Permit No. 25-1611 Permit Type   COMMERCIAL NEW Site Address   4141 PLUM CREEK BLVD
CASTLE ROCK, CO 80104
Applied   05/09/2025 Applicant   Andrew Holcomb
Approved   10/23/2025 Owner   PORTERCARE ADVENTIST HEALTH SYSTEM
Issued   10/23/2025 Contractor  
Parent Permit No.   Description   ADVENTHEALTH MEDICAL OFFICE
  Notes   Please also reference SDP25-001
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 10/16/2025B:ELECTRICAL SERVICEVINCE RAPONEPARTIALUFER GROUND10/16/2025 3:19:44 PM Ufer ground good Concrete encased electrode

 11/05/2025PRE CON INSPECTIONBRETT LONGNECKERAPPROVED11/6/2025 3:56:58 PM Complete Building Pre Con on Wednesday, November 5th at 2:00 pm with Gordan Galbraith, Braden Frey and Lars Nilsson. Gave contractor building precon folder with all inspection cards, checklists and general requirements to the Town of Castle Rock Building Division.

 11/21/2025B:UNGRD PLUMBMARTIN MAGERSAPPROVEDFinal Underground Plumbing Inspection11/20/2025 12:41:29 PM 11/20/2025 12:41 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 11/20/2025 12:46:51 PM 11/20/2025 12:46 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 11/21/2025 12:10:43 PM All DVW and Storm Drains approved.

 12/29/2025B:UNGRD PLUMBMARTIN MAGERSPARTIALAfter 9am inspection preferred.12/24/2025 12:23:28 PM 12/24/2025 12:23 PM Gordon Galbraith Inspection of storm leader to storm drain underground connections prior to backfill. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 12/29/2025 2:43:36 PM Storm drain connection on the east side approved.

 01/12/2026B:RGH ELECTVINCE RAPONEPARTIALUnderslab Electrical1/9/2026 1:33:39 PM 1/9/2026 1:33 PM Braden Frey Underslab Electrical Inspection Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: bmfrey@tcco.com 1/12/2026 3:26:08 PM Under slab pvc trunk line up to electrical room good Low volt sleeves Branch circuiting

 01/14/2026B:RGH ELECTVINCE RAPONEPARTIALunder slab1/13/2026 1:21:19 PM 1/13/2026 1:21 PM Gordon Galbraith Additional under slab inspection to allow for backfill. Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 1/14/2026 12:25:02 PM Under slab rough electrical 1" pvc HR trunk line good

 01/15/2026TRAINING_SHAWNSHAWN VALENZUELAPARTIALunder slab electrical room1/15/2026 12:52:06 PM Under slab electrical room good This completes under slab

 01/15/2026B:ELECTRICAL TRENCHVINCE RAPONEPARTIALunder slab electrical room1/14/2026 3:29:42 PM 1/14/2026 3:29 PM Gordon Galbraith Final under slab electrical inspection to complete backfill Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 1/15/2026 3:03:23 PM Under slab electrical room good This completes under slab

 01/16/2026B:UNGRD PLUMBMARTIN MAGERSAPPROVEDDecon Tank UG Inspection1/15/2026 10:09:54 AM 1/15/2026 10:09 AM COLORADO MECHANICAL SYSTEMS LLC Decon Tank UG Inspection. Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: nkinder@coloradomech.com 1/16/2026 12:55:40 PM Decon tank and pump approved.

 01/28/2026B:EXT SHEAR_SHEATHIJOE CARBAUGHPARTIALPartial exterior cold formed framing1/27/2026 1:29:34 PM 1/27/2026 1:29 PM Gordon Galbraith East & west building elevations Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 1/28/2026 3:06:15 PM PARTIAL- CHECKED EXTERIOR WALL CONNECTIONS FROM FIRST FLOOR TO SECOND FLOOR . 1) FCB43.5'S , FCB45.4'S CONNECTIONS AT GRID LINE (B) / EAST FROM 2 - 4.7 - OK PER PLAN. 2) FCB43.5'S , FCB45.4'S CONNECTION AT GRID LINE (F) / WEST FROM 3-5 - OK PER PLAN. Note: Rest of grid lines for exterior-wall connections to be checked at future inspection.

 02/04/2026B:UNGRD PLUMBMARTIN MAGERSAPPROVEDUnderground water from meter pit2/3/2026 8:26:36 AM 2/3/2026 8:26 AM Gordon Galbraith Contact Name: Fabian Mendez Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: ggalbraith@tcco.com 2/4/2026 12:05:35 PM Water line from meter pit to building approved.

 02/04/2026B:EXT SHEAR_SHEATHIJOE CARBAUGHCANCELeTRAKiT Inspection Request2/3/2026 8:39:03 AM 2/3/2026 8:39 AM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 2/4/2026 2:19:30 PM DUPLICATE INSPECTION.

 02/06/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request2/5/2026 3:33:25 PM 2/5/2026 3:33 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 2/6/2026 2:16:08 PM PARTIAL- MINERAL WOOL INSULATION AT ROOF PARAPET WALLS - APPROVED FROM GRID LINES ( F 4 - 5 ). NOTE: REST OF MINERAL WOOL INSULATION & GRID LINES TO BE CHECKED AT FUTURE INSPECTION.

 02/10/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request2/9/2026 11:36:25 AM 2/9/2026 11:36 AM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 2/10/2026 2:36:52 PM INSULATION-(PARTIAL) MINERAL WOOL AT ROOF PARAPET WALLS - GRID ( C- F) SOUTH SIDE , GRID ( 1- 3) WEST SIDE, GRID (5-7) WEST SIDE , GRID ( D- F) NORTH SIDE-OK PER PLAN. NOTE: GRID (5 - 5.5) EAST AND (A- D) NORTH AT PARAPET WALLS TO BE CHECKED AT FUTURE INSPECTION.

 02/12/2026B:EXT SHEAR_SHEATHIJOE CARBAUGHPARTIALeTRAKiT Inspection Request2/11/2026 10:30:38 AM 2/11/2026 10:30 AM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 2/12/2026 3:40:38 PM ITEMS INSPECTED 1) 5/8 DEN GLASS - SECOND FLOOR GRID LINES ( C - F SOUTH ) / GRID LINES (1-6 WEST) / GRID LINES (C - F NORTH) & GRID LINE ( A 1.1 - 5.5 2) 5/8 DEN GLASS EXTERIOR SHEAR/ SCREW INSPECTION - FIRST & SECOND FLOOR GRID LINES ( C - F SOUTH ) / GRID LINES (1-6 WEST) / GRID LINES (C - F NORTH) & GRID LINE ( A 1.1 - 5.5 - OK. 3) FRAMING AT TOP OF FIRST FLOOR WALL TO SECOND FLOOR FRAMI NG OK THRUGH RID LINE (C- F) SOUTH , ( F 1-5) WEST- OK.

 02/13/2026B:RGH PLUMBMARTIN MAGERSAPPROVEDStorm drain tie in - west side2/12/2026 10:39:19 AM 2/12/2026 10:39 AM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 2/13/2026 10:11:49 AM Storm drain stub outs ok

 02/13/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request2/12/2026 10:16:55 PM 2/12/2026 10:16 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 2/13/2026 2:12:17 PM RGH FRAME - 1) ROOF PARAPET FRAMING WALLS & CONNECTIONS AT NORTH / EAST CORNER - GRID LINES (A 4.7- 7) & (A - C) - OK. NOTE: OK TO PLACE REQUIRED MINERAL WOOL AT REQUIRED SECTION ABOVE.

 02/17/2026B:EXT SHEAR_SHEATHIJOE CARBAUGHCANCELeTRAKiT Inspection Request2/13/2026 12:58:19 PM 2/13/2026 12:58 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 2/17/2026 12:17:20 PM CANCELED DO TO WEATHER.

 02/20/2026B:EXT SHEAR_SHEATHIJOE CARBAUGHPARTIALeTRAKiT Inspection Request2/19/2026 11:45:16 PM 2/19/2026 11:45 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 2/20/2026 11:18:08 AM EXT SHEAR SHEATHING- 1) MINERAL WOOL / DENS DECK & NAILING -OK AT GRID LINES (A 4.7- 7 EAST & A - C NORTH ROOF PARAPET WALL).

 02/26/2026B:EXT SHEAR_SHEATHIBRETT LONGNECKERPARTIALnorth elevation2/25/2026 1:12:14 PM 2/25/2026 1:12 PM Braden Frey Exterior Column Framing Contact Name: Braden Frey Site Address: 4141 PLUM CREEK BLVD Phone: 3035183298 e-Mail: bmfrey@tcco.com 2/26/2026 1:00:26 PM North elevation of structure exterior sheathing complete.

