| 10/16/2025 | B:ELECTRICAL SERVICE | VINCE RAPONE | PARTIAL | UFER GROUND | 10/16/2025 3:19:44 PM
Ufer ground good
Concrete encased electrode
|
|
| 11/05/2025 | PRE CON INSPECTION | BRETT LONGNECKER | APPROVED | | 11/6/2025 3:56:58 PM
Complete Building Pre Con on Wednesday, November 5th at 2:00 pm with Gordan Galbraith, Braden Frey and Lars Nilsson. Gave contractor building precon folder with all inspection cards, checklists and general requirements to the Town of Castle Rock Building Division.
|
|
| 11/21/2025 | B:UNGRD PLUMB | MARTIN MAGERS | APPROVED | Final Underground Plumbing Inspection | 11/20/2025 12:41:29 PM
11/20/2025 12:41 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
11/20/2025 12:46:51 PM
11/20/2025 12:46 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
11/21/2025 12:10:43 PM
All DVW and Storm Drains approved.
|
|
| 12/29/2025 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | After 9am inspection preferred. | 12/24/2025 12:23:28 PM
12/24/2025 12:23 PM Gordon Galbraith
Inspection of storm leader to storm drain underground connections prior to backfill.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
12/29/2025 2:43:36 PM
Storm drain connection on the east side approved.
|
|
| 01/12/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Underslab Electrical | 1/9/2026 1:33:39 PM
1/9/2026 1:33 PM Braden Frey
Underslab Electrical Inspection
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: bmfrey@tcco.com
1/12/2026 3:26:08 PM
Under slab pvc trunk line up to electrical room good
Low volt sleeves
Branch circuiting
|
|
| 01/14/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | under slab | 1/13/2026 1:21:19 PM
1/13/2026 1:21 PM Gordon Galbraith
Additional under slab inspection to allow for backfill.
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
1/14/2026 12:25:02 PM
Under slab rough electrical
1" pvc HR trunk line good
|
|
| 01/15/2026 | TRAINING_SHAWN | SHAWN VALENZUELA | PARTIAL | under slab electrical room | 1/15/2026 12:52:06 PM
Under slab electrical room good
This completes under slab
|
|
| 01/15/2026 | B:ELECTRICAL TRENCH | VINCE RAPONE | PARTIAL | under slab electrical room | 1/14/2026 3:29:42 PM
1/14/2026 3:29 PM Gordon Galbraith
Final under slab electrical inspection to complete backfill
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
1/15/2026 3:03:23 PM
Under slab electrical room good
This completes under slab
|
|
| 01/16/2026 | B:UNGRD PLUMB | MARTIN MAGERS | APPROVED | Decon Tank UG Inspection | 1/15/2026 10:09:54 AM
1/15/2026 10:09 AM COLORADO MECHANICAL SYSTEMS LLC
Decon Tank UG Inspection. Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: nkinder@coloradomech.com
1/16/2026 12:55:40 PM
Decon tank and pump approved.
|
|
| 01/28/2026 | B:EXT SHEAR_SHEATHI | JOE CARBAUGH | PARTIAL | Partial exterior cold formed framing | 1/27/2026 1:29:34 PM
1/27/2026 1:29 PM Gordon Galbraith
East & west building elevations
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
1/28/2026 3:06:15 PM
PARTIAL- CHECKED EXTERIOR WALL CONNECTIONS FROM FIRST FLOOR TO SECOND FLOOR .
1) FCB43.5'S , FCB45.4'S CONNECTIONS AT GRID LINE (B) / EAST FROM 2 - 4.7 - OK PER PLAN.
2) FCB43.5'S , FCB45.4'S CONNECTION AT GRID LINE (F) / WEST FROM 3-5 - OK PER PLAN.
Note: Rest of grid lines for exterior-wall connections to be checked at future inspection.
|
|
| 02/04/2026 | B:UNGRD PLUMB | MARTIN MAGERS | APPROVED | Underground water from meter pit | 2/3/2026 8:26:36 AM
2/3/2026 8:26 AM Gordon Galbraith
Contact Name: Fabian Mendez
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: ggalbraith@tcco.com
2/4/2026 12:05:35 PM
Water line from meter pit to building approved.
|
|
| 02/04/2026 | B:EXT SHEAR_SHEATHI | JOE CARBAUGH | CANCEL | eTRAKiT Inspection Request | 2/3/2026 8:39:03 AM
2/3/2026 8:39 AM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
2/4/2026 2:19:30 PM
DUPLICATE INSPECTION.
|
|
| 02/06/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 2/5/2026 3:33:25 PM
2/5/2026 3:33 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
2/6/2026 2:16:08 PM
PARTIAL- MINERAL WOOL INSULATION AT ROOF PARAPET WALLS - APPROVED FROM GRID LINES ( F 4 - 5 ).
NOTE: REST OF MINERAL WOOL INSULATION & GRID LINES TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 02/10/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 2/9/2026 11:36:25 AM
2/9/2026 11:36 AM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
2/10/2026 2:36:52 PM
INSULATION-(PARTIAL)
MINERAL WOOL AT ROOF PARAPET WALLS - GRID ( C- F) SOUTH SIDE , GRID ( 1- 3) WEST SIDE, GRID (5-7) WEST SIDE , GRID ( D- F) NORTH SIDE-OK PER PLAN.
NOTE: GRID (5 - 5.5) EAST AND (A- D) NORTH AT PARAPET WALLS TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 02/12/2026 | B:EXT SHEAR_SHEATHI | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 2/11/2026 10:30:38 AM
2/11/2026 10:30 AM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
2/12/2026 3:40:38 PM
ITEMS INSPECTED
1) 5/8 DEN GLASS - SECOND FLOOR GRID LINES ( C - F SOUTH ) / GRID LINES (1-6 WEST) / GRID LINES (C - F NORTH) & GRID LINE ( A 1.1 - 5.5
2) 5/8 DEN GLASS EXTERIOR SHEAR/ SCREW INSPECTION - FIRST & SECOND FLOOR GRID LINES ( C - F SOUTH ) / GRID LINES (1-6 WEST) / GRID LINES (C - F NORTH) & GRID LINE ( A 1.1 - 5.5 - OK.
3) FRAMING AT TOP OF FIRST FLOOR WALL TO SECOND FLOOR FRAMI NG OK THRUGH RID LINE (C- F) SOUTH , ( F 1-5) WEST- OK.
|
|
| 02/13/2026 | B:RGH PLUMB | MARTIN MAGERS | APPROVED | Storm drain tie in - west side | 2/12/2026 10:39:19 AM
2/12/2026 10:39 AM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
2/13/2026 10:11:49 AM
Storm drain stub outs ok
|
|
| 02/13/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 2/12/2026 10:16:55 PM
2/12/2026 10:16 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
2/13/2026 2:12:17 PM
RGH FRAME -
1) ROOF PARAPET FRAMING WALLS & CONNECTIONS AT NORTH / EAST CORNER - GRID LINES (A 4.7- 7) & (A - C) - OK.
NOTE: OK TO PLACE REQUIRED MINERAL WOOL AT REQUIRED SECTION ABOVE.
|
|
| 02/17/2026 | B:EXT SHEAR_SHEATHI | JOE CARBAUGH | CANCEL | eTRAKiT Inspection Request | 2/13/2026 12:58:19 PM
2/13/2026 12:58 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
2/17/2026 12:17:20 PM
CANCELED DO TO WEATHER.
|
|
| 02/20/2026 | B:EXT SHEAR_SHEATHI | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 2/19/2026 11:45:16 PM
2/19/2026 11:45 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
2/20/2026 11:18:08 AM
EXT SHEAR SHEATHING- 1) MINERAL WOOL / DENS DECK & NAILING -OK AT GRID LINES (A 4.7- 7 EAST & A - C NORTH ROOF PARAPET WALL).
|
|
| 02/26/2026 | B:EXT SHEAR_SHEATHI | BRETT LONGNECKER | PARTIAL | north elevation | 2/25/2026 1:12:14 PM
2/25/2026 1:12 PM Braden Frey
Exterior Column Framing
Contact Name: Braden Frey
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035183298
e-Mail: bmfrey@tcco.com
2/26/2026 1:00:26 PM
North elevation of structure exterior sheathing complete.
|
|
| 03/03/2026 | B:EXT SHEAR_SHEATHI | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/2/2026 1:20:35 PM
3/2/2026 1:20 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/3/2026 3:52:15 PM
1) IT ROOM 140 TOP OUT RATED 2 hr EAST & WEST WALLS - 1st layer of 5/8 type X - PENDING UL ASSEMBLY HW-D-0420
2) MECHANICAL ROOM 160 - WEST & EAST 16" WALL - 1 EACH SIDE 1 HOUR RATED UL ASSEMBLY HW-D-0420 - OK.
3) DENS GLASS AT NORTH EAST GRID LINES C- F & FIN WALL AT GRID LINE C- F SCREW / SHEATHING INSPECTION - OK.
4) ELECTRICAL ROOM 170- 1 LAYER 1 HOUR RATED WALLS EAST, WEST & NORTH INSIDE OF ROOM DRY WALL & SCREW SCHEDULE - OK.
5) DENS GLASS SHEATHING- SOUTH SIDE / GRID LINES C- F - OK.
|
|
| 03/04/2026 | B:RGH FRAME | BRETT LONGNECKER | NOT APPROVED | eTRAKiT Inspection Request | 3/3/2026 4:04:51 PM
3/3/2026 4:04 PM Gordon Galbraith
North east overhang cold form framing
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/4/2026 2:37:34 PM
Cold steel frame for east entry overhang ok.
Highlighted in blue on town approved plans S2.02 and uploaded photo.
Cold steel exterior wall frame east entry ok.
