Gordon Galbraith Remainder of 2nd floor grid Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/17/2026 3:32:53 PM PARTIAL- GRID SUPPORT 204,216,206 - OK.

 09/18/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request9/17/2026 5:16:05 PM 9/17/2026 5:16 PM Gordon Galbraith Remainder of level 2 OH Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 9/18/2026 2:15:44 PM Rough electrical partial inspection approved Notes 2nd floor drop ceiling only rooms corridors approved 248, 220, 205, 208, nurse station 223, nurse station 237, All Corridors 2nd floor complete

 09/18/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/17/2026 5:15:01 PM 9/17/2026 5:15 PM Gordon Galbraith Remainder of level 2 grid Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/18/2026 2:27:19 PM PARTIAL- 1) 2nd FLOOR GRID SUPPORT - 248, 220, 205, 208, 223 & 237 - OK.

 09/21/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request9/18/2026 5:51:21 PM 9/18/2026 5:51 PM Gordon Galbraith Hoping for last ceiling grid inspection on level 2 reception & 1st floor elevator lobby Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 9/21/2026 2:54:05 PM Rough electrical inspection partial approved 2nd floor lobby 201 1st floor elevator lobby e110 All drop ceiling completed 1st floor 2nd floor electrical only

 09/21/2026B:RGH FRAMESHAWN VALENZUELAPARTIALeTRAKiT Inspection Request9/18/2026 5:49:21 PM 9/18/2026 5:49 PM Gordon Galbraith Hoping for last ceiling grid inspection on level 2 reception & 1st floor elevator lobby Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/21/2026 12:40:49 PM Inspector JOCA changed the inspection assignment from JOCA to SHVA 9/21/2026 2:54:08 PM Rough frame partial approved Above ceiling grid supports areas approved 2nd floor lobby 201 1st floor elevator lobby e110

 09/24/2026B:RGH PLUMBMARTIN MAGERSAPPROVEDFinal Rough Inspection, Stock Approval9/23/2026 3:35:15 PM 9/23/2026 3:35 PM COLORADO MECHANICAL SYSTEMS LLC Final Rough Inspection for building dept. Stock inspection. Just need signature and inspection of any final items needed. Please contact Fabian Mendez (303)704-9745 or Nathan Kinder (720)877-0032 to discuss prior to arrival. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 9/24/2026 10:22:29 AM All rough plumbing on 8/4. Must call final plumbing and have hot water running to inspect for stock and train approval.

 09/24/2026B:RGH ELECTSHAWN VALENZUELAAPPROVEDeTRAKiT Inspection Request9/23/2026 3:21:26 PM 9/23/2026 3:21 PM Kelly Sherman Casework Electrical - Dan Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 9/24/2026 10:49:40 AM Rough electrical inspection approved Note 2nd case work ma station 237, 223 Rough electrical inspection complete

 09/24/2026B:RGH MECHJOE CARBAUGHAPPROVEDFinal Rough Inspection, Stock Approval9/23/2026 3:35:14 PM 9/23/2026 3:35 PM COLORADO MECHANICAL SYSTEMS LLC Final Rough Inspection for building dept. Stock inspection. Just need signature and inspection of any final items needed. Please contact Fabian Mendez (303)704-9745 or Nathan Kinder (720)877-0032 to discuss prior to arrival. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 9/24/2026 12:27:18 PM APPROVED. RGH MECH FOR WALLS & CEILING 1st & 2nd floor (IT 25-2082 ( ONLY) - OK.

 09/25/2026B:RGH FRAMEJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request9/24/2026 4:58:24 PM 9/24/2026 4:58 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/25/2026 3:09:10 PM RGH FRAME FOR TI ( ONLY) APPROVED.

 09/25/2026B:INSULATIONJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request9/24/2026 4:58:55 PM 9/24/2026 4:58 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/25/2026 3:09:12 PM INSULATION FOR TI -APPROVED.

 09/28/2026B:DRYWALLJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request9/27/2026 7:35:36 PM 9/27/2026 7:35 PM Gordon Galbraith FInal drywall to sign permit card Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/28/2026 11:58:14 AM APPROVED- WHOLE BUILDING.