 03/03/2026B:EXT SHEAR_SHEATHIJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/2/2026 1:20:35 PM 3/2/2026 1:20 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/3/2026 3:52:15 PM 1) IT ROOM 140 TOP OUT RATED 2 hr EAST & WEST WALLS - 1st layer of 5/8 type X - PENDING UL ASSEMBLY HW-D-0420 2) MECHANICAL ROOM 160 - WEST & EAST 16" WALL - 1 EACH SIDE 1 HOUR RATED UL ASSEMBLY HW-D-0420 - OK. 3) DENS GLASS AT NORTH EAST GRID LINES C- F & FIN WALL AT GRID LINE C- F SCREW / SHEATHING INSPECTION - OK. 4) ELECTRICAL ROOM 170- 1 LAYER 1 HOUR RATED WALLS EAST, WEST & NORTH INSIDE OF ROOM DRY WALL & SCREW SCHEDULE - OK. 5) DENS GLASS SHEATHING- SOUTH SIDE / GRID LINES C- F - OK.

 03/04/2026B:RGH FRAMEBRETT LONGNECKERNOT APPROVEDeTRAKiT Inspection Request3/3/2026 4:04:51 PM 3/3/2026 4:04 PM Gordon Galbraith North east overhang cold form framing Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/4/2026 2:37:34 PM Cold steel frame for east entry overhang ok. Highlighted in blue on town approved plans S2.02 and uploaded photo. Cold steel exterior wall frame east entry ok. Highlighted in blue on town approved plans S2.01 and uploaded photo.

 03/09/2026B:RGH MECHMARTIN MAGERSPARTIALFire Damper Framing Inspection3/6/2026 11:22:50 AM 3/6/2026 11:22 AM COLORADO MECHANICAL SYSTEMS LLC Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3035197973 e-Mail: AR@COLORADOMECH.COM 3/9/2026 1:23:08 PM Duct work as high lighted on M2.11 in yellow. 3/9/2026 1:24:36 PM Duct work as high lighted on M2.11 in yellow.

 03/09/2026B:INSULATIONJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request3/6/2026 1:35:19 PM 3/6/2026 1:35 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/9/2026 3:33:55 PM NOT APPROVED. Not ready at time of inspection.

 03/10/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/9/2026 3:23:19 PM 3/9/2026 3:23 PM Gordon Galbraith Exterior eye brow framing mineral wool insulation Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/10/2026 2:06:10 PM PARTIAL ? MINERAL WOOL INSULATION AT GRID LINES A 4.7 - 7 EAST & A 7 - C NORTH- APPROVED.

 03/11/2026B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request3/10/2026 4:09:47 PM 3/10/2026 4:09 PM Gordon Galbraith Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 3/11/2026 10:44:56 AM Rough electrical walls only - above drop ceiling good Okay to rock

 03/17/2026B:DRYWALLJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request3/16/2026 5:41:28 PM 3/16/2026 5:41 PM Gordon Galbraith Top of wall drywall interior. Jesus with ICI. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/17/2026 3:38:26 PM PARTIAL- SECOND LAYER TOP OF WALL DRY-WALL INSPECTION AT WEST WALL ONLY OF IT 140 - OK.

 03/17/2026B:RGH FRAMEJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request3/16/2026 5:40:34 PM 3/16/2026 5:40 PM Gordon Galbraith Small bit of cold form framing on the SE exterior of the building & some top of wall framing interior. For Jesus with ICI. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/17/2026 3:38:28 PM NOT APPROVED- SOUTH / EAST BUMP- OUT - OK PER ON SITE UPDATED DETAIL 3 , PENDING TOWN REVIEW.

 03/18/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/17/2026 7:43:28 PM 3/17/2026 7:43 PM Gordon Galbraith Witness install of UL head of wall - ICI Jesus Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/18/2026 3:56:55 PM Partial- 1). (2) HR RATED HW- D - 0420 DRYWALL/ SCREW INSPECTION - TOP OUT (2) LAYERS OF 5/8 TYPE X AT INTERIOR SIDE OF WEST & EAST WALLS IN IT 140. 2). IT 140 CORRIDOR 105 (1st) LAYER DRYWALL/ SCREW INSPECTION- TOP OUT 5/8 TYPE X - OK.

 03/18/2026B:INSULATIONJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request3/17/2026 7:42:13 PM 3/17/2026 7:42 PM Gordon Galbraith upper roof east side mineral wool - ICI Jesus. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/18/2026 3:56:58 PM PARTIAL- ENTRANCE COVER INSULATION FROM GRID LINES 4.7 SOUTH 4.7- 7 - OK.

 03/18/2026B:EXT SHEAR_SHEATHIJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/17/2026 7:40:45 PM 3/17/2026 7:40 PM Gordon Galbraith East side upper eyebrow sheathing - ICI Jesus. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/18/2026 3:57:00 PM PARTIAL- DEN-GLASS AT FRONT ENTRANCE COVER - OK.

 03/19/2026B:FIRE SMOKE RESISTJOE CARBAUGHNOT APPROVEDSECOND LAYER TOP OUT AT IT ROOM 1403/18/2026 1:55:53 PM 3/18/2026 1:55 PM Gordon Galbraith 1st Floor - IT room 140 2nd layer drywall top out - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/19/2026 2:54:48 PM 1) DRYWALL (2ND) LAYER TOP OUT OF 2 HR SOUTH RATED WALL AT - IT ROOM 140 - OK.

 03/23/2026B:RGH PLUMBBRETT LONGNECKERPARTIALOverhead Vent & In-Wall Domestic3/20/2026 12:52:45 PM 3/20/2026 12:52 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30 pm Contact Name: Fabian Mendez Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 3/23/2026 12:47:27 PM Waste and overhead and wall vent, domestic water test wall only for 1st floor as highlighted in blue in town approved plans P2.21. TI in wall rough inspected on this permit.

 03/23/2026B:RGH MECHJOE CARBAUGHNOT APPROVEDFire Damper Framing Inspection3/20/2026 12:53:54 PM 3/20/2026 12:53 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 7205359789 e-Mail: AR@COLORADOMECH.COM 3/23/2026 1:57:16 PM PARTIAL- DAMPER FRAMING - AT AMBULANCE AREA - OK.

 03/27/2026B:DRYWALLMARTIN MAGERSPARTIALeTRAKiT Inspection Request3/26/2026 3:17:09 PM 3/26/2026 3:17 PM Gordon Galbraith 1st Floor electrical & IT Room drywall - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/27/2026 1:18:46 PM 1st layer at IT room 140, Interior walls ok, exterior wall not not started. 1st layer in electrical room, all walls ok.

 03/27/2026B:INSULATIONMARTIN MAGERSPARTIALeTRAKiT Inspection Request3/26/2026 3:16:22 PM 3/26/2026 3:16 PM Gordon Galbraith 1st Floor Insulation - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/27/2026 1:18:48 PM IT room 140,. Insulation, R 13 on south wall ok.

 03/27/2026B:FIRE SMOKE RESISTMARTIN MAGERSPARTIALeTRAKiT Inspection Request3/26/2026 3:19:00 PM 3/26/2026 3:19 PM Gordon Galbraith 1st floor eletrical & IT rooms - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 3/27/2026 1:18:44 PM Fire rip at top of wall at electrical and IT rooms. ok #10 HW-D-0420. 3/27/2026 2:20:11 PM Fire rip at top of wall at electrical and IT rooms. ok #10 HW-D-0420.

 04/01/2026B:DRYWALLJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/31/2026 2:49:38 PM 3/31/2026 2:49 PM Gordon Galbraith 2nd layer screw inspection at IT room - 2 hr assembly - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/1/2026 1:02:39 PM IT ROOM E140 SECOND LAYER DRYWALL & SCREW INSPECTION-OK.

 04/01/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/31/2026 2:48:30 PM 3/31/2026 2:48 PM Gordon Galbraith Level 1 Head of Wall UL @ IT Room - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/1/2026 1:02:42 PM PARTIAL- FIRE RIP SYSTEM AT INTERIOR ROOM OF IT E140-OK.

 04/03/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/2/2026 9:10:35 AM 4/2/2026 9:10 AM Gordon Galbraith Mineral wool at parapet above elevator core Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/3/2026 10:36:30 AM PARTIAL- FRAMING , MINERAL WOOL & SHEATHING AT N/W PARAPET WALL/ WEST SIDE OF CMU. - OK.

 04/03/2026B:WEATHER BARRIERJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/2/2026 8:51:27 AM 4/2/2026 8:51 AM Gordon Galbraith Air barrier south & east elevation Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/3/2026 10:36:35 AM PARTIAL- 1) SOUTH & NORTH ELEVATION / GRID LINES A- F SOUTH ELEVATION- OK. 2) NORTH ELEVATION / GRID LINES A- F NORTH ELEVATION- OK. NOTE: EAST & WEST ELEVATIONS TO BE CHECKED AT FUTURE INSPECTION.

 04/03/2026B:EXT SHEAR_SHEATHIJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request4/2/2026 9:11:43 AM 4/2/2026 9:11 AM Gordon Galbraith Small bit of sheathing at parapet top of elevator core Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/3/2026 10:36:24 AM EXT SHEAR _ SHEATHING - APPROVED.