Highlighted in blue on town approved plans S2.01 and uploaded photo.
|
|
| 03/09/2026 | B:RGH MECH | MARTIN MAGERS | PARTIAL | Fire Damper Framing Inspection | 3/6/2026 11:22:50 AM
3/6/2026 11:22 AM COLORADO MECHANICAL SYSTEMS LLC
Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035197973
e-Mail: AR@COLORADOMECH.COM
3/9/2026 1:23:08 PM
Duct work as high lighted on M2.11 in yellow.
3/9/2026 1:24:36 PM
Duct work as high lighted on M2.11 in yellow.
|
|
| 03/09/2026 | B:INSULATION | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 3/6/2026 1:35:19 PM
3/6/2026 1:35 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/9/2026 3:33:55 PM
NOT APPROVED.
Not ready at time of inspection.
|
|
| 03/10/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/9/2026 3:23:19 PM
3/9/2026 3:23 PM Gordon Galbraith
Exterior eye brow framing mineral wool insulation
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/10/2026 2:06:10 PM
PARTIAL ? MINERAL WOOL INSULATION AT GRID LINES A 4.7 - 7 EAST & A 7 - C NORTH- APPROVED.
|
|
| 03/11/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 3/10/2026 4:09:47 PM
3/10/2026 4:09 PM Gordon Galbraith
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
3/11/2026 10:44:56 AM
Rough electrical walls only - above drop ceiling good
Okay to rock
|
|
| 03/17/2026 | B:DRYWALL | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 3/16/2026 5:41:28 PM
3/16/2026 5:41 PM Gordon Galbraith
Top of wall drywall interior. Jesus with ICI.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/17/2026 3:38:26 PM
PARTIAL- SECOND LAYER TOP OF WALL DRY-WALL INSPECTION AT WEST WALL ONLY OF IT 140 - OK.
|
|
| 03/17/2026 | B:RGH FRAME | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 3/16/2026 5:40:34 PM
3/16/2026 5:40 PM Gordon Galbraith
Small bit of cold form framing on the SE exterior of the building & some top of wall framing interior. For Jesus with ICI.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/17/2026 3:38:28 PM
NOT APPROVED-
SOUTH / EAST BUMP- OUT - OK PER ON SITE UPDATED DETAIL 3 , PENDING TOWN REVIEW.
|
|
| 03/18/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/17/2026 7:43:28 PM
3/17/2026 7:43 PM Gordon Galbraith
Witness install of UL head of wall - ICI Jesus
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/18/2026 3:56:55 PM
Partial-
1). (2) HR RATED HW- D - 0420 DRYWALL/ SCREW INSPECTION - TOP OUT (2) LAYERS OF 5/8 TYPE X AT INTERIOR SIDE OF WEST & EAST WALLS IN IT 140.
2). IT 140 CORRIDOR 105 (1st) LAYER DRYWALL/ SCREW INSPECTION- TOP OUT 5/8 TYPE X - OK.
|
|
| 03/18/2026 | B:INSULATION | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 3/17/2026 7:42:13 PM
3/17/2026 7:42 PM Gordon Galbraith
upper roof east side mineral wool - ICI Jesus.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/18/2026 3:56:58 PM
PARTIAL-
ENTRANCE COVER INSULATION FROM GRID LINES 4.7 SOUTH 4.7- 7 - OK.
|
|
| 03/18/2026 | B:EXT SHEAR_SHEATHI | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/17/2026 7:40:45 PM
3/17/2026 7:40 PM Gordon Galbraith
East side upper eyebrow sheathing - ICI Jesus.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/18/2026 3:57:00 PM
PARTIAL- DEN-GLASS AT FRONT ENTRANCE COVER - OK.
|
|
| 03/19/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | NOT APPROVED | SECOND LAYER TOP OUT AT IT ROOM 140 | 3/18/2026 1:55:53 PM
3/18/2026 1:55 PM Gordon Galbraith
1st Floor - IT room 140 2nd layer drywall top out - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/19/2026 2:54:48 PM
1) DRYWALL (2ND) LAYER TOP OUT OF 2 HR SOUTH RATED WALL AT - IT ROOM 140 - OK.
|
|
| 03/23/2026 | B:RGH PLUMB | BRETT LONGNECKER | PARTIAL | Overhead Vent & In-Wall Domestic | 3/20/2026 12:52:45 PM
3/20/2026 12:52 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30 pm
Contact Name: Fabian Mendez
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
3/23/2026 12:47:27 PM
Waste and overhead and wall vent, domestic water test wall only for 1st floor as highlighted in blue in town approved plans P2.21. TI in wall rough inspected on this permit.
|
|
| 03/23/2026 | B:RGH MECH | JOE CARBAUGH | NOT APPROVED | Fire Damper Framing Inspection | 3/20/2026 12:53:54 PM
3/20/2026 12:53 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205359789
e-Mail: AR@COLORADOMECH.COM
3/23/2026 1:57:16 PM
PARTIAL- DAMPER FRAMING - AT AMBULANCE AREA - OK.
|
|
| 03/27/2026 | B:DRYWALL | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 3/26/2026 3:17:09 PM
3/26/2026 3:17 PM Gordon Galbraith
1st Floor electrical & IT Room drywall - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/27/2026 1:18:46 PM
1st layer at IT room 140, Interior walls ok, exterior wall not not started.
1st layer in electrical room, all walls ok.
|
|
| 03/27/2026 | B:INSULATION | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 3/26/2026 3:16:22 PM
3/26/2026 3:16 PM Gordon Galbraith
1st Floor Insulation - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/27/2026 1:18:48 PM
IT room 140,. Insulation, R 13 on south wall ok.
|
|
| 03/27/2026 | B:FIRE SMOKE RESIST | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 3/26/2026 3:19:00 PM
3/26/2026 3:19 PM Gordon Galbraith
1st floor eletrical & IT rooms - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
3/27/2026 1:18:44 PM
Fire rip at top of wall at electrical and IT rooms. ok #10 HW-D-0420.
3/27/2026 2:20:11 PM
Fire rip at top of wall at electrical and IT rooms. ok #10 HW-D-0420.
|
|
| 04/01/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/31/2026 2:49:38 PM
3/31/2026 2:49 PM Gordon Galbraith
2nd layer screw inspection at IT room - 2 hr assembly - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/1/2026 1:02:39 PM
IT ROOM E140 SECOND LAYER DRYWALL & SCREW INSPECTION-OK.
|
|
| 04/01/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/31/2026 2:48:30 PM
3/31/2026 2:48 PM Gordon Galbraith
Level 1 Head of Wall UL @ IT Room - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/1/2026 1:02:42 PM
PARTIAL-
FIRE RIP SYSTEM AT INTERIOR ROOM OF IT E140-OK.
|
|
| 04/03/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/2/2026 9:10:35 AM
4/2/2026 9:10 AM Gordon Galbraith
Mineral wool at parapet above elevator core
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/3/2026 10:36:30 AM
PARTIAL- FRAMING , MINERAL WOOL & SHEATHING AT N/W PARAPET WALL/ WEST SIDE OF CMU. - OK.
|
|
| 04/03/2026 | B:WEATHER BARRIER | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/2/2026 8:51:27 AM
4/2/2026 8:51 AM Gordon Galbraith
Air barrier south & east elevation
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/3/2026 10:36:35 AM
PARTIAL-
1) SOUTH & NORTH ELEVATION / GRID LINES A- F SOUTH ELEVATION- OK.
2) NORTH ELEVATION / GRID LINES A- F NORTH ELEVATION- OK.
NOTE: EAST & WEST ELEVATIONS TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 04/03/2026 | B:EXT SHEAR_SHEATHI | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 4/2/2026 9:11:43 AM
4/2/2026 9:11 AM Gordon Galbraith
Small bit of sheathing at parapet top of elevator core
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/3/2026 10:36:24 AM
EXT SHEAR _ SHEATHING - APPROVED.
|
|
| 04/06/2026 | B:RGH PLUMB | BRETT LONGNECKER | CANCEL | eTRAKiT Inspection Request | 4/3/2026 2:30:14 PM
4/3/2026 2:30 PM Gordon Galbraith
DWV in-wall & OH - plan north - Fabian w/CMS
Contact Name: Fabian Mendez
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: ggalbraith@tcco.com
4/6/2026 9:41:23 AM
Cancel per conversation with plumbing contractor.
|
|
| 04/06/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | Z CHANNEL & CONNECTIONS | 4/3/2026 2:27:57 PM
4/3/2026 2:27 PM Gordon Galbraith
Z furring at east high overhang (eyebrow) & z furring at top of storefront header - Jeff w/ Flynn
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/6/2026 10:51:38 AM
PARTIAL-
1) MAIN ENTRANCE COVER Z CHANNEL 16 O.C. & CONNECTIONS AT GRID LINES 4.7- 7 - OK.
2) Z CHANNEL AT 16 O.C. & CONNECTIONS AT FRONT / EAST EYEBROW GRID LINES A 1.1 - 4.7 - Ok.
|
|
| 04/06/2026 | B:INSULATION | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 4/3/2026 2:54:05 PM
4/3/2026 2:54 PM Gordon Galbraith
Mineral wool at slab edge - Jesus w/ICI. Afternoon inspection if at all possible.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/6/2026 2:49:05 PM
WITNESS INSPECTION -
1) SECOND FLOOR EDGED OF SLAB INSULATION (NORTH WALL) / GRID LINE 6 F-C MINERAL WOOL INSULATION INSPECTION- 711119a HILTI - OK
|
|
| 04/07/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | CANCEL | eTRAKiT Inspection Request | 4/6/2026 3:32:18 PM
4/6/2026 3:32 PM Gordon Galbraith
2nd floor north side slab edge spray
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/7/2026 2:54:19 PM
INSPECTION CANCELED BY CONTRACTOR.
|
|
| 04/07/2026 | B:RGH PLUMB | BRETT LONGNECKER | PARTIAL | 1st floor DWV | 4/6/2026 3:30:47 PM
4/6/2026 3:30 PM Gordon Galbraith
Waste & Vent 1st Floor - water test
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/7/2026 3:20:15 PM
1st floor ok except drinking fountain DWV to 2nd floor and EVS closet.
|
|
| 04/08/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/7/2026 3:06:56 PM
4/7/2026 3:06 PM Gordon Galbraith
Rigid insulation - exterior - Jeff w/Flynn
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/8/2026 3:27:42 PM
NOT APPROVED-
1) (FIRST LAYER) DRYWALL SCREW INSPECTION/ NORTH WALL OF IT 220 - OK.