 09/29/2026B:FINAL FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/28/2026 12:13:42 PM 9/28/2026 12:13 PM Gordon Galbraith No Inspection Type listed for final frame on the TI permit. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/29/2026 3:46:37 PM PARTIAL- FIRE DAMPER INSPECTION E MECH/ FIRE - OK. MISSING MECHANICAL ANGLE ON ONE SIDE & ELECTRIC E170- NEED REINSPECT WHEN CORRECTED. NOTE: REST OF FIRE DAMPERS TO BE CHECKED AT FUTURE INSPECTION.

 09/30/2026B:ROUGH MECHANICALBRETT LONGNECKERPARTIALeTRAKiT Inspection Request9/28/2026 12:11:56 PM 9/28/2026 12:11 PM Gordon Galbraith Fire dampers. Fire AHJ''s will be on site from 12pm - 3pm for visual inspection of all fire dampers. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/30/2026 6:38:57 AM All dampers checked ok. Still need to complete remaining fire damper rough inspections.

 09/30/2026B:FIRE SMOKE RESISTJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request9/29/2026 4:23:43 PM 9/29/2026 4:23 PM Gordon Galbraith CRFD will be on site at 9am to continue fire damper inspection. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/30/2026 11:08:17 AM APPROVED- 1) ALL FIRE DAMPERS IN BUILDING HAVE BEEN INSPECTED & APPROVED FROM BUILDING & CASTLE ROCK FIRE.

 10/01/2026B:FINAL BUILDINGBRETT LONGNECKERNOT APPROVEDeTRAKiT Inspection Request9/30/2026 4:03:48 PM 9/30/2026 4:03 PM Gordon Galbraith Stocking acceptance pending 1pm fire alarm annunciator panel replacement & inspection by CRFD. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/1/2026 3:58:52 PM Ok FOR STOCK ONLY. NO EMPLOYEES ARE ALLOWED UNTIL A STOCK AND TRAIN HAS BEEN APPROVED BY TOWN OF CASTLE ROCK BUILDING DIVISION AND FIRE LIFE SAFETY DIVISION. THIS INSPECTION WAS ONLY TO VERIFY GENERAL LIFE SAFETY ITEMS FOR STOCKING ONLY. A FULL FINAL BUILDING INSPECTION WILL BE PERFORMED ONCE READY FOR STOCK AND TRAIN AND TCO.

 10/06/2026B:ELECTRICAL TRENCHSHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request10/5/2026 10:14:08 AM 10/5/2026 10:14 AM Kelly Sherman Underground Electrical C&S Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 10/6/2026 10:02:21 AM No inspection conducted at this time scheduled under wrong permit number

 10/14/2026B:FINAL ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request10/13/2026 2:28:25 PM 10/13/2026 2:28 PM Kelly Sherman Dan Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 10/14/2026 2:53:29 PM Final electrical inspection partial approved TI final inspection only All other rooms on 2nd floor approved Rooms with corrections on 2nd floor Room 241 receptacle with in 6 foot of sink requires gfci protection Room 234 receptacle with in 6 foot of sink requires gfci protection Room 211 missing floor box Room 214 receptacle with in 6 foot of sink requires gfci protection Room 253 receptacle within 6 foot of sink requires gfci protection Room 249 receptacle within 6 foot of sink requires gfci protection Room 248 receptacle within 6 foot of sink requires gfci protection Lighting controls in hallways/corridors need to be programmed all of 2nd floor Receptacle in hallways good Highlighted on stamp plans page number A2.12A/B rooms approved Did not check em/critical branch circuits powered off generator

 10/15/2026B:FNL ELECTRICSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request10/14/2026 2:16:07 PM 10/14/2026 2:16 PM Kelly Sherman Dan Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 10/15/2026 3:23:50 PM final electrical inspection partial approved Rooms with corrections Room 211 floor box not installed All other rooms on TI only approved Em lights and critical branch circuits, fed from generator not inspected/ tested at this time Hallways/ corridors lighting controls not programmed at this time Highlighted plans on page number A2.12A/B