 04/06/2026B:RGH PLUMBBRETT LONGNECKERCANCELeTRAKiT Inspection Request4/3/2026 2:30:14 PM 4/3/2026 2:30 PM Gordon Galbraith DWV in-wall & OH - plan north - Fabian w/CMS Contact Name: Fabian Mendez Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: ggalbraith@tcco.com 4/6/2026 9:41:23 AM Cancel per conversation with plumbing contractor.

 04/06/2026B:RGH FRAMEJOE CARBAUGHPARTIALZ CHANNEL & CONNECTIONS4/3/2026 2:27:57 PM 4/3/2026 2:27 PM Gordon Galbraith Z furring at east high overhang (eyebrow) & z furring at top of storefront header - Jeff w/ Flynn Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/6/2026 10:51:38 AM PARTIAL- 1) MAIN ENTRANCE COVER Z CHANNEL 16 O.C. & CONNECTIONS AT GRID LINES 4.7- 7 - OK. 2) Z CHANNEL AT 16 O.C. & CONNECTIONS AT FRONT / EAST EYEBROW GRID LINES A 1.1 - 4.7 - Ok.

 04/06/2026B:INSULATIONJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request4/3/2026 2:54:05 PM 4/3/2026 2:54 PM Gordon Galbraith Mineral wool at slab edge - Jesus w/ICI. Afternoon inspection if at all possible. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/6/2026 2:49:05 PM WITNESS INSPECTION - 1) SECOND FLOOR EDGED OF SLAB INSULATION (NORTH WALL) / GRID LINE 6 F-C MINERAL WOOL INSULATION INSPECTION- 711119a HILTI - OK

 04/07/2026B:FIRE SMOKE RESISTJOE CARBAUGHCANCELeTRAKiT Inspection Request4/6/2026 3:32:18 PM 4/6/2026 3:32 PM Gordon Galbraith 2nd floor north side slab edge spray Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/7/2026 2:54:19 PM INSPECTION CANCELED BY CONTRACTOR.

 04/07/2026B:RGH PLUMBBRETT LONGNECKERPARTIAL1st floor DWV4/6/2026 3:30:47 PM 4/6/2026 3:30 PM Gordon Galbraith Waste & Vent 1st Floor - water test Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/7/2026 3:20:15 PM 1st floor ok except drinking fountain DWV to 2nd floor and EVS closet.

 04/08/2026B:DRYWALLJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/7/2026 3:06:56 PM 4/7/2026 3:06 PM Gordon Galbraith Rigid insulation - exterior - Jeff w/Flynn Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/8/2026 3:27:42 PM NOT APPROVED- 1) (FIRST LAYER) DRYWALL SCREW INSPECTION/ NORTH WALL OF IT 220 - OK. 2) FIRST LAYER) 1HR DRYWALL SCREW INSPECTION/ NORTH WALL FOR CORE & SHELL STAFF TOILET 209 -OK. NOTE: THROUGH PENETRATION AT REAR/ NORTH WALL DETAIL 5 PENETRATION AT RATED PARTITIONS PAGE A7.10 TO BE CHECKED AT FUTURE INSPECTION.

 04/08/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/7/2026 2:28:00 PM 4/7/2026 2:28 PM Gordon Galbraith 2nd Floor electrical room - 1st layer drywall - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/8/2026 3:27:45 PM 1) SECOND FLOOR EDGED OF SLAB INSULATION (SOUTH WALL) / GRID LINES 1 F-C MINERAL WOOL INSULATION INSPECTION- 711119a HILTI - OK

 04/08/2026B:LATH INSPECTIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/7/2026 2:24:10 PM 4/7/2026 2:24 PM Gordon Galbraith East elevation, stone veneer - Junior w/BSM Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/8/2026 3:27:48 PM PARTIAL- 1) LATH INSPECTION ON EAST ELEVATION/ GRID LINES 1.1 THROUGH 4.7 - OK.

 04/09/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request4/8/2026 3:02:28 PM 4/8/2026 3:02 PM Gordon Galbraith 1st floor in-wall - Dan w/Duro Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/9/2026 10:57:53 AM 1st floor core and shell wall rough electrical Room numbers 150, 190, 180, 170, 160, 140, 110 ok to drywall

 04/09/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/8/2026 3:28:09 PM 4/8/2026 3:28 PM Gordon Galbraith 2nd layer dryall & slab edge - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/9/2026 3:13:41 PM DRYWALL SCREW INSPECTION ELECTRICAL ROOM 210 - 1) 2nd LAYER DRYWALL/ SCREW INSPECTION, HEAD OF WALL ZIP SYSTEM & BOTTOM TRACK SEAL CFS-BTS 5/8 SEAL -OK. 2) 1ST LAYER DRYWALL IT ROOM 220 WEST WALL & EAST WALL- OK.

 04/09/2026B:LATH INSPECTIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/8/2026 2:54:22 PM 4/8/2026 2:54 PM Gordon Galbraith Stone inspection exterior - east elevation - Junior w/BSM Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/9/2026 3:13:43 PM PARTIAL- 1) ISTO PRIMER/ ADHESIVE -B AT (E) STAIR SOUTH E501 - OK.

 04/09/2026B:EXT SHEAR_SHEATHIJOE CARBAUGHPARTIALEFIS INSPECTION4/8/2026 2:49:48 PM 4/8/2026 2:49 PM Gordon Galbraith EIFs, east & south elevation - Junior w/BSM Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/9/2026 3:13:45 PM PARTIAL- EIFS-INSPECTION At (E) STAIR SOUTH E501- OK. R13089 CERTIFIED/ 68P7 RATED RIDGED FOAM, ISTO PRIMER/ ADHESIVE -B, 80921 STO ARMOR MAT& VM- 04 80lb.

 04/09/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/8/2026 2:47:58 PM 4/8/2026 2:47 PM Gordon Galbraith Exterior insulation - Jeff w/Flynn Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/9/2026 3:13:47 PM PARTIAL- 1) SECOND FLOOR EDGED OF SLAB INSULATION (WEST WALL) / GRID LINES F 3-4 MINERAL WOOL INSULATION INSPECTION- 711119a HILTI - OK.

 04/10/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request4/9/2026 2:13:43 PM 4/9/2026 2:13 PM Gordon Galbraith 2nd floor wall rough - Dan w/Duro Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/10/2026 11:37:48 AM 2nd floor core and shell partial Core and shell areas ok to drywall on 2nd floor Shell space 2nd floor area B south west corner of building mechanical shaft verify on final 2 access panels are installed , IT room 220, electrical room 210, 2nd floor bathroom 209. Ok to drywall if all other inspections have been completed Mechanical shaft outside of 208 need to finish framing ****not ok to drywall**** Elevator inspection has not been conducted at this time of inspection

 04/10/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALHEAD OF WALL FIRE RIP INSPECTION4/9/2026 2:12:53 PM 4/9/2026 2:12 PM Gordon Galbraith West side slab edge mineral wool - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/10/2026 3:14:58 PM PARTIAL- 1) HEAD OF WALL FIRE RIP & FRAMING INSPECTION AT ELECTRICAL ROOM 210 & GRID LINE D & 2 - OK.

 04/10/2026B:LATH INSPECTIONJOE CARBAUGHCANCELeTRAKiT Inspection Request4/9/2026 2:08:07 PM 4/9/2026 2:08 PM Gordon Galbraith EIFS & Stone - Junior w/BSM Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/10/2026 3:15:00 PM CANCELED- 1) COURTESY INSPECTION FOR STEPS & REQUIRED BY TOWN.

 04/10/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/9/2026 2:07:27 PM 4/9/2026 2:07 PM Gordon Galbraith 1st & 2nd floor - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/10/2026 3:15:04 PM RGH FRAME CORE & SHELL- 1) RGH FRAME - FOR SHELL SPACE AT GRID LINES D & 2 - OK 2) MECHANICAL- SOUTH ELEVATION COMBO FIRE/ SMOKE DAMPER DUCT & PENETRATIONS - OK. 3) RGH FRAME - ELECTRICAL 210, IT ROOM 220 ALL HEAD OF WALLS & WALLS -OK.

 04/10/2026B:RGH MECHJOE CARBAUGHPARTIALLevel 2 Fire Damper Frame Inspection4/9/2026 2:35:42 PM 4/9/2026 2:35 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3:30pm Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3035197973 e-Mail: AR@COLORADOMECH.COM 4/10/2026 3:15:09 PM PARTIAL- 1) MECHANICAL- (SOUTH ELEVATION) COMBO FIRE/ SMOKE DAMPER DUCT / PENETRATIONS & ATTACHMENT- OK PER MANUFACTURER INSTALLATION INSTRUCTIONS.