2) FIRST LAYER) 1HR DRYWALL SCREW INSPECTION/ NORTH WALL FOR CORE & SHELL STAFF TOILET 209 -OK.
NOTE: THROUGH PENETRATION AT REAR/ NORTH WALL DETAIL 5 PENETRATION AT RATED PARTITIONS PAGE A7.10 TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 04/08/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/7/2026 2:28:00 PM
4/7/2026 2:28 PM Gordon Galbraith
2nd Floor electrical room - 1st layer drywall - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/8/2026 3:27:45 PM
1) SECOND FLOOR EDGED OF SLAB INSULATION (SOUTH WALL) / GRID LINES 1 F-C MINERAL WOOL INSULATION INSPECTION- 711119a HILTI - OK
|
|
| 04/08/2026 | B:LATH INSPECTION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/7/2026 2:24:10 PM
4/7/2026 2:24 PM Gordon Galbraith
East elevation, stone veneer - Junior w/BSM
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/8/2026 3:27:48 PM
PARTIAL-
1) LATH INSPECTION ON EAST ELEVATION/ GRID LINES 1.1 THROUGH 4.7 - OK.
|
|
| 04/09/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 4/8/2026 3:02:28 PM
4/8/2026 3:02 PM Gordon Galbraith
1st floor in-wall - Dan w/Duro
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/9/2026 10:57:53 AM
1st floor core and shell wall rough electrical
Room numbers 150, 190, 180, 170, 160, 140, 110 ok to drywall
|
|
| 04/09/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/8/2026 3:28:09 PM
4/8/2026 3:28 PM Gordon Galbraith
2nd layer dryall & slab edge - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/9/2026 3:13:41 PM
DRYWALL SCREW INSPECTION
ELECTRICAL ROOM 210 -
1) 2nd LAYER DRYWALL/ SCREW INSPECTION, HEAD OF WALL ZIP SYSTEM & BOTTOM TRACK SEAL CFS-BTS 5/8 SEAL -OK.
2) 1ST LAYER DRYWALL IT ROOM 220 WEST WALL & EAST WALL- OK.
|
|
| 04/09/2026 | B:LATH INSPECTION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/8/2026 2:54:22 PM
4/8/2026 2:54 PM Gordon Galbraith
Stone inspection exterior - east elevation - Junior w/BSM
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/9/2026 3:13:43 PM
PARTIAL-
1) ISTO PRIMER/ ADHESIVE -B AT (E) STAIR SOUTH E501 - OK.
|
|
| 04/09/2026 | B:EXT SHEAR_SHEATHI | JOE CARBAUGH | PARTIAL | EFIS INSPECTION | 4/8/2026 2:49:48 PM
4/8/2026 2:49 PM Gordon Galbraith
EIFs, east & south elevation - Junior w/BSM
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/9/2026 3:13:45 PM
PARTIAL-
EIFS-INSPECTION At (E) STAIR SOUTH E501- OK. R13089 CERTIFIED/ 68P7 RATED RIDGED FOAM, ISTO PRIMER/ ADHESIVE -B, 80921 STO ARMOR MAT& VM- 04 80lb.
|
|
| 04/09/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/8/2026 2:47:58 PM
4/8/2026 2:47 PM Gordon Galbraith
Exterior insulation - Jeff w/Flynn
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/9/2026 3:13:47 PM
PARTIAL-
1) SECOND FLOOR EDGED OF SLAB INSULATION (WEST WALL) / GRID LINES F 3-4 MINERAL WOOL INSULATION INSPECTION- 711119a HILTI - OK.
|
|
| 04/10/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 4/9/2026 2:13:43 PM
4/9/2026 2:13 PM Gordon Galbraith
2nd floor wall rough - Dan w/Duro
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/10/2026 11:37:48 AM
2nd floor core and shell partial
Core and shell areas ok to drywall on 2nd floor
Shell space 2nd floor area B south west corner of building mechanical shaft verify on final 2 access panels are installed , IT room 220, electrical room 210, 2nd floor bathroom 209. Ok to drywall if all other inspections have been completed
Mechanical shaft outside of 208 need to finish framing ****not ok to drywall****
Elevator inspection has not been conducted at this time of inspection
|
|
| 04/10/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | HEAD OF WALL FIRE RIP INSPECTION | 4/9/2026 2:12:53 PM
4/9/2026 2:12 PM Gordon Galbraith
West side slab edge mineral wool - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/10/2026 3:14:58 PM
PARTIAL-
1) HEAD OF WALL FIRE RIP & FRAMING INSPECTION AT ELECTRICAL ROOM 210 & GRID LINE D & 2 - OK.
|
|
| 04/10/2026 | B:LATH INSPECTION | JOE CARBAUGH | CANCEL | eTRAKiT Inspection Request | 4/9/2026 2:08:07 PM
4/9/2026 2:08 PM Gordon Galbraith
EIFS & Stone - Junior w/BSM
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/10/2026 3:15:00 PM
CANCELED-
1) COURTESY INSPECTION FOR STEPS & REQUIRED BY TOWN.
|
|
| 04/10/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/9/2026 2:07:27 PM
4/9/2026 2:07 PM Gordon Galbraith
1st & 2nd floor - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/10/2026 3:15:04 PM
RGH FRAME CORE & SHELL-
1) RGH FRAME - FOR SHELL SPACE AT GRID LINES D & 2 - OK
2) MECHANICAL- SOUTH ELEVATION COMBO FIRE/ SMOKE DAMPER DUCT & PENETRATIONS - OK.
3) RGH FRAME - ELECTRICAL 210, IT ROOM 220 ALL HEAD OF WALLS & WALLS -OK.
|
|
| 04/10/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | Level 2 Fire Damper Frame Inspection | 4/9/2026 2:35:42 PM
4/9/2026 2:35 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3:30pm
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035197973
e-Mail: AR@COLORADOMECH.COM
4/10/2026 3:15:09 PM
PARTIAL-
1) MECHANICAL- (SOUTH ELEVATION) COMBO FIRE/ SMOKE DAMPER DUCT / PENETRATIONS & ATTACHMENT- OK PER MANUFACTURER INSTALLATION INSTRUCTIONS.
|
|
| 04/10/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | | 4/10/2026 3:15:46 PM
PARTIAL-
1) WITNESS INSPECTION - HILTI 711119a CFS-SP WB FIRE-STOP JOINT SPRAY 1/8" (WET) AT WEST, NORTH & SOUTH ELEVATIONS - OK.
NOTE: 2nd LAYER 1" MINERAL WOOL AT SLAB EDGE TO BE INSPECTED AT FUTURE SMOKE RESIST INSPECTION.
|
|
| 04/13/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | TOP OUT INSULATION FOR CORN & SHELL | 4/10/2026 6:07:23 PM
4/10/2026 6:07 PM Gordon Galbraith
Insulation - 1st & 2nd floor - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/13/2026 4:13:45 PM
TOP OUT / HEAD OF WALL INSULATION R19 FOR CORN & SHELL INSPECTION TWO FULL AREAS
1st FLOOR-
(WEST) ELEVATION -
1) GRIDS F 2-7 (TOP OUT / HEAD OF WALL) EXTERIOR WALL- OK.
2) EXAM 125 & BARIATRIC 117 - (FULL) EXTERIOR WALL- OK.
( NORTH) ELEVATION -
1) GRID LINES- F - C ON 6 - OK.
2nd FLOOR -
TOP OUT EXTERIOR INSULATION -
1) EAST/ SOUTH/ WEST & NORTH ELEVATIONS - OK.
CORE & SHELL
1) (FULL WALL)
R19 FOR EXTERIOR & R13 FOR INTERIOR WALLS - OK.
IT 220 & ELECTORAL 210
|
|
| 04/13/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/10/2026 6:04:33 PM
4/10/2026 6:04 PM Gordon Galbraith
2nd floor slab edge, framing & insulation
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/13/2026 4:13:48 PM
WITNESS-
1) SOUTH WALL - 1 INCH MINERAL WALL AT SECOND FLOOR SLAB EDGE INSPECTION AT GRID LINES 1 F- C - OK.
2) NORTH WALL - 1 INCH MINERAL WALL AT SECOND FLOOR SLAB EDGE INSPECTION AT GRID LINES 6 F-C - OK.