 10/19/2026B:FNL ELECTRICVINCE RAPONEPARTIALeTRAKiT Inspection Request10/16/2026 4:06:00 PM 10/16/2026 4:06 PM Gordon Galbraith Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 10/19/2026 1:50:58 PM Final electrical approved 102, 109, 111, 112, 114, 115, 117, 121, 122, 125, 126, 127, 132 133, 134, 135, 145, 147, 148, 149, 152, 153, 154, 155, 156, 158, 159, staff room, waiting area, corridors, nourish Still need lounge room 129 - gfci behind refrigerator

 10/22/2026B:FINAL PLUMBINGMARTIN MAGERSNOT APPROVEDeTRAKiT Inspection Request10/19/2026 1:58:37 PM 10/19/2026 1:58 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/22/2026 1:46:47 PM 1. Right side Drinking fountain on 2nd floor inoperative. 2. Missing aerator at sink at exam 7 on second floor. Room 247. 3. Drinking fountains on first floor inoperative. 4. ED 147, lab eye wash inoperative. 5. Bathroom 123, is due to be remodeled, and is incomplete at this point.

 10/22/2026B:FINAL MECHANICALJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request10/19/2026 1:57:59 PM 10/19/2026 1:57 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/22/2026 1:55:16 PM NOT APPROVED- 1) LINEAR SLOT AT 111 STORAGE DOES NOT MATCH LAY IN DIFFUSER PER PLAN. REST OF TI MECHANICAL- OK.

 10/26/2026B:FNL MECHJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request10/23/2026 4:25:20 PM 10/23/2026 4:25 PM Gordon Galbraith Reinspection for to-do items. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/26/2026 2:09:13 PM PARTIAL- 1) ITEMS CORRECTED FROM LAST INSPECTION. 2) TAB REPORT IS NEEDED TO GET CO.

 10/26/2026B:FNL PLUMBMARTIN MAGERSAPPROVEDeTRAKiT Inspection Request10/23/2026 9:01:57 AM 10/23/2026 9:01 AM Gordon Galbraith Reinspection drinking fountains, eyewash in ED Lab, & aerator in 247. Contact Name: Fabian Mendez Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: ggalbraith@tcco.com 10/26/2026 4:03:37 PM Corrections made

 10/27/2026B:ELECTRICAL SERVICESHAWN VALENZUELACANCELeTRAKiT Inspection Request10/23/2026 3:16:27 PM 10/23/2026 3:16 PM Gordon Galbraith Pending submission of updated feeder schedule for change from aluminum back to copper for generator feeders. Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 10/27/2026 7:47:52 AM Inspection canceled electrical service inspection scheduled on wrong permit See permit number 25-1611 for schedule inspection

 10/27/2026B:FINAL BUILDINGBRETT LONGNECKERINC OK FOR TCOeTRAKiT Inspection Request10/22/2026 7:15:50 PM 10/22/2026 7:15 PM Gordon Galbraith Attempting to get DFPC, Castle Rock Fire, & Castle Rock Building all on site at 2pm for life safety & building TCO final. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/27/2026 3:46:14 PM 1. Reorient exit sign on west 1st floor exit out of building. 2. Handrails missing returns at north stair hand rails. 3. 2nd floor data room conduit for bda missing fire stopping. 4. Conduit through wall above 2nd floor data room door fire stopping damaged. 5. Complete final mechanical. 6. Complete final electrical. 7. Complete final fire.

 11/12/2026B:FNL MECHJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request11/10/2026 12:10:23 PM 11/10/2026 12:10 PM Braden Frey TAB report was uploaded to Etrackit Contact Name: Braden Frey Site Address: 4141 PLUM CREEK BLVD Phone: 3035183298 e-Mail: bmfrey@tcco.com 11/12/2026 10:34:14 AM APPROVED.

 11/12/2026B:FNL ELECTRICSHAWN VALENZUELAAPPROVEDeTRAKiT Inspection Request11/10/2026 12:10:23 PM 11/10/2026 12:10 PM Braden Frey TAB report was uploaded to Etrackit Contact Name: Braden Frey Site Address: 4141 PLUM CREEK BLVD Phone: 3035183298 e-Mail: bmfrey@tcco.com 11/12/2026 11:54:02 AM Final electrical inspection approved All corrections have been completed