 04/10/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIAL4/10/2026 3:15:46 PM PARTIAL- 1) WITNESS INSPECTION - HILTI 711119a CFS-SP WB FIRE-STOP JOINT SPRAY 1/8" (WET) AT WEST, NORTH & SOUTH ELEVATIONS - OK. NOTE: 2nd LAYER 1" MINERAL WOOL AT SLAB EDGE TO BE INSPECTED AT FUTURE SMOKE RESIST INSPECTION.

 04/13/2026B:INSULATIONJOE CARBAUGHPARTIALTOP OUT INSULATION FOR CORN & SHELL4/10/2026 6:07:23 PM 4/10/2026 6:07 PM Gordon Galbraith Insulation - 1st & 2nd floor - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/13/2026 4:13:45 PM TOP OUT / HEAD OF WALL INSULATION R19 FOR CORN & SHELL INSPECTION TWO FULL AREAS 1st FLOOR- (WEST) ELEVATION - 1) GRIDS F 2-7 (TOP OUT / HEAD OF WALL) EXTERIOR WALL- OK. 2) EXAM 125 & BARIATRIC 117 - (FULL) EXTERIOR WALL- OK. ( NORTH) ELEVATION - 1) GRID LINES- F - C ON 6 - OK. 2nd FLOOR - TOP OUT EXTERIOR INSULATION - 1) EAST/ SOUTH/ WEST & NORTH ELEVATIONS - OK. CORE & SHELL 1) (FULL WALL) R19 FOR EXTERIOR & R13 FOR INTERIOR WALLS - OK. IT 220 & ELECTORAL 210

 04/13/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/10/2026 6:04:33 PM 4/10/2026 6:04 PM Gordon Galbraith 2nd floor slab edge, framing & insulation Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/13/2026 4:13:48 PM WITNESS- 1) SOUTH WALL - 1 INCH MINERAL WALL AT SECOND FLOOR SLAB EDGE INSPECTION AT GRID LINES 1 F- C - OK. 2) NORTH WALL - 1 INCH MINERAL WALL AT SECOND FLOOR SLAB EDGE INSPECTION AT GRID LINES 6 F-C - OK. 3) WEST WALL- 1 INCH MINERAL WALL AT SECOND FLOOR SLAB EDGE INSPECTION AT GRID LINES - F 1- 6 - OK.

 04/13/2026B:RGH MECHJOE CARBAUGHPARTIALLevel 2 Shaft Fire Damper Openings4/10/2026 1:16:18 PM 4/10/2026 1:16 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Patrick Hughes (303)519-7973. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3035197973 e-Mail: AR@COLORADOMECH.COM 4/13/2026 4:13:51 PM Level 2 Shaft Fire Damper Openings & ATTACHMENTS - OK.

 04/14/2026B:INSULATIONJOE CARBAUGHPARTIALEFIS INSPECTION4/13/2026 5:32:06 PM 4/13/2026 5:32 PM Gordon Galbraith Slab edge mineral wool - east side - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/14/2026 11:12:14 AM PARTIAL- 1) EFIS INSPECTION AT S/E CORNER & FRONT/ EAST FACING ELEVATION GRID LINe 1 C-B & GRID LINE B 1- 4.7 - OK.

 04/14/2026B:DRYWALLJOE CARBAUGHPARTIALDRYWALL/SCREW INSPECTION4/13/2026 5:31:23 PM 4/13/2026 5:31 PM Gordon Galbraith Screw inspection - 1st floor vestibule - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/14/2026 11:12:16 AM PARTIAL- DRYWALL / SCREW INSPECTION 1) VESTIBULE 100 INTERIOR DRYWALL/ SCREW INSPECTION FIRST LAYER 5/8 TYPE X - OK PENDING EXTERIOR WATER PROOFING.

 04/14/2026B:RGH FRAMEJOE CARBAUGHPARTIALINTERIOR CORN SHELL FRAMING, FIRST FLOOR4/13/2026 5:30:36 PM 4/13/2026 5:30 PM Gordon Galbraith 1st Floor mech room/IT room/vestibule - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/14/2026 11:12:19 AM PARTIAL- FIRST FLOOR INTERIOR CORE & SHELL FRAMING 1) IT 140 WHOLE ROOM - OK. 2) VESTIBULE 100 & LOBBY 110 - OK. 3) MECH/ FIRE ROOM 160 & ELECTRICAL 170- OK.

 04/14/2026B:LATH INSPECTIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/13/2026 5:34:10 PM 4/13/2026 5:34 PM Gordon Galbraith EIFS - Junior w/BSM Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/14/2026 11:12:11 AM PARTIAL- 1) FULL SOUTH ELEVATION / GRID LINES 1 F-C LATH & ATTACHMENT INSPECTION - OK.

 04/15/2026B:INSULATIONJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request4/14/2026 3:20:52 PM 4/14/2026 3:20 PM Gordon Galbraith IT room north side - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/15/2026 3:01:29 PM PARTIAL- 2nd FLOOR 1 LAYER OF 3" MINERAL WOOL WITNESS (CEJ421P) PERIMETER FIRE BARRIER SYSTEM INSPECTION GID LINES B 1- 4.7 EAST WALL - OK.

 04/16/2026B:RGH PLUMBBRETT LONGNECKERPARTIALin wall pipe insulation4/15/2026 4:09:18 PM 4/15/2026 4:09 PM Gordon Galbraith 1st floor domestic water insulation - Fabian w/CMS Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/16/2026 9:44:17 AM 1st floor in wall domestic water pipe insulation ok.

 04/16/2026B:INSULATIONJOE CARBAUGHPARTIALEXTERIOR INSULATION INSPECTION4/15/2026 4:10:34 PM 4/15/2026 4:10 PM Gordon Galbraith Exterior insulation 1st floor - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/16/2026 9:55:42 AM PARTIAL- 1) EXTERIOR INSULATION R19 INSPECTION/ NORTH & WEST WALLS - OK.

 04/16/2026B:FIRE SMOKE RESISTJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request4/15/2026 4:11:53 PM 4/15/2026 4:11 PM Gordon Galbraith Slab edge final fire spray - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/16/2026 9:55:38 AM PARTIAL- 1) WITNESS INSPECTOR SLAB EDGE CEJ421 P ( HI/BP 120-03) ASTM E 2307 SRAY GRID LINES (B) (1-4.7) . -OK.

 04/17/2026B:LATH INSPECTIONJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request4/16/2026 4:17:13 PM 4/16/2026 4:17 PM Gordon Galbraith Final stone inspection - east side - Junior w/BSM Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/17/2026 3:03:08 PM NOT APPROVED. 1) DRAIN NOT SEALED. REST OF EAST ELEVATION - OK. NOTE: BLANKET OR INSULATE FOR TEMPERATURES WHILE CURING.

 04/17/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/16/2026 4:16:04 PM 4/16/2026 4:16 PM Gordon Galbraith 2nd floor east slab edge - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/17/2026 3:03:10 PM PARTIAL- 1) FIRST FLOOR WITNESS INSPECTION OF MINERAL WOOL AT SLAB EDGE ( EAST) WALL/ ELEVATION CEJ421 P GRID LINES ( B 3-4) OK.

 04/20/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/17/2026 3:05:37 PM 4/17/2026 3:05 PM Gordon Galbraith 1st floor insulation - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/20/2026 3:16:11 PM 1st FLOOR INSTALLATION R13 INTERIOR WALLS AND R 19 EXTERIOR WALLS INSPECTION 1) IT 140 SOUTH , EAST & WEST WALLS - OK. 2) WATER ENTRY 150 NORTH WALL - OK. 3) MECHANICAL/ FIRE 160 ALL WALLS - OK.

 04/21/2026B:DRYWALLJOE CARBAUGHPARTIALDRYWALL / SCREW INSPECTION4/20/2026 3:37:15 PM 4/20/2026 3:37 PM Gordon Galbraith 1st floor drywall (screw) - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/21/2026 10:50:47 AM PARTIAL- 1) DRYWALL / SCREW INSPECTION 141 (NORTH WALL 1 LAYER ONLY) - OK . 2) DRYWALL/ SCREW INSPECTION ELEC 170 SOUTH WALL NORTH SIDE OF WALL - OK

 04/21/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/20/2026 3:37:52 PM 4/20/2026 3:37 PM Gordon Galbraith 1st floor framing - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/21/2026 10:50:44 AM PARTIAL- 1) CORE & SHELL FULL WALL FRAME AT WATER ENTRY 150, EM ELEC 150 & MED GAS 190 - OK.

 04/21/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/20/2026 3:36:36 PM 4/20/2026 3:36 PM Gordon Galbraith 1st floor insulation - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/21/2026 10:50:50 AM PARTIAL- 1st FLOOR INSULATION & WITNESS MINERAL WOOL INSULATION. 1) MECH/FIRE 160 & ELEC 170 ALL WALLS R13 - OK. 2) WITNESSES MINERAL WOOL AT BEAM POCKET & R13 WALL INSPECTION AT EM ELEC 180 - OK. 3) WATER ENTRY ROOM 150 R13 ALL WALLS - OK.