3) WEST WALL- 1 INCH MINERAL WALL AT SECOND FLOOR SLAB EDGE INSPECTION AT GRID LINES - F 1- 6 - OK.
|
|
| 04/13/2026 | B:RGH MECH | JOE CARBAUGH | PARTIAL | Level 2 Shaft Fire Damper Openings | 4/10/2026 1:16:18 PM
4/10/2026 1:16 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035197973
e-Mail: AR@COLORADOMECH.COM
4/13/2026 4:13:51 PM
Level 2 Shaft Fire Damper Openings & ATTACHMENTS - OK.
|
|
| 04/14/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | EFIS INSPECTION | 4/13/2026 5:32:06 PM
4/13/2026 5:32 PM Gordon Galbraith
Slab edge mineral wool - east side - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/14/2026 11:12:14 AM
PARTIAL-
1) EFIS INSPECTION AT S/E CORNER & FRONT/ EAST FACING ELEVATION GRID LINe 1 C-B & GRID LINE B 1- 4.7 - OK.
|
|
| 04/14/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | DRYWALL/SCREW INSPECTION | 4/13/2026 5:31:23 PM
4/13/2026 5:31 PM Gordon Galbraith
Screw inspection - 1st floor vestibule - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/14/2026 11:12:16 AM
PARTIAL-
DRYWALL / SCREW INSPECTION
1) VESTIBULE 100 INTERIOR DRYWALL/ SCREW INSPECTION FIRST LAYER 5/8 TYPE X - OK PENDING EXTERIOR WATER PROOFING.
|
|
| 04/14/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | INTERIOR CORN SHELL FRAMING, FIRST FLOOR | 4/13/2026 5:30:36 PM
4/13/2026 5:30 PM Gordon Galbraith
1st Floor mech room/IT room/vestibule - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/14/2026 11:12:19 AM
PARTIAL-
FIRST FLOOR INTERIOR CORE & SHELL FRAMING
1) IT 140 WHOLE ROOM - OK.
2) VESTIBULE 100 & LOBBY 110 - OK.
3) MECH/ FIRE ROOM 160 & ELECTRICAL 170- OK.
|
|
| 04/14/2026 | B:LATH INSPECTION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/13/2026 5:34:10 PM
4/13/2026 5:34 PM Gordon Galbraith
EIFS - Junior w/BSM
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/14/2026 11:12:11 AM
PARTIAL-
1) FULL SOUTH ELEVATION / GRID LINES 1 F-C LATH & ATTACHMENT INSPECTION - OK.
|
|
| 04/15/2026 | B:INSULATION | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 4/14/2026 3:20:52 PM
4/14/2026 3:20 PM Gordon Galbraith
IT room north side - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/15/2026 3:01:29 PM
PARTIAL-
2nd FLOOR 1 LAYER OF 3" MINERAL WOOL WITNESS (CEJ421P) PERIMETER FIRE BARRIER SYSTEM INSPECTION GID LINES B 1- 4.7 EAST WALL - OK.
|
|
| 04/16/2026 | B:RGH PLUMB | BRETT LONGNECKER | PARTIAL | in wall pipe insulation | 4/15/2026 4:09:18 PM
4/15/2026 4:09 PM Gordon Galbraith
1st floor domestic water insulation - Fabian w/CMS
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/16/2026 9:44:17 AM
1st floor in wall domestic water pipe insulation ok.
|
|
| 04/16/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | EXTERIOR INSULATION INSPECTION | 4/15/2026 4:10:34 PM
4/15/2026 4:10 PM Gordon Galbraith
Exterior insulation 1st floor - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/16/2026 9:55:42 AM
PARTIAL-
1) EXTERIOR INSULATION R19 INSPECTION/ NORTH & WEST WALLS - OK.
|
|
| 04/16/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 4/15/2026 4:11:53 PM
4/15/2026 4:11 PM Gordon Galbraith
Slab edge final fire spray - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/16/2026 9:55:38 AM
PARTIAL-
1) WITNESS INSPECTOR SLAB EDGE CEJ421 P ( HI/BP 120-03) ASTM E 2307 SRAY GRID LINES (B) (1-4.7) . -OK.
|
|
| 04/17/2026 | B:LATH INSPECTION | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 4/16/2026 4:17:13 PM
4/16/2026 4:17 PM Gordon Galbraith
Final stone inspection - east side - Junior w/BSM
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/17/2026 3:03:08 PM
NOT APPROVED.
1) DRAIN NOT SEALED.
REST OF EAST ELEVATION - OK.
NOTE: BLANKET OR INSULATE FOR TEMPERATURES WHILE CURING.
|
|
| 04/17/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/16/2026 4:16:04 PM
4/16/2026 4:16 PM Gordon Galbraith
2nd floor east slab edge - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/17/2026 3:03:10 PM
PARTIAL-
1) FIRST FLOOR WITNESS INSPECTION OF MINERAL WOOL AT SLAB EDGE ( EAST) WALL/ ELEVATION CEJ421 P GRID LINES ( B 3-4) OK.
|
|
| 04/20/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/17/2026 3:05:37 PM
4/17/2026 3:05 PM Gordon Galbraith
1st floor insulation - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/20/2026 3:16:11 PM
1st FLOOR INSTALLATION R13 INTERIOR WALLS AND R 19 EXTERIOR WALLS INSPECTION
1) IT 140 SOUTH , EAST & WEST WALLS - OK.
2) WATER ENTRY 150 NORTH WALL - OK.
3) MECHANICAL/ FIRE 160 ALL WALLS - OK.
|
|
| 04/21/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | DRYWALL / SCREW INSPECTION | 4/20/2026 3:37:15 PM
4/20/2026 3:37 PM Gordon Galbraith
1st floor drywall (screw) - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/21/2026 10:50:47 AM
PARTIAL-
1) DRYWALL / SCREW INSPECTION 141 (NORTH WALL 1 LAYER ONLY) - OK .
2) DRYWALL/ SCREW INSPECTION ELEC 170 SOUTH WALL NORTH SIDE OF WALL - OK
|
|
| 04/21/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/20/2026 3:37:52 PM
4/20/2026 3:37 PM Gordon Galbraith
1st floor framing - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/21/2026 10:50:44 AM
PARTIAL-
1) CORE & SHELL FULL WALL FRAME AT WATER ENTRY 150, EM ELEC 150 & MED GAS 190 - OK.
|
|
| 04/21/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/20/2026 3:36:36 PM
4/20/2026 3:36 PM Gordon Galbraith
1st floor insulation - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/21/2026 10:50:50 AM
PARTIAL-
1st FLOOR INSULATION & WITNESS MINERAL WOOL INSULATION.
1) MECH/FIRE 160 & ELEC 170 ALL WALLS R13 - OK.
2) WITNESSES MINERAL WOOL AT BEAM POCKET & R13 WALL INSPECTION AT EM ELEC 180 - OK.
3) WATER ENTRY ROOM 150 R13 ALL WALLS - OK.
|
|
| 04/22/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | EAST ELEVATION EXTERIOR INSULATION R19 | 4/21/2026 3:07:27 PM
4/21/2026 3:07 PM Gordon Galbraith
1st floor east exam room exterior wall insulation - Brian w/E&K
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/22/2026 3:14:55 PM
PARTIAL-
1) EAST ELEVATION EXTERIOR INSULATION R19 GRID LINES A 1 THROUGH 4.7 - OK.
|
|
| 04/22/2026 | B:LATH INSPECTION | JOE CARBAUGH | PARTIAL | LATH INSPECTION S/W ELEVATION | 4/21/2026 3:06:14 PM
4/21/2026 3:06 PM Gordon Galbraith
West elevation lath - Junior w/BSM
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/22/2026 3:14:58 PM
PARTIAL-
1) LATH INSPECTION S/W ELEVATION -OK.
|
|
| 04/22/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/21/2026 3:08:05 PM
4/21/2026 3:08 PM Gordon Galbraith
1st floor screw inspection - Jesus w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
4/22/2026 3:14:52 PM
PARTIAL-
CORE & SHELL
WITNESSES DRYWALL/SCREW INSPECTION FOR ASSEMBLY U411 (2) HR WALL - IT 140
WITNESSES DRYWALL/SCREW INSPECTION FOR ASSEMBLY U465 (1) HR WALL - ELEC 170
1) 1st LAYER 5/8 TYPE X DRYWALL & SCREW INSPECTION - EAST OUT SIDE WALL OF IT 140 - OK.
2) WITNESSES 5/8 TYPE X DRYWALL & SCREW INSPECTION- EAST OUT SIDE WALL OF ELEC 170 - OK.
3) DRYWALL 5/8 TYPE X & SCREW INSPECTION ALL WALLS MEC/ FIRE 160 **** ( EXCEPT SOUTH WEST CORNER). ****
|
|
| 04/23/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | 2ND FLOOR EXTERIOR INSULATION | 4/22/2026 3:36:41 PM
4/22/2026 3:36 PM Kelly Sherman
1st Floor Screw Inspection - Jesus w/ICI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/23/2026 1:53:41 PM
PARTIAL-
2ND FLOOR EXTERIOR INSULATION AT SOUTH & WEST WALLS OF SHELL SPACE
1) R19 BATT INSULATION AT GRID LINES C THROUGH F & F 1 THROUGH 3.5 - OK.
|
|
| 04/23/2026 | B:INSULATION | JOE CARBAUGH | CANCEL | DUPLICATE INSPECTION | 4/22/2026 2:51:22 PM
4/22/2026 2:51 PM Kelly Sherman
2nd Floor Exterior Insulation - Brian with E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/23/2026 1:53:46 PM
CANCELED- DUPLICATE INSPECTION.
|
|
| 04/23/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/22/2026 3:36:41 PM
4/22/2026 3:36 PM Kelly Sherman
1st Floor Screw Inspection - Jesus w/ICI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/23/2026 1:53:44 PM
PARTIAL-
1) WITNESS (2nd) LAYER 5/8 TYPE X DRYWALL & SCREW INSPECTION / U411 (2 HR RATED ASSEMBLY) - IT 140 OUTSIDE EAST INTERIOR WALL - OK .
2) (1st) LAYER 5/8 X DRYWALL & SCREW INSPECTION / U411 (2 HR RATED ASSEMBLY) - IT 140 - OK .
|
|
| 04/24/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | DRYWALL & SCREW INSPECTION | 4/23/2026 2:43:30 PM
4/23/2026 2:43 PM Kelly Sherman
1st Floor Screw Inspection - Jesus w/ICI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/24/2026 11:15:06 AM
PARTIAL-
1st FLOOR
1) ONE LAYER 5/8 TYPE X ALL WALLS IN EM ELEC - 180 - OK.
2) ONE LAYER 5/8 TYPE X AT EAST & WEST WALLS OF DECONTAM - 133 CORE & SHELL - OK
3) ONE LAYER 5/8 TYPE X ALL WALLS (E) MED GAS - 190 - OK.
4) ONE LAYER 5/8 TYPE X WEST / OUTSIDE WALL OF TI - 140 - OK.
5) 2nd LAYER 5/8 TYPE X SOUTH & EAST OUTSIDE WALLS OF TI - 140 - OK.
2nd FLOOR
1) WITNESSES FIRST LAYER OF 5/8 TYPE X & SCREW INSPECTION FOR U411 2HR RATED ASSEMBLY OUTSIDE EAST WALL OF IT 220 - OK.
|
|
| 04/24/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/23/2026 2:42:41 PM
4/23/2026 2:42 PM Kelly Sherman
1st & 2nd Floor Insulation Inspection - Jesus w/ICI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/24/2026 11:15:09 AM
PARTIAL -
1) 1st FLOOR INTERIOR INSULATION R13 AT INSIDE WEST WALL OF EM ELEC 180 - OK.
2) 2nd FLOOR SHELL SPACE INSULATION R13 AT GRID LINE D & 2 - OK.
|
|
| 04/27/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/24/2026 5:07:29 PM
4/24/2026 5:07 PM Kelly Sherman
1st Floor - Jesus w/ICI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/27/2026 1:41:09 PM
PARTIAL-
WATER ENTRY R19 ROOM 150 - OK.
|
|
| 04/27/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | DRYWALL SCREW INSPECTION | 4/24/2026 5:07:29 PM
4/24/2026 5:07 PM Kelly Sherman
1st Floor - Jesus w/ICI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/27/2026 1:41:12 PM
PARTIAL-
1) DRYWALL SCREW INSPECTION FOR WATER ENTRY 150 - OK.
2) (CORE & SHELL MECH) - FIRE ROOM 160 OUTSIDE NORTH WALL & EAST OUTSIDE WALL ELEC 170 - OK.
|
|
| 04/27/2026 | B:LATH INSPECTION | JOE CARBAUGH | PARTIAL | LATH N/ W CORNER INSPECTION | 4/24/2026 2:03:26 PM
4/24/2026 2:03 PM Kelly Sherman
Lath Inspection on North - Junior w/BSM
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/27/2026 1:41:14 PM
PARTIAL-
1) N/ W CORNER LATH INSPECTION - OK.
NOTE: PICTURES ATTACHED.
|
|
| 04/28/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | FIRE RIP AT HEAD OF WALL | 4/27/2026 6:44:46 PM
4/27/2026 6:44 PM Kelly Sherman
Insulation & Fireproofing - Jesus w/ICI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/28/2026 12:33:26 PM
PARTIAL-
FIRE RIP AT HEAD OF WALL FOR -
1) IT 140 ALL WALLS EXCEPT EXTERIOR - OK.
2) EM ELEC 180 ALL WALLS EXCEPT EXTERIOR - OK.
3) ELEC 170 ALL WALLS - OK.
4) MEC FIRE 160 ALL WALLS EXCEPT EXTERIOR - OK.
5) MEC GAS 180 ALL WALLS EXCEPT EXTERIOR - OK.
6) WATER ENTRY 150 ALL WALLS EXCEPT EXTERIOR - OK.
|
|
| 04/28/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/27/2026 6:44:46 PM
4/27/2026 6:44 PM Kelly Sherman
Insulation & Fireproofing - Jesus w/ICI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/28/2026 12:33:23 PM
PARTIAL-
1) SECOND FLOOR INSULATION AT MECHANICAL SHAFT / FLOOR DAMPERS AT GRID LINE C/5 - OK.
|
|
| 04/29/2026 | B:ELECTRICAL TRENCH | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 4/28/2026 4:20:51 PM
4/28/2026 4:20 PM Kelly Sherman
Fiber line - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/29/2026 10:20:50 AM
Electrical trench partial approved
Notes.
2 4in pvc fiber optic conduits 36ins deep. Both conduits coming from west side of property line to west side of building. Will terminate to under slab conduits feeding IT room.
Please call in another inspection when final connections are made to conduits under slab/ utility fiber location on west side of property line.
|
|
| 04/30/2026 | B:FIRE SMOKE RESIST | JOE CARBAUGH | PARTIAL | WITNESS INSPECTION FIRE RATED PLY WOOD | 4/29/2026 3:08:56 PM
4/29/2026 3:08 PM Kelly Sherman
Visual Inspection on Fire Rated Plywood on IT Rooms - Braulio with Turner SPO
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/30/2026 6:55:20 AM
PARTIAL-
WITNESS INSPECTION Inspection on Fire Rated Plywood on IT Rooms - Braulio with Turner SPO - OK.
4/30/2026 12:00:14 PM
PARTIAL-
1st FLOOR -
1) WITNESS INSPECTION FOR FIRE RATED PLY WOOD AT IT 140 - OK.
2nd FLOOR- HEAD OF WALL
1) WITNESS MINERAL WOOL INSULATION & FIRE RIP INSIDE & OUTSIDE WALLS AT IT 220 - OK.
2) MINERAL WOOL INSULATION & FIRE RIP INSIDE & OUTSIDE WALLS AT ELECTRIC 210 - OK.
3) SECOND LAYER 5/8 TYP X GYP EXPECT EXTERIOR WALL IT 220 - OK.
|
|
| 04/30/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 4/29/2026 3:07:18 PM
4/29/2026 3:07 PM Kelly Sherman
2nd Floor Screw & Head of Wall 2nd layer Inspection - Jesus w/ICI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
4/30/2026 12:00:16 PM
PARTIAL-
1ST FLOOR -
1) FRAMING & INSULATION AT WEST SIDE LOBBY 110 - OK.
2) FRAMING AT NORTH OUTSIDE WALL & EAST SIDE OF LOBBY 110 - OK.
3) FRAMING / INSULATION & RATED 2x BACKING AT VESTIBULE 100 ALL WALLS - OK.
|
|
| 05/05/2026 | B:LATH STONE OR BRICK TIE | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 5/4/2026 3:23:08 PM
5/4/2026 3:23 PM Kelly Sherman
NE Corner Lath Inspection - Junior w/BSM
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/5/2026 11:57:09 AM
PARTIAL-
1) N/E CORNER LATH - OK.
|
|
| 05/07/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 5/6/2026 7:28:49 PM
5/6/2026 7:28 PM Gordon Galbraith
1st floor domestic water - Fabian w/CMS - reinspection for failed inspection on 5/4
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
5/7/2026 12:16:05 PM
Over head domestic water ok as marked on P2.11 see picture.
Included 3 hose bibs.
|
|
| 05/08/2026 | B:DRYWALL FIRE WALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 5/7/2026 8:43:51 AM
5/7/2026 8:43 AM Kelly Sherman
Fire Rated Plywood on 2nd Floor IT - Braulio w/SPO
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/8/2026 2:23:24 PM
PARTIAL-
WITNESS RATED SHEETING FOR (IT ROOM 220) - OK.
|
|
| 05/13/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 5/12/2026 1:56:46 PM
5/12/2026 1:56 PM Kelly Sherman
North Stair Insulation - ICI w/Ever
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/13/2026 1:29:11 PM
PARTIAL-
1) CORE & SHELL FRAMING FOR INTERIOR SOUTH STAIRS LEVELS ONE & TWO - OK.
NOTE: LID FRAMING TO BE INSPECTED AT FUTURE CORE & SHELL INSPECTION.
|
|
| 05/13/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | | 5/13/2026 1:29:49 PM
PARTIAL-
1) R19 INSULATION & PROTECTED / PUTTY PADS FOR ELECTRICAL BOXES / NORTH STAIRS, NORTH OUTSIDE WALL OF (E) VESTIBULE E100 - OK.
|
|
| 05/14/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 5/13/2026 5:19:08 PM
5/13/2026 5:19 PM Kelly Sherman
2nd Floor C&S - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/14/2026 10:51:18 AM
Rough electrical walls only
Upstairs core and shell room approved
|
|
| 05/22/2026 | B:DRYWALL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 5/21/2026 1:10:25 PM
5/21/2026 1:10 PM Kelly Sherman
Screw Inspection South Stair & Shell, North Stair - Ever w/ ICI
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
5/22/2026 11:37:20 AM
PARTIAL-
1). DRY WALL SCREW INSPECTION SOUTH STAIR WELL - OK.
|
|
| 05/28/2026 | B:ROUGH FRAME | JOE CARBAUGH | CANCEL | eTRAKiT Inspection Request | 5/27/2026 4:23:42 PM
5/27/2026 4:23 PM Gordon Galbraith
east side exterior, framing beneath metal panels - Flynn
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
5/28/2026 6:50:18 AM
CANCELED- DUPLICATE INSPECTION.
|
|
| 05/28/2026 | B:RE ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 5/27/2026 2:34:47 PM
5/27/2026 2:34 PM Gordon Galbraith
West exterior canopy rough frame - ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
5/28/2026 12:57:41 PM
PARTIAL-
1) Z CHANNELS ON EXTERIOR EAST ELEVATION - OK.
2) COLD FORM STILL FRAMING FOR WEST ELEVATION COVER ? OK.
|
|
| 06/02/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | | 6/2/2026 1:12:33 PM
Piping for domestic water on first floor complete and approved. Still needs insulation.
|
|
| 06/08/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 6/5/2026 4:51:33 PM
6/5/2026 4:51 PM Gordon Galbraith
exterior framing inspection prior to insulation for metal wall panels - Jeff with Flynn
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/8/2026 1:26:09 PM
PARTIAL
1) EXTERIOR HORIZONTAL FRAMING ON EXTERIOR/ NORTH WALL OF NORTH ELEVATOR - OK.
|
|
| 06/09/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | 1st & 2nd Floor Storm Piping | 6/8/2026 12:33:00 PM
6/8/2026 12:33 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
6/9/2026 2:48:12 PM
All storm water drain test approved. Need insulation
Marked in Blue on P2.23,P2.22, P2.21 see pics.