 04/22/2026B:INSULATIONJOE CARBAUGHPARTIALEAST ELEVATION EXTERIOR INSULATION R194/21/2026 3:07:27 PM 4/21/2026 3:07 PM Gordon Galbraith 1st floor east exam room exterior wall insulation - Brian w/E&K Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/22/2026 3:14:55 PM PARTIAL- 1) EAST ELEVATION EXTERIOR INSULATION R19 GRID LINES A 1 THROUGH 4.7 - OK.

 04/22/2026B:LATH INSPECTIONJOE CARBAUGHPARTIALLATH INSPECTION S/W ELEVATION4/21/2026 3:06:14 PM 4/21/2026 3:06 PM Gordon Galbraith West elevation lath - Junior w/BSM Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/22/2026 3:14:58 PM PARTIAL- 1) LATH INSPECTION S/W ELEVATION -OK.

 04/22/2026B:DRYWALLJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/21/2026 3:08:05 PM 4/21/2026 3:08 PM Gordon Galbraith 1st floor screw inspection - Jesus w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 4/22/2026 3:14:52 PM PARTIAL- CORE & SHELL WITNESSES DRYWALL/SCREW INSPECTION FOR ASSEMBLY U411 (2) HR WALL - IT 140 WITNESSES DRYWALL/SCREW INSPECTION FOR ASSEMBLY U465 (1) HR WALL - ELEC 170 1) 1st LAYER 5/8 TYPE X DRYWALL & SCREW INSPECTION - EAST OUT SIDE WALL OF IT 140 - OK. 2) WITNESSES 5/8 TYPE X DRYWALL & SCREW INSPECTION- EAST OUT SIDE WALL OF ELEC 170 - OK. 3) DRYWALL 5/8 TYPE X & SCREW INSPECTION ALL WALLS MEC/ FIRE 160 **** ( EXCEPT SOUTH WEST CORNER). ****

 04/23/2026B:INSULATIONJOE CARBAUGHPARTIAL2ND FLOOR EXTERIOR INSULATION4/22/2026 3:36:41 PM 4/22/2026 3:36 PM Kelly Sherman 1st Floor Screw Inspection - Jesus w/ICI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/23/2026 1:53:41 PM PARTIAL- 2ND FLOOR EXTERIOR INSULATION AT SOUTH & WEST WALLS OF SHELL SPACE 1) R19 BATT INSULATION AT GRID LINES C THROUGH F & F 1 THROUGH 3.5 - OK.

 04/23/2026B:INSULATIONJOE CARBAUGHCANCELDUPLICATE INSPECTION4/22/2026 2:51:22 PM 4/22/2026 2:51 PM Kelly Sherman 2nd Floor Exterior Insulation - Brian with E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/23/2026 1:53:46 PM CANCELED- DUPLICATE INSPECTION.

 04/23/2026B:DRYWALLJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/22/2026 3:36:41 PM 4/22/2026 3:36 PM Kelly Sherman 1st Floor Screw Inspection - Jesus w/ICI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/23/2026 1:53:44 PM PARTIAL- 1) WITNESS (2nd) LAYER 5/8 TYPE X DRYWALL & SCREW INSPECTION / U411 (2 HR RATED ASSEMBLY) - IT 140 OUTSIDE EAST INTERIOR WALL - OK . 2) (1st) LAYER 5/8 X DRYWALL & SCREW INSPECTION / U411 (2 HR RATED ASSEMBLY) - IT 140 - OK .

 04/24/2026B:DRYWALLJOE CARBAUGHPARTIALDRYWALL & SCREW INSPECTION4/23/2026 2:43:30 PM 4/23/2026 2:43 PM Kelly Sherman 1st Floor Screw Inspection - Jesus w/ICI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/24/2026 11:15:06 AM PARTIAL- 1st FLOOR 1) ONE LAYER 5/8 TYPE X ALL WALLS IN EM ELEC - 180 - OK. 2) ONE LAYER 5/8 TYPE X AT EAST & WEST WALLS OF DECONTAM - 133 CORE & SHELL - OK 3) ONE LAYER 5/8 TYPE X ALL WALLS (E) MED GAS - 190 - OK. 4) ONE LAYER 5/8 TYPE X WEST / OUTSIDE WALL OF TI - 140 - OK. 5) 2nd LAYER 5/8 TYPE X SOUTH & EAST OUTSIDE WALLS OF TI - 140 - OK. 2nd FLOOR 1) WITNESSES FIRST LAYER OF 5/8 TYPE X & SCREW INSPECTION FOR U411 2HR RATED ASSEMBLY OUTSIDE EAST WALL OF IT 220 - OK.

 04/24/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/23/2026 2:42:41 PM 4/23/2026 2:42 PM Kelly Sherman 1st & 2nd Floor Insulation Inspection - Jesus w/ICI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/24/2026 11:15:09 AM PARTIAL - 1) 1st FLOOR INTERIOR INSULATION R13 AT INSIDE WEST WALL OF EM ELEC 180 - OK. 2) 2nd FLOOR SHELL SPACE INSULATION R13 AT GRID LINE D & 2 - OK.

 04/27/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/24/2026 5:07:29 PM 4/24/2026 5:07 PM Kelly Sherman 1st Floor - Jesus w/ICI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/27/2026 1:41:09 PM PARTIAL- WATER ENTRY R19 ROOM 150 - OK.

 04/27/2026B:DRYWALLJOE CARBAUGHPARTIALDRYWALL SCREW INSPECTION4/24/2026 5:07:29 PM 4/24/2026 5:07 PM Kelly Sherman 1st Floor - Jesus w/ICI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/27/2026 1:41:12 PM PARTIAL- 1) DRYWALL SCREW INSPECTION FOR WATER ENTRY 150 - OK. 2) (CORE & SHELL MECH) - FIRE ROOM 160 OUTSIDE NORTH WALL & EAST OUTSIDE WALL ELEC 170 - OK.

 04/27/2026B:LATH INSPECTIONJOE CARBAUGHPARTIALLATH N/ W CORNER INSPECTION4/24/2026 2:03:26 PM 4/24/2026 2:03 PM Kelly Sherman Lath Inspection on North - Junior w/BSM Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/27/2026 1:41:14 PM PARTIAL- 1) N/ W CORNER LATH INSPECTION - OK. NOTE: PICTURES ATTACHED.

 04/28/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALFIRE RIP AT HEAD OF WALL4/27/2026 6:44:46 PM 4/27/2026 6:44 PM Kelly Sherman Insulation & Fireproofing - Jesus w/ICI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/28/2026 12:33:26 PM PARTIAL- FIRE RIP AT HEAD OF WALL FOR - 1) IT 140 ALL WALLS EXCEPT EXTERIOR - OK. 2) EM ELEC 180 ALL WALLS EXCEPT EXTERIOR - OK. 3) ELEC 170 ALL WALLS - OK. 4) MEC FIRE 160 ALL WALLS EXCEPT EXTERIOR - OK. 5) MEC GAS 180 ALL WALLS EXCEPT EXTERIOR - OK. 6) WATER ENTRY 150 ALL WALLS EXCEPT EXTERIOR - OK.

 04/28/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/27/2026 6:44:46 PM 4/27/2026 6:44 PM Kelly Sherman Insulation & Fireproofing - Jesus w/ICI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/28/2026 12:33:23 PM PARTIAL- 1) SECOND FLOOR INSULATION AT MECHANICAL SHAFT / FLOOR DAMPERS AT GRID LINE C/5 - OK.

 04/29/2026B:ELECTRICAL TRENCHSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request4/28/2026 4:20:51 PM 4/28/2026 4:20 PM Kelly Sherman Fiber line - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/29/2026 10:20:50 AM Electrical trench partial approved Notes. 2 4in pvc fiber optic conduits 36ins deep. Both conduits coming from west side of property line to west side of building. Will terminate to under slab conduits feeding IT room. Please call in another inspection when final connections are made to conduits under slab/ utility fiber location on west side of property line.

 04/30/2026B:FIRE SMOKE RESISTJOE CARBAUGHPARTIALWITNESS INSPECTION FIRE RATED PLY WOOD4/29/2026 3:08:56 PM 4/29/2026 3:08 PM Kelly Sherman Visual Inspection on Fire Rated Plywood on IT Rooms - Braulio with Turner SPO Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/30/2026 6:55:20 AM PARTIAL- WITNESS INSPECTION Inspection on Fire Rated Plywood on IT Rooms - Braulio with Turner SPO - OK. 4/30/2026 12:00:14 PM PARTIAL- 1st FLOOR - 1) WITNESS INSPECTION FOR FIRE RATED PLY WOOD AT IT 140 - OK. 2nd FLOOR- HEAD OF WALL 1) WITNESS MINERAL WOOL INSULATION & FIRE RIP INSIDE & OUTSIDE WALLS AT IT 220 - OK. 2) MINERAL WOOL INSULATION & FIRE RIP INSIDE & OUTSIDE WALLS AT ELECTRIC 210 - OK. 3) SECOND LAYER 5/8 TYP X GYP EXPECT EXTERIOR WALL IT 220 - OK.