All 6 roof drains approved.
|
|
| 06/10/2026 | B:EXTERIOR AND INTERIOR SHEAR AND SHEATHING | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 6/9/2026 8:44:55 PM
6/9/2026 8:44 PM Gordon Galbraith
Exterior insulation for metal panels - Jeff with Flynn
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/10/2026 2:26:08 PM
PARTIAL-
1) RIDGED FOAM INSULATION & Z TRACK ON NORTH EXTERIOR ELEVATOR ALL ELEVATION - OK.
2) UNDER FRONT ENTRANCE COVER Z TRACK CHANNEL ON N/ W & S - OK.
6/10/2026 3:15:09 PM
PARTIAL-
1) RIDGED FOAM INSULATION & Z TRACK ON NORTH EXTERIOR ELEVATOR ALL ELEVATION - OK.
2) UNDER FRONT ENTRANCE COVER Z TRACK CHANNEL ON N/ W & S - OK.
|
|
| 06/10/2026 | B:ROUGH FRAME | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 6/9/2026 8:43:06 PM
6/9/2026 8:43 PM Gordon Galbraith
Exterior framing for insulated metal panels - Jeff with Flynn
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/10/2026 2:26:15 PM
NOT APPROVED-
1) COMPLETE ALL RGH MEP's AT FIRST FLOOR HARD LIDS.
2) SEE PICTURE OF MARKED UP PLANS & NOTES FOR 06/09/26 RGH FRAME INSPECTION.
NOTE: RE- CALL RGH FRAME / HARD LID INSPECTIONS FOR FIRST FLOOR WHEN (ALL) ITEMS HAVE BEEN CORRECTED.
6/10/2026 3:15:14 PM
NOT APPROVED-
1) COMPLETE ALL RGH MEP's AT FIRST FLOOR HARD LIDS.
2) SEE PICTURE OF MARKED UP PLANS & NOTES FOR 06/09/26 RGH FRAME INSPECTION.
NOTE: RE- CALL RGH FRAME / HARD LID INSPECTIONS FOR FIRST FLOOR WHEN (ALL) ITEMS HAVE BEEN CORRECTED.
|
|
| 06/10/2026 | B:ELECTRICAL TRENCH | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 6/9/2026 8:42:00 PM
6/9/2026 8:42 PM Gordon Galbraith
Inspection for underground fiber conduit, two 4" east side of building - Dan with Duro
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/10/2026 9:14:25 AM
Underground- 2 - 4" fiber sleeves approved
Pull box to pull box east side
|
|
| 06/16/2026 | B:RE ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 5/12/2026 1:54:01 PM
5/12/2026 1:54 PM Kelly Sherman
South Stair Framing - ICI w/Ever
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/15/2026 9:58:06 AM
6/15/2026 9:58 AM Gordon Galbraith
final two studs at east exterior curtain wall - Ever w/ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/16/2026 1:23:18 PM
PARTIAL-
FIRST FLOOR
1) RGH WINDOW FRAMING / STAFF LOUNGE 112- OK.
2) RGH WINDOW FRAME / EMS LOUNGE 129 - OK.
3) RGH FRAME / MAIN ENTRANCE LEFT/ SOUTH ELEVATION- OK.
SECOND FLOOR
1) RGH WINDOW FRAMING / STAFF LOUNGE 214 - OK.
|
|
| 06/16/2026 | B:INSULATION | JOE CARBAUGH | CANCEL | eTRAKiT Inspection Request | 4/14/2026 3:20:03 PM
4/14/2026 3:20 PM Gordon Galbraith
Mineral wool slab edge east side - Jesus ICI
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/15/2026 9:59:21 AM
6/15/2026 9:59 AM Gordon Galbraith
spandrel insulation 1st & second floor - Kelly w/Turner
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
6/16/2026 1:23:23 PM
NOT APPROVED.
NOTE: INSPECTION NOT REQUIRED.
|
|
| B:RE ROUGH FRAME | BRETT LONGNECKER | | eTRAKiT Inspection Request | 6/17/2026 3:48:18 PM
6/17/2026 3:48 PM Kelly Sherman
Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
|
|
| B:RE ROUGH ELECTRICAL | VINCE RAPONE | | eTRAKiT Inspection Request | 6/17/2026 3:48:59 PM
6/17/2026 3:48 PM Kelly Sherman
Underground w/Dan
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
|
|
| 06/18/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 6/17/2026 3:52:01 PM
6/17/2026 3:52 PM Kelly Sherman
Underground w/Dan
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/18/2026 2:30:00 PM
Rough electrical partial inspection approved
1. 1in pvc going to center pole in east parking lot. Going into landscape (marked on plans)
2. 6 3 1/2 pvc conduits user cabinet coming from stub up to transformer. (See photo)
3. six 3 1/2 inch PVC conduit from user cabinet going into the building. ( see photo)
4. Room e100 verify access panel at final electrical hard lid inspection
|
|
| 06/18/2026 | B:ROUGH FRAME | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 6/17/2026 3:51:02 PM
6/17/2026 3:51 PM Kelly Sherman
Frame w/Brian w/E&K
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/18/2026 3:23:56 PM
NOT APPROVED.
1) NOT READY AT TIME OF INSPECTION.
|
|
| 06/22/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | Underground lightpole feeder east side | 6/19/2026 4:14:25 PM
6/19/2026 4:14 PM Braden Frey
Underground lightpole feeder east side
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: bmfrey@tcco.com
6/22/2026 1:16:04 PM
3 - 3" pvc future car chargers
1 - 1" pvc for light pole
road crossing okay
|
|
| 06/22/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 6/19/2026 1:21:23 PM
6/19/2026 1:21 PM Kelly Sherman
2nd Floor overhead Vent Piping w/Fabian CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/22/2026 3:12:34 PM
All drain waste and vent for 2nd Floor approved.
|
|
| 06/24/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 6/23/2026 2:48:21 PM
6/23/2026 2:48 PM Kelly Sherman
South Stair Hardlid & Underground - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/24/2026 2:39:44 PM
Hard lid electrical rough south stair level 1 & 2 okay
Electrical trench light pole and j box okay
|
|
| 06/25/2026 | B:LATH STONE OR BRICK TIE | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 6/24/2026 12:14:59 PM
6/24/2026 12:14 PM Kelly Sherman
Lath for canopies & generator enclosure - Junior w/BSM
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/25/2026 1:21:45 PM
PARTIAL
1) LATH INSPECTION AT CMU GENERATOR WALL & FRONT ENTRANCE COLUMN's - OK.
|
|
| 06/25/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 6/24/2026 2:39:36 PM
6/24/2026 2:39 PM Kelly Sherman
2nd Floor Overhead Domestic Water
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/25/2026 2:51:00 PM
All 2nd floor water lines approved and roof hydrant. Still needs insulation.
6/25/2026 2:52:16 PM
All 2nd floor water lines approved and roof hydrant. Still needs insulation.
|
|
| 06/29/2026 | B:LATH STONE OR BRICK TIE | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 6/26/2026 10:51:41 AM
6/26/2026 10:51 AM Kelly Sherman
West Columns Lath Inspection - Junior w/BSM
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
6/29/2026 2:55:17 PM
PARTIAL-
1) LATH INSPECTION FOR WEST ENTRANCE COLUMNS ? OK.
|
|
| 07/02/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 7/1/2026 4:00:48 PM
7/1/2026 4:00 PM Kelly Sherman
Overhead Domestic Water on Level 2 Insulation - Fabian w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/2/2026 10:27:53 AM
All water lines insulated on 2nd floor.
7/2/2026 1:19:10 PM
All water lines insulated on 2nd floor.
|
|
| 07/07/2026 | B:LATH STONE OR BRICK TIE | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 7/6/2026 1:50:21 PM
7/6/2026 1:50 PM Kelly Sherman
East Bumpout Lath - Junior w/BSM
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/7/2026 3:11:15 PM
APPROVED.
|
|
| 07/08/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 7/7/2026 3:24:46 PM
7/7/2026 3:24 PM Kelly Sherman
Canopies - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/8/2026 2:45:21 PM
Rough electrical inspection partial approved
Notes
Outside under canopy can lights and gutter heat trace two locations one on east side of building and one on west side of building
|
|
| 07/08/2026 | B:GAS PIPE AIR TEST | MARTIN MAGERS | APPROVED | eTRAKiT Inspection Request | 7/7/2026 8:42:51 AM
7/7/2026 8:42 AM Kelly Sherman
All Gas Piping - Fabian w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/8/2026 3:26:25 PM
Gas pipe and air test approved.
|
|
| 07/09/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/8/2026 2:02:50 PM
7/8/2026 2:02 PM Kelly Sherman
East & West Canopy Framing
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
7/9/2026 1:38:04 PM
PARTIAL-
1) RGH FRAME AT EAST &WEST LID/ COVERS - OK.
|
|
| 07/21/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | Water Entry & Water Heater Rough | 7/20/2026 1:35:32 PM
7/20/2026 1:35 PM COLORADO MECHANICAL SYSTEMS LLC
Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm.
Contact Name: COLORADO MECHANICAL SYSTEMS LLC
Site Address: 4141 PLUM CREEK BLVD
Phone: 3037049745
e-Mail: AR@COLORADOMECH.COM
7/21/2026 12:10:38 PM
Approved piping in water heater room. Consulted on water meter release.
|
|
| 07/24/2026 | B:FIRE STOPPING AND PENETRATIONS | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 7/23/2026 4:44:25 PM
7/23/2026 4:44 PM Gordon Galbraith
If possible, please arrive as close to 10am as possible. Elevator shaft penetrations & top of shaft & top of stair core.
Contact Name: Braden Frey
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035183298
e-Mail: bmfrey@tcco.com
7/24/2026 11:28:36 AM
PARTIAL-
1) PENETRATIONS / BEAM POCKETS & SEAL AT UNDER SIDE OF ROOF DECK - OK. STAIR SOUTH, OPEN STAIR NORTH & ELEVATOR 120.
2) FIRE STOP SYSTEM AT HEAD OF CMU WALL TO DECK TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 08/06/2026 | B:GROUND PLUMBING | MARTIN MAGERS | CANCEL | eTRAKiT Inspection Request | 8/5/2026 12:36:44 PM
8/5/2026 12:36 PM Kelly Sherman
Main Line for Irrigation
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
8/6/2026 11:56:49 AM
Wrong inspection scheduled.
|
|
| 08/07/2026 | L: BACKFLOW SURVEY INSPECTION | ERIN SWEENEY | APPROVED | See notes. | 8/7/2026 11:07:01 AM
Appropriate backflow protection for use and level of hazard. Passing test reports required prior to issuance of C.O. or T.C.O. Any questions please contact Erin Sweeney at xconnection@crgov.com or 720-733-6020. Field notes attached.
|
|
| 08/07/2026 | B:CAISSONS | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 8/6/2026 10:47:04 AM
8/6/2026 10:47 AM Kelly Sherman
Light Pole Bases - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
8/7/2026 8:27:07 AM
Inspector VIRA changed the inspection assignment from VIRA to SHVA
8/7/2026 11:40:36 AM
6
8/7/2026 2:50:58 PM
Caissons light pole inspection not approved
1. There is no current structural detail uploaded to plans or permit at this time. Plans that were provided on site have not been reviewed by the town of castle rock.
Notes
Verified 6 caisson that match the plans that have not been approved yet. Pour at your own risk as this current caisson plans have not been approved
Upload caisson light pole detail contact front building contact when plans are uploaded
Marked on site lighting plans on what has been inspected
Underground raceways from light pole to light pole have not been ran at this time
|
|
| U:METER SET COMM | METER SERVICES | | VOIDED (GRSW 8/7/2026) | 8/7/2026 4:50:44 PM
Inspection voided by GRSW.
|
|
| 08/10/2026 | B:ELECTRICAL SERVICE | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 8/7/2026 3:46:57 PM
8/7/2026 3:46 PM Kelly Sherman
ELectrical Service INspection - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
8/10/2026 1:43:37 PM
Electrical service inspection partial approved
Missing 3/0 grounding jumper from MDC to IT room
Missing SPD at MDC
Snow melt panel shows on one line diagram need clarification
Will verify at next service inspection sub panels
Notes
Marked on site plans what is approved at the time
cold water, building steel, ufer , and ground rod approved
|
|
| 08/11/2026 | B:ROUGH MECHANICAL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 8/10/2026 1:56:52 PM
8/10/2026 1:56 PM Kelly Sherman
Mechanical TI Inspection - Nick w/CMS
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
8/11/2026 1:53:53 PM
PARTIAL-
1) 1st floor AREA ( B) above ceiling - OK.
|
|
| 08/13/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 8/12/2026 2:13:27 PM
8/12/2026 2:13 PM Kelly Sherman
Light Pole Inspection - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
8/13/2026 2:45:59 PM
4 - light pole caissons approved
|
|
| 08/17/2026 | U:METER SET COMM | GRANT TAYLOR | APPROVED | | |
|
| L: BACKFLOW SURVEY INSPECTION | ERIN SWEENEY | | VOIDED (ERSW 8/18/2026) | 8/18/2026 7:15:56 AM
Inspection voided by ERSW.
|
|
| 08/24/2026 | B:FIRE STOPPING AND PENETRATIONS | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 8/21/2026 2:39:55 PM
8/21/2026 2:39 PM Gordon Galbraith
Rated wall penetration inspection to close ceilings, 1st & 2nd Floor
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
8/24/2026 3:32:58 PM
NOT APPROVED-
1) INSPECTION WAS TURNED INTO A CONSULTATION ABOUT FIRE STOP SYSTEM INDUCTING THROUGH THROUGH PENETRATIONS.
|
|
| 08/31/2026 | B:FIRE STOPPING AND PENETRATIONS | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 8/28/2026 7:35:33 AM
8/28/2026 7:35 AM Gordon Galbraith
rated wall firestopping. State Fire will be on site from 1-3pm.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/1/2026 6:56:28 AM
NOT APPROVED-
1) FIRE STOP SYSTEM FOR PENETRATIONS PRE- WALK.
|
|
| 09/01/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 8/31/2026 8:57:48 AM
8/31/2026 8:57 AM Kelly Sherman
Light Pole Bases
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
9/1/2026 1:07:49 PM
2 - 1" conduits - light poles irrigation.
3 - light pole caissons
|
|
| 09/01/2026 | B:FIRE STOPPING AND PENETRATIONS | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 8/31/2026 10:11:42 PM
8/31/2026 10:11 PM Gordon Galbraith
State inspection moved from 8/31 to 11:30am on 9/1. Hoping to have this inspection coincide.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/1/2026 3:11:34 PM
PARTIAL-
1) FIRST FLOOR FIRE-STOPPING FOR MEMBRANE & THROUGH PENETRATIONS ABOVE CEING GRID LINES MARKED IN GREEN - OK.
NOTE: MARKINGS IN BLUE STILL NEED TO BE INSPECTED AT FUTURE INSPECTION.
|
|
| 09/02/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/1/2026 1:45:38 PM
9/1/2026 1:45 PM Gordon Galbraith
1st & 2nd floor in-wall rough at elevator front
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
9/2/2026 2:53:51 PM
Rough electrical partial inspection approved
1st and 2nd floor wall rough for elevator lobby
Marked on plans what was inspected at this time
|
|
| 09/02/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/1/2026 1:39:54 PM
9/1/2026 1:39 PM Kelly Sherman
Underground Light Pole Conduit
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
9/2/2026 2:53:54 PM
Underground trench inspection partial approved
Under ground 1in pvc from light pole to light pole marked on plans what was inspected
|
|
| 09/10/2026 | B:FIRE STOPPING AND PENETRATIONS | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 9/9/2026 10:56:35 PM
9/9/2026 10:56 PM Gordon Galbraith
state fire will be on site at 1pm. if inspections can conincide that would be preferable. rated wall penetrations, 1st & 2nd floors
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/10/2026 1:16:06 PM
NOT APPROVED-
1) PRE WALK FOR FIRE, STOPPING IN PENETRATIONS.
|
|
| 09/11/2026 | B:FIRE STOPPING AND PENETRATIONS | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/10/2026 2:07:40 PM
9/10/2026 2:07 PM Gordon Galbraith
Rated wall penetrations on 1st & 2nd floor.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/11/2026 2:55:26 PM
APPROVED-
1) FIRST FLOOR & SECOND FLOOR - OK.
|
|
| B:ROUGH ELECTRICAL | VINCE RAPONE | | eTRAKiT Inspection Request | 9/15/2026 2:19:00 PM
9/15/2026 2:19 PM Kelly Sherman
Exterior Light Poles - Dan w/Duro
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
|
|
| 09/22/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 9/21/2026 4:01:50 PM
9/21/2026 4:01 PM Kelly Sherman
Electrical Light Poles, Elevator Rough, & C&S Ceilings
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
9/22/2026 2:54:37 PM
Rough electrical inspection approved
Elevator shaft and pit inspection
Rough roof top inspection, verify labels and wire size at final
Core and shell ceiling complete
Core and shell electrical roughs completed
|
|
| 09/23/2026 | B:ELECTRICAL TRENCH | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 9/22/2026 3:41:37 PM
9/22/2026 3:41 PM Kelly Sherman
There is no udnerground electrical option under inspection type. This inspection is for underground electrical for light pole bases.
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
9/23/2026 10:36:35 AM
Electrical trench partial approved
Notes
4 landscape lights east front entrance and caissons each light in ground j box.
1 landscape lights south side of building and caissons
1in PVC stub ups into caissons
|
|
| 09/25/2026 | B:ROUGH MECHANICAL | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/24/2026 5:01:22 PM
9/24/2026 5:01 PM Gordon Galbraith
Close out both ceiling & walls
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/25/2026 3:09:06 PM
RGH MECHANICAL- APPROVED.
|
|
| 09/25/2026 | B:FIRE STOPPING AND PENETRATIONS | JOE CARBAUGH | CANCEL | eTRAKiT Inspection Request | 9/24/2026 4:59:59 PM
9/24/2026 4:59 PM Gordon Galbraith
Includes visual on fire dampers.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/25/2026 3:09:08 PM
CANCELED
SPOKE WITH SUPERINTENDENT GORDON GALBRAITH VIA PHONE. CONTRACTOR WILL RE-CALL INSPECTION WHEN READY.
|
|
| 09/28/2026 | B:DRYWALL | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/27/2026 7:37:14 PM
9/27/2026 7:37 PM Gordon Galbraith
Final drywall to sign permit card
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/28/2026 11:58:12 AM
APPROVED - WHOLE BUILDING.
|
|
| 09/29/2026 | B:ROUGH MECHANICAL | BRETT LONGNECKER | APPROVED | eTRAKiT Inspection Request | 9/28/2026 12:11:30 PM
9/28/2026 12:11 PM Gordon Galbraith
Fire dampers. Fire AHJ''s will be on site from 12pm - 3pm for visual inspection of all fire dampers.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
|
|
| 09/29/2026 | B:FIRE STOPPING AND PENETRATIONS | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/28/2026 12:14:29 PM
9/28/2026 12:14 PM Gordon Galbraith
Final for firestopping & penetrations.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/29/2026 3:13:09 PM
APPROVED. VERTICAL FIRE-STOP SYSTEM- OK.
|
|
| 09/29/2026 | B:FINAL FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/28/2026 12:12:33 PM
9/28/2026 12:12 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/29/2026 3:46:35 PM
PARTIAL-
FIRE DAMPER TEST- ED LAB 147 , PAT TLT 146, SOILED 145, CLEAN 135, MED PREP 134 - OK.