 04/30/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request4/29/2026 3:07:18 PM 4/29/2026 3:07 PM Kelly Sherman 2nd Floor Screw & Head of Wall 2nd layer Inspection - Jesus w/ICI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 4/30/2026 12:00:16 PM PARTIAL- 1ST FLOOR - 1) FRAMING & INSULATION AT WEST SIDE LOBBY 110 - OK. 2) FRAMING AT NORTH OUTSIDE WALL & EAST SIDE OF LOBBY 110 - OK. 3) FRAMING / INSULATION & RATED 2x BACKING AT VESTIBULE 100 ALL WALLS - OK.

 05/05/2026B:LATH STONE OR BRICK TIEJOE CARBAUGHPARTIALeTRAKiT Inspection Request5/4/2026 3:23:08 PM 5/4/2026 3:23 PM Kelly Sherman NE Corner Lath Inspection - Junior w/BSM Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/5/2026 11:57:09 AM PARTIAL- 1) N/E CORNER LATH - OK.

 05/07/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request5/6/2026 7:28:49 PM 5/6/2026 7:28 PM Gordon Galbraith 1st floor domestic water - Fabian w/CMS - reinspection for failed inspection on 5/4 Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 5/7/2026 12:16:05 PM Over head domestic water ok as marked on P2.11 see picture. Included 3 hose bibs.

 05/08/2026B:DRYWALL FIRE WALLJOE CARBAUGHPARTIALeTRAKiT Inspection Request5/7/2026 8:43:51 AM 5/7/2026 8:43 AM Kelly Sherman Fire Rated Plywood on 2nd Floor IT - Braulio w/SPO Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/8/2026 2:23:24 PM PARTIAL- WITNESS RATED SHEETING FOR (IT ROOM 220) - OK.

 05/13/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request5/12/2026 1:56:46 PM 5/12/2026 1:56 PM Kelly Sherman North Stair Insulation - ICI w/Ever Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/13/2026 1:29:11 PM PARTIAL- 1) CORE & SHELL FRAMING FOR INTERIOR SOUTH STAIRS LEVELS ONE & TWO - OK. NOTE: LID FRAMING TO BE INSPECTED AT FUTURE CORE & SHELL INSPECTION.

 05/13/2026B:INSULATIONJOE CARBAUGHPARTIAL5/13/2026 1:29:49 PM PARTIAL- 1) R19 INSULATION & PROTECTED / PUTTY PADS FOR ELECTRICAL BOXES / NORTH STAIRS, NORTH OUTSIDE WALL OF (E) VESTIBULE E100 - OK.

 05/14/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request5/13/2026 5:19:08 PM 5/13/2026 5:19 PM Kelly Sherman 2nd Floor C&S - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/14/2026 10:51:18 AM Rough electrical walls only Upstairs core and shell room approved

 05/22/2026B:DRYWALLJOE CARBAUGHPARTIALeTRAKiT Inspection Request5/21/2026 1:10:25 PM 5/21/2026 1:10 PM Kelly Sherman Screw Inspection South Stair & Shell, North Stair - Ever w/ ICI Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 5/22/2026 11:37:20 AM PARTIAL- 1). DRY WALL SCREW INSPECTION SOUTH STAIR WELL - OK.

 05/28/2026B:ROUGH FRAMEJOE CARBAUGHCANCELeTRAKiT Inspection Request5/27/2026 4:23:42 PM 5/27/2026 4:23 PM Gordon Galbraith east side exterior, framing beneath metal panels - Flynn Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 5/28/2026 6:50:18 AM CANCELED- DUPLICATE INSPECTION.

 05/28/2026B:RE ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request5/27/2026 2:34:47 PM 5/27/2026 2:34 PM Gordon Galbraith West exterior canopy rough frame - ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 5/28/2026 12:57:41 PM PARTIAL- 1) Z CHANNELS ON EXTERIOR EAST ELEVATION - OK. 2) COLD FORM STILL FRAMING FOR WEST ELEVATION COVER ? OK.

 06/02/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIAL6/2/2026 1:12:33 PM Piping for domestic water on first floor complete and approved. Still needs insulation.

 06/08/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request6/5/2026 4:51:33 PM 6/5/2026 4:51 PM Gordon Galbraith exterior framing inspection prior to insulation for metal wall panels - Jeff with Flynn Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/8/2026 1:26:09 PM PARTIAL 1) EXTERIOR HORIZONTAL FRAMING ON EXTERIOR/ NORTH WALL OF NORTH ELEVATOR - OK.

 06/09/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIAL1st & 2nd Floor Storm Piping6/8/2026 12:33:00 PM 6/8/2026 12:33 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 6/9/2026 2:48:12 PM All storm water drain test approved. Need insulation Marked in Blue on P2.23,P2.22, P2.21 see pics. All 6 roof drains approved.

 06/10/2026B:EXTERIOR AND INTERIOR SHEAR AND SHEATHINGJOE CARBAUGHPARTIALeTRAKiT Inspection Request6/9/2026 8:44:55 PM 6/9/2026 8:44 PM Gordon Galbraith Exterior insulation for metal panels - Jeff with Flynn Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/10/2026 2:26:08 PM PARTIAL- 1) RIDGED FOAM INSULATION & Z TRACK ON NORTH EXTERIOR ELEVATOR ALL ELEVATION - OK. 2) UNDER FRONT ENTRANCE COVER Z TRACK CHANNEL ON N/ W & S - OK. 6/10/2026 3:15:09 PM PARTIAL- 1) RIDGED FOAM INSULATION & Z TRACK ON NORTH EXTERIOR ELEVATOR ALL ELEVATION - OK. 2) UNDER FRONT ENTRANCE COVER Z TRACK CHANNEL ON N/ W & S - OK.

 06/10/2026B:ROUGH FRAMEJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request6/9/2026 8:43:06 PM 6/9/2026 8:43 PM Gordon Galbraith Exterior framing for insulated metal panels - Jeff with Flynn Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/10/2026 2:26:15 PM NOT APPROVED- 1) COMPLETE ALL RGH MEP's AT FIRST FLOOR HARD LIDS. 2) SEE PICTURE OF MARKED UP PLANS & NOTES FOR 06/09/26 RGH FRAME INSPECTION. NOTE: RE- CALL RGH FRAME / HARD LID INSPECTIONS FOR FIRST FLOOR WHEN (ALL) ITEMS HAVE BEEN CORRECTED. 6/10/2026 3:15:14 PM NOT APPROVED- 1) COMPLETE ALL RGH MEP's AT FIRST FLOOR HARD LIDS. 2) SEE PICTURE OF MARKED UP PLANS & NOTES FOR 06/09/26 RGH FRAME INSPECTION. NOTE: RE- CALL RGH FRAME / HARD LID INSPECTIONS FOR FIRST FLOOR WHEN (ALL) ITEMS HAVE BEEN CORRECTED.

 06/10/2026B:ELECTRICAL TRENCHVINCE RAPONEPARTIALeTRAKiT Inspection Request6/9/2026 8:42:00 PM 6/9/2026 8:42 PM Gordon Galbraith Inspection for underground fiber conduit, two 4" east side of building - Dan with Duro Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/10/2026 9:14:25 AM Underground- 2 - 4" fiber sleeves approved Pull box to pull box east side

 06/16/2026B:RE ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request5/12/2026 1:54:01 PM 5/12/2026 1:54 PM Kelly Sherman South Stair Framing - ICI w/Ever Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/15/2026 9:58:06 AM 6/15/2026 9:58 AM Gordon Galbraith final two studs at east exterior curtain wall - Ever w/ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/16/2026 1:23:18 PM PARTIAL- FIRST FLOOR 1) RGH WINDOW FRAMING / STAFF LOUNGE 112- OK. 2) RGH WINDOW FRAME / EMS LOUNGE 129 - OK. 3) RGH FRAME / MAIN ENTRANCE LEFT/ SOUTH ELEVATION- OK. SECOND FLOOR 1) RGH WINDOW FRAMING / STAFF LOUNGE 214 - OK.

 06/16/2026B:INSULATIONJOE CARBAUGHCANCELeTRAKiT Inspection Request4/14/2026 3:20:03 PM 4/14/2026 3:20 PM Gordon Galbraith Mineral wool slab edge east side - Jesus ICI Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/15/2026 9:59:21 AM 6/15/2026 9:59 AM Gordon Galbraith spandrel insulation 1st & second floor - Kelly w/Turner Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 6/16/2026 1:23:23 PM NOT APPROVED. NOTE: INSPECTION NOT REQUIRED.