NOTE: REST OF DAMPERS TO BE CHECKED AT FUTURE INSPECTION.
|
|
| 09/30/2026 | B:FINAL FRAME | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/29/2026 4:22:48 PM
9/29/2026 4:22 PM Gordon Galbraith
CRFD will be on site at 9am to continue fire damper inspection.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
9/30/2026 11:08:14 AM
APPROVED-
1) ALL FIRE DAMPERS IN BUILDING HAVE BEEN INSPECTED & APPROVED FROM BUILDING & CASTLE ROCK FIRE.
|
|
| 10/01/2026 | B:LATH STONE OR BRICK TIE | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 9/30/2026 2:31:43 PM
9/30/2026 2:31 PM Gordon Galbraith
All weather barrier, lath & stone complete.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/1/2026 2:22:52 PM
APPROVED.
|
|
| 10/01/2026 | B:RE FINAL BUILDING | BRETT LONGNECKER | NOT APPROVED | eTRAKiT Inspection Request | 9/30/2026 4:03:19 PM
9/30/2026 4:03 PM Gordon Galbraith
Stocking acceptance pending 1pm fire alarm annunciator panel replacement & inspection by CRFD.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/1/2026 3:58:50 PM
Ok FOR STOCK ONLY. NO EMPLOYEES ARE ALLOWED UNTIL A STOCK AND TRAIN HAS BEEN APPROVED BY TOWN OF CASTLE ROCK BUILDING DIVISION AND FIRE LIFE SAFETY DIVISION.
THIS INSPECTION WAS ONLY TO VERIFY GENERAL LIFE SAFETY ITEMS FOR STOCKING ONLY. A FULL FINAL BUILDING INSPECTION WILL BE PERFORMED ONCE READY FOR STOCK AND TRAIN AND TCO.
|
|
| 10/06/2026 | B:ELECTRICAL TRENCH | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 10/5/2026 10:12:53 AM
10/5/2026 10:12 AM Kelly Sherman
Underground Electrical
Contact Name: Kelly Sherman
Site Address: 4141 PLUM CREEK BLVD
Phone: 7208549829
e-Mail: ksherman@tcco.com
10/6/2026 10:02:19 AM
Electrical trench inspection approved
Notes
5 light poles underground inspection 1in pvc north and north east outside of parking lot.
Underground for core and shell complete
|
|
| 10/21/2026 | B:FINAL ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 10/19/2026 1:47:42 PM
10/19/2026 1:47 PM Gordon Galbraith
Generator blackout test with Castle Rock Fire & DFPC at 9AM
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/21/2026 10:42:52 AM
Final electrical inspection partial approved
Notes
Generator black-out test. Verify critical branch circuits switch with generator when normal loss of power is simulated. Verified receptacles, EM lights exit lights.
This inspection was scheduled on core and shell permit. Verified these teams on IT side also.
|
|
| 10/22/2026 | B:FINAL PLUMBING | MARTIN MAGERS | APPROVED | eTRAKiT Inspection Request | 10/19/2026 1:57:36 PM
10/19/2026 1:57 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/22/2026 1:46:40 PM
All plumbing and gas pipe approved.
|
|
| 10/22/2026 | B:FINAL MECHANICAL | JOE CARBAUGH | APPROVED | eTRAKiT Inspection Request | 10/19/2026 1:57:10 PM
10/19/2026 1:57 PM Gordon Galbraith
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/22/2026 1:55:12 PM
APPROVED.
1) CONTROL WIRING AT EXHAUST FAN FOR A & 4B ROOF TOP.
2) STATIC PRESSURE AT RTU SENSOR.
3) REST OF CORE & SHELL - OK.
NOTE: ITEMS ABOVE TO BE CHECKED AT FINAL BUILDING.
|
|
| 10/22/2026 | B:FINAL ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 10/19/2026 1:55:44 PM
10/19/2026 1:55 PM Gordon Galbraith
Panels & gear, panel schedules, phenolic labels etc etc.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/22/2026 2:57:54 PM
Final electrical inspection partial approved for core and shell only
Rooms with corrections
1. Facp room 160. Label all blank j box cover plates, data missing bushing and ko fillers
2. Med gas room 190 label blank j box covers
3. Room 150 water entry label j box covers
4. 1st floor data room e140 label all j box covers, disconnect, thermostat incomplete
5. 1st floor ambulance entry missing can light trim controls incomplete
6. Access panel not installed for for sign j box 1st floor elevator lobby
7. 2nd floor room e220 label disconnects, label receptacles, emt missing bushing, have all junction boxes closed
Recall inspection when corrections are completed
Not inspection at this time
Roof top final inspection, exterior site inspection light poles, complete service inspection.
|
|
| 10/23/2026 | B:ELECTRICAL SERVICE | SHAWN VALENZUELA | NOT APPROVED | eTRAKiT Inspection Request | 10/21/2026 11:46:13 AM
10/21/2026 11:46 AM Gordon Galbraith
Service inspection.
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
10/26/2026 7:00:51 AM
Electrical service inspection not approved
1. Plans show aluminum wire feeding generator currently installed is 3 parallel runs of 4 300 and 1/0 ground in each conduit. Please upload plans showing copper in replacement of aluminum.
Recall inspection when corrections are completed
Rest of service ok pending revision
|
|
| 10/23/2026 | B:FINAL ELECTRICAL | SHAWN VALENZUELA | CANCEL | eTRAKiT Inspection Request | 10/22/2026 3:43:19 PM
10/22/2026 3:43 PM Gordon Galbraith
Roof & any labeling / fixes Dan Castro can get done between now & 10/23 PM
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
|
|
| 10/26/2026 | Z:FNL SITE COMPLIA | SCOTT SEUBERT | APPROVED | | 10/26/2026 12:48:09 PM
approved . waiting sign call for inspections.
|
|
| 10/26/2026 | B:FINAL ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 10/21/2026 11:48:21 AM
10/21/2026 11:48 AM Gordon Galbraith
Roof & exterior finals.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/26/2026 2:28:30 PM
Final electrical inspection partial approved core and shell only
Core and shell electrical service has not passed at this time. Final building for core and shell can not be approved until electrical service is approved
Notes
Roof top core and shell final inspection approved
Inside building core and shell approved
Outside exterior inspection has not been completed at this time.
Schedule inspection when ready.
|
|
| 10/27/2026 | B:FINAL ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 10/26/2026 3:03:26 PM
10/26/2026 3:03 PM Gordon Galbraith
Final exterior.
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
10/27/2026 3:22:34 PM
Final electrical inspection, core, and shell only
Generator revision needs to be reviewed and approved by the town of Castlerock before final electrical inspection will be approved
Exterior final electrical is approved
|
|
| 10/27/2026 | B:ELECTRICAL SERVICE | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 10/23/2026 3:15:01 PM
10/23/2026 3:15 PM Gordon Galbraith
Final, including all fixes noted during other final inspections.
Contact Name: Dan Castro
Site Address: 4141 PLUM CREEK BLVD
Phone: 7205958205
e-Mail: ggalbraith@tcco.com
10/27/2026 3:22:37 PM
Electrical service inspection approved
All corrections have been completed
Generator revision has been uploaded. This has not been reviewed by the town of Castle rock until this revision is reviewed and approved. This will hold up final electrical inspection on Core Shell.
|
|
| 10/28/2026 | B:REQUEST TCO REVIEW | BUILDING COUNTER | CANCEL | eTRAKiT Inspection Request | 10/22/2026 7:15:10 PM
10/22/2026 7:15 PM Gordon Galbraith
Pending TCO inspections on 10/27 & document upload to eTrakit.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/28/2026 8:07:33 AM
The Final Building inspection determines when a TCO or CO can be issued.
|
|
| 10/27/2026 | B:FINAL BUILDING | BRETT LONGNECKER | INC OK FOR TCO | eTRAKiT Inspection Request | 10/22/2026 7:14:15 PM
10/22/2026 7:14 PM Gordon Galbraith
Attempting to get DFPC, Castle Rock Fire, & Castle Rock Building all on site at 2pm for life safety & building TCO final.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/27/2026 3:46:12 PM
1. 1st floor data room fireproofing at beams needs patches from removed fireproofing.
2. Complete final mechanical.
3. Complete final electrical.
4. Compete final fire.
|
|
| 10/29/2026 | B:FIRE STOPPING AND PENETRATIONS | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 10/28/2026 2:17:33 PM
10/28/2026 2:17 PM Gordon Galbraith
Missed conduit firestopping on 2nd floor.
Contact Name: Gordon Galbraith
Site Address: 4141 PLUM CREEK BLVD
Phone: 3038422415
e-Mail: ggalbraith@tcco.com
10/29/2026 2:32:52 PM
NOT APPROVED.
NOTE: FIRE STOP FOR CONFERENCE 211 ABOVE GRID TO BE LOOKED AT BUILDING FINAL. REST OF FIRE STOP - OK.
FIRE STOP OK FOR TCO.
|
|
| 11/12/2026 | B:RE FINAL ELECTRICAL | SHAWN VALENZUELA | APPROVED | eTRAKiT Inspection Request | 11/10/2026 12:15:52 PM
11/10/2026 12:15 PM Braden Frey
Updated one-line showing change in generator feeder material uploaded to eTrackit.
Contact Name: Braden Frey
Site Address: 4141 PLUM CREEK BLVD
Phone: 3035183298
e-Mail: bmfrey@tcco.com
11/12/2026 11:54:00 AM
Final electrical inspection approved
All corrections have been completed
|
|