B:RE ROUGH FRAMEBRETT LONGNECKEReTRAKiT Inspection Request6/17/2026 3:48:18 PM 6/17/2026 3:48 PM Kelly Sherman Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com

B:RE ROUGH ELECTRICALVINCE RAPONEeTRAKiT Inspection Request6/17/2026 3:48:59 PM 6/17/2026 3:48 PM Kelly Sherman Underground w/Dan Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com

 06/18/2026B:ROUGH ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request6/17/2026 3:52:01 PM 6/17/2026 3:52 PM Kelly Sherman Underground w/Dan Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/18/2026 2:30:00 PM Rough electrical partial inspection approved 1. 1in pvc going to center pole in east parking lot. Going into landscape (marked on plans) 2. 6 3 1/2 pvc conduits user cabinet coming from stub up to transformer. (See photo) 3. six 3 1/2 inch PVC conduit from user cabinet going into the building. ( see photo) 4. Room e100 verify access panel at final electrical hard lid inspection

 06/18/2026B:ROUGH FRAMEJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request6/17/2026 3:51:02 PM 6/17/2026 3:51 PM Kelly Sherman Frame w/Brian w/E&K Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/18/2026 3:23:56 PM NOT APPROVED. 1) NOT READY AT TIME OF INSPECTION.

 06/22/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALUnderground lightpole feeder east side6/19/2026 4:14:25 PM 6/19/2026 4:14 PM Braden Frey Underground lightpole feeder east side Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: bmfrey@tcco.com 6/22/2026 1:16:04 PM 3 - 3" pvc future car chargers 1 - 1" pvc for light pole road crossing okay

 06/22/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request6/19/2026 1:21:23 PM 6/19/2026 1:21 PM Kelly Sherman 2nd Floor overhead Vent Piping w/Fabian CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/22/2026 3:12:34 PM All drain waste and vent for 2nd Floor approved.

 06/24/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request6/23/2026 2:48:21 PM 6/23/2026 2:48 PM Kelly Sherman South Stair Hardlid & Underground - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/24/2026 2:39:44 PM Hard lid electrical rough south stair level 1 & 2 okay Electrical trench light pole and j box okay

 06/25/2026B:LATH STONE OR BRICK TIEJOE CARBAUGHPARTIALeTRAKiT Inspection Request6/24/2026 12:14:59 PM 6/24/2026 12:14 PM Kelly Sherman Lath for canopies & generator enclosure - Junior w/BSM Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/25/2026 1:21:45 PM PARTIAL 1) LATH INSPECTION AT CMU GENERATOR WALL & FRONT ENTRANCE COLUMN's - OK.

 06/25/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request6/24/2026 2:39:36 PM 6/24/2026 2:39 PM Kelly Sherman 2nd Floor Overhead Domestic Water Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/25/2026 2:51:00 PM All 2nd floor water lines approved and roof hydrant. Still needs insulation. 6/25/2026 2:52:16 PM All 2nd floor water lines approved and roof hydrant. Still needs insulation.

 06/29/2026B:LATH STONE OR BRICK TIEJOE CARBAUGHPARTIALeTRAKiT Inspection Request6/26/2026 10:51:41 AM 6/26/2026 10:51 AM Kelly Sherman West Columns Lath Inspection - Junior w/BSM Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 6/29/2026 2:55:17 PM PARTIAL- 1) LATH INSPECTION FOR WEST ENTRANCE COLUMNS ? OK.

 07/02/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request7/1/2026 4:00:48 PM 7/1/2026 4:00 PM Kelly Sherman Overhead Domestic Water on Level 2 Insulation - Fabian w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/2/2026 10:27:53 AM All water lines insulated on 2nd floor. 7/2/2026 1:19:10 PM All water lines insulated on 2nd floor.

 07/07/2026B:LATH STONE OR BRICK TIEJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request7/6/2026 1:50:21 PM 7/6/2026 1:50 PM Kelly Sherman East Bumpout Lath - Junior w/BSM Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/7/2026 3:11:15 PM APPROVED.

 07/08/2026B:ROUGH ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request7/7/2026 3:24:46 PM 7/7/2026 3:24 PM Kelly Sherman Canopies - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/8/2026 2:45:21 PM Rough electrical inspection partial approved Notes Outside under canopy can lights and gutter heat trace two locations one on east side of building and one on west side of building

 07/08/2026B:GAS PIPE AIR TESTMARTIN MAGERSAPPROVEDeTRAKiT Inspection Request7/7/2026 8:42:51 AM 7/7/2026 8:42 AM Kelly Sherman All Gas Piping - Fabian w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/8/2026 3:26:25 PM Gas pipe and air test approved.

 07/09/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request7/8/2026 2:02:50 PM 7/8/2026 2:02 PM Kelly Sherman East & West Canopy Framing Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 7/9/2026 1:38:04 PM PARTIAL- 1) RGH FRAME AT EAST &WEST LID/ COVERS - OK.

 07/21/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALWater Entry & Water Heater Rough7/20/2026 1:35:32 PM 7/20/2026 1:35 PM COLORADO MECHANICAL SYSTEMS LLC Please contact Fabian Mendez (303)704-9745. Crew is offsite at 3:30pm. Contact Name: COLORADO MECHANICAL SYSTEMS LLC Site Address: 4141 PLUM CREEK BLVD Phone: 3037049745 e-Mail: AR@COLORADOMECH.COM 7/21/2026 12:10:38 PM Approved piping in water heater room. Consulted on water meter release.

 07/24/2026B:FIRE STOPPING AND PENETRATIONSJOE CARBAUGHPARTIALeTRAKiT Inspection Request7/23/2026 4:44:25 PM 7/23/2026 4:44 PM Gordon Galbraith If possible, please arrive as close to 10am as possible. Elevator shaft penetrations & top of shaft & top of stair core. Contact Name: Braden Frey Site Address: 4141 PLUM CREEK BLVD Phone: 3035183298 e-Mail: bmfrey@tcco.com 7/24/2026 11:28:36 AM PARTIAL- 1) PENETRATIONS / BEAM POCKETS & SEAL AT UNDER SIDE OF ROOF DECK - OK. STAIR SOUTH, OPEN STAIR NORTH & ELEVATOR 120. 2) FIRE STOP SYSTEM AT HEAD OF CMU WALL TO DECK TO BE CHECKED AT FUTURE INSPECTION.

 08/06/2026B:GROUND PLUMBINGMARTIN MAGERSCANCELeTRAKiT Inspection Request8/5/2026 12:36:44 PM 8/5/2026 12:36 PM Kelly Sherman Main Line for Irrigation Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 8/6/2026 11:56:49 AM Wrong inspection scheduled.

 08/07/2026L: BACKFLOW SURVEY INSPECTIONERIN SWEENEYAPPROVEDSee notes.8/7/2026 11:07:01 AM Appropriate backflow protection for use and level of hazard. Passing test reports required prior to issuance of C.O. or T.C.O. Any questions please contact Erin Sweeney at xconnection@crgov.com or 720-733-6020. Field notes attached.

 08/07/2026B:CAISSONSSHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request8/6/2026 10:47:04 AM 8/6/2026 10:47 AM Kelly Sherman Light Pole Bases - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 8/7/2026 8:27:07 AM Inspector VIRA changed the inspection assignment from VIRA to SHVA 8/7/2026 11:40:36 AM 6 8/7/2026 2:50:58 PM Caissons light pole inspection not approved 1. There is no current structural detail uploaded to plans or permit at this time. Plans that were provided on site have not been reviewed by the town of castle rock. Notes Verified 6 caisson that match the plans that have not been approved yet. Pour at your own risk as this current caisson plans have not been approved Upload caisson light pole detail contact front building contact when plans are uploaded Marked on site lighting plans on what has been inspected Underground raceways from light pole to light pole have not been ran at this time

U:METER SET COMMMETER SERVICESVOIDED (GRSW 8/7/2026)8/7/2026 4:50:44 PM Inspection voided by GRSW.

 08/10/2026B:ELECTRICAL SERVICESHAWN VALENZUELAPARTIALeTRAKiT Inspection Request8/7/2026 3:46:57 PM 8/7/2026 3:46 PM Kelly Sherman ELectrical Service INspection - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 8/10/2026 1:43:37 PM Electrical service inspection partial approved Missing 3/0 grounding jumper from MDC to IT room Missing SPD at MDC Snow melt panel shows on one line diagram need clarification Will verify at next service inspection sub panels Notes Marked on site plans what is approved at the time cold water, building steel, ufer , and ground rod approved

 08/11/2026B:ROUGH MECHANICALJOE CARBAUGHPARTIALeTRAKiT Inspection Request8/10/2026 1:56:52 PM 8/10/2026 1:56 PM Kelly Sherman Mechanical TI Inspection - Nick w/CMS Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 8/11/2026 1:53:53 PM PARTIAL- 1) 1st floor AREA ( B) above ceiling - OK.

 08/13/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request8/12/2026 2:13:27 PM 8/12/2026 2:13 PM Kelly Sherman Light Pole Inspection - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 8/13/2026 2:45:59 PM 4 - light pole caissons approved

 08/17/2026U:METER SET COMMGRANT TAYLORAPPROVED

L: BACKFLOW SURVEY INSPECTIONERIN SWEENEYVOIDED (ERSW 8/18/2026)8/18/2026 7:15:56 AM Inspection voided by ERSW.

 08/24/2026B:FIRE STOPPING AND PENETRATIONSJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request8/21/2026 2:39:55 PM 8/21/2026 2:39 PM Gordon Galbraith Rated wall penetration inspection to close ceilings, 1st & 2nd Floor Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 8/24/2026 3:32:58 PM NOT APPROVED- 1) INSPECTION WAS TURNED INTO A CONSULTATION ABOUT FIRE STOP SYSTEM INDUCTING THROUGH THROUGH PENETRATIONS.

 08/31/2026B:FIRE STOPPING AND PENETRATIONSJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request8/28/2026 7:35:33 AM 8/28/2026 7:35 AM Gordon Galbraith rated wall firestopping. State Fire will be on site from 1-3pm. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/1/2026 6:56:28 AM NOT APPROVED- 1) FIRE STOP SYSTEM FOR PENETRATIONS PRE- WALK.

 09/01/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request8/31/2026 8:57:48 AM 8/31/2026 8:57 AM Kelly Sherman Light Pole Bases Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 9/1/2026 1:07:49 PM 2 - 1" conduits - light poles irrigation. 3 - light pole caissons

 09/01/2026B:FIRE STOPPING AND PENETRATIONSJOE CARBAUGHPARTIALeTRAKiT Inspection Request8/31/2026 10:11:42 PM 8/31/2026 10:11 PM Gordon Galbraith State inspection moved from 8/31 to 11:30am on 9/1. Hoping to have this inspection coincide. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/1/2026 3:11:34 PM PARTIAL- 1) FIRST FLOOR FIRE-STOPPING FOR MEMBRANE & THROUGH PENETRATIONS ABOVE CEING GRID LINES MARKED IN GREEN - OK. NOTE: MARKINGS IN BLUE STILL NEED TO BE INSPECTED AT FUTURE INSPECTION.

 09/02/2026B:ROUGH ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request9/1/2026 1:45:38 PM 9/1/2026 1:45 PM Gordon Galbraith 1st & 2nd floor in-wall rough at elevator front Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 9/2/2026 2:53:51 PM Rough electrical partial inspection approved 1st and 2nd floor wall rough for elevator lobby Marked on plans what was inspected at this time

 09/02/2026B:ROUGH ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request9/1/2026 1:39:54 PM 9/1/2026 1:39 PM Kelly Sherman Underground Light Pole Conduit Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 9/2/2026 2:53:54 PM Underground trench inspection partial approved Under ground 1in pvc from light pole to light pole marked on plans what was inspected

 09/10/2026B:FIRE STOPPING AND PENETRATIONSJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request9/9/2026 10:56:35 PM 9/9/2026 10:56 PM Gordon Galbraith state fire will be on site at 1pm. if inspections can conincide that would be preferable. rated wall penetrations, 1st & 2nd floors Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/10/2026 1:16:06 PM NOT APPROVED- 1) PRE WALK FOR FIRE, STOPPING IN PENETRATIONS.

 09/11/2026B:FIRE STOPPING AND PENETRATIONSJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request9/10/2026 2:07:40 PM 9/10/2026 2:07 PM Gordon Galbraith Rated wall penetrations on 1st & 2nd floor. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/11/2026 2:55:26 PM APPROVED- 1) FIRST FLOOR & SECOND FLOOR - OK.

B:ROUGH ELECTRICALVINCE RAPONEeTRAKiT Inspection Request9/15/2026 2:19:00 PM 9/15/2026 2:19 PM Kelly Sherman Exterior Light Poles - Dan w/Duro Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com

 09/22/2026B:ROUGH ELECTRICALSHAWN VALENZUELAAPPROVEDeTRAKiT Inspection Request9/21/2026 4:01:50 PM 9/21/2026 4:01 PM Kelly Sherman Electrical Light Poles, Elevator Rough, & C&S Ceilings Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 9/22/2026 2:54:37 PM Rough electrical inspection approved Elevator shaft and pit inspection Rough roof top inspection, verify labels and wire size at final Core and shell ceiling complete Core and shell electrical roughs completed

 09/23/2026B:ELECTRICAL TRENCHSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request9/22/2026 3:41:37 PM 9/22/2026 3:41 PM Kelly Sherman There is no udnerground electrical option under inspection type. This inspection is for underground electrical for light pole bases. Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 9/23/2026 10:36:35 AM Electrical trench partial approved Notes 4 landscape lights east front entrance and caissons each light in ground j box. 1 landscape lights south side of building and caissons 1in PVC stub ups into caissons

 09/25/2026B:ROUGH MECHANICALJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request9/24/2026 5:01:22 PM 9/24/2026 5:01 PM Gordon Galbraith Close out both ceiling & walls Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/25/2026 3:09:06 PM RGH MECHANICAL- APPROVED.

 09/25/2026B:FIRE STOPPING AND PENETRATIONSJOE CARBAUGHCANCELeTRAKiT Inspection Request9/24/2026 4:59:59 PM 9/24/2026 4:59 PM Gordon Galbraith Includes visual on fire dampers. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/25/2026 3:09:08 PM CANCELED SPOKE WITH SUPERINTENDENT GORDON GALBRAITH VIA PHONE. CONTRACTOR WILL RE-CALL INSPECTION WHEN READY.

 09/28/2026B:DRYWALLJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request9/27/2026 7:37:14 PM 9/27/2026 7:37 PM Gordon Galbraith Final drywall to sign permit card Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/28/2026 11:58:12 AM APPROVED - WHOLE BUILDING.

 09/29/2026B:ROUGH MECHANICALBRETT LONGNECKERAPPROVEDeTRAKiT Inspection Request9/28/2026 12:11:30 PM 9/28/2026 12:11 PM Gordon Galbraith Fire dampers. Fire AHJ''s will be on site from 12pm - 3pm for visual inspection of all fire dampers. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com

 09/29/2026B:FIRE STOPPING AND PENETRATIONSJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request9/28/2026 12:14:29 PM 9/28/2026 12:14 PM Gordon Galbraith Final for firestopping & penetrations. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/29/2026 3:13:09 PM APPROVED. VERTICAL FIRE-STOP SYSTEM- OK.

 09/29/2026B:FINAL FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/28/2026 12:12:33 PM 9/28/2026 12:12 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/29/2026 3:46:35 PM PARTIAL- FIRE DAMPER TEST- ED LAB 147 , PAT TLT 146, SOILED 145, CLEAN 135, MED PREP 134 - OK. NOTE: REST OF DAMPERS TO BE CHECKED AT FUTURE INSPECTION.

 09/30/2026B:FINAL FRAMEJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request9/29/2026 4:22:48 PM 9/29/2026 4:22 PM Gordon Galbraith CRFD will be on site at 9am to continue fire damper inspection. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 9/30/2026 11:08:14 AM APPROVED- 1) ALL FIRE DAMPERS IN BUILDING HAVE BEEN INSPECTED & APPROVED FROM BUILDING & CASTLE ROCK FIRE.

 10/01/2026B:LATH STONE OR BRICK TIEJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request9/30/2026 2:31:43 PM 9/30/2026 2:31 PM Gordon Galbraith All weather barrier, lath & stone complete. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/1/2026 2:22:52 PM APPROVED.

 10/01/2026B:RE FINAL BUILDINGBRETT LONGNECKERNOT APPROVEDeTRAKiT Inspection Request9/30/2026 4:03:19 PM 9/30/2026 4:03 PM Gordon Galbraith Stocking acceptance pending 1pm fire alarm annunciator panel replacement & inspection by CRFD. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/1/2026 3:58:50 PM Ok FOR STOCK ONLY. NO EMPLOYEES ARE ALLOWED UNTIL A STOCK AND TRAIN HAS BEEN APPROVED BY TOWN OF CASTLE ROCK BUILDING DIVISION AND FIRE LIFE SAFETY DIVISION. THIS INSPECTION WAS ONLY TO VERIFY GENERAL LIFE SAFETY ITEMS FOR STOCKING ONLY. A FULL FINAL BUILDING INSPECTION WILL BE PERFORMED ONCE READY FOR STOCK AND TRAIN AND TCO.

 10/06/2026B:ELECTRICAL TRENCHSHAWN VALENZUELAAPPROVEDeTRAKiT Inspection Request10/5/2026 10:12:53 AM 10/5/2026 10:12 AM Kelly Sherman Underground Electrical Contact Name: Kelly Sherman Site Address: 4141 PLUM CREEK BLVD Phone: 7208549829 e-Mail: ksherman@tcco.com 10/6/2026 10:02:19 AM Electrical trench inspection approved Notes 5 light poles underground inspection 1in pvc north and north east outside of parking lot. Underground for core and shell complete

 10/21/2026B:FINAL ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request10/19/2026 1:47:42 PM 10/19/2026 1:47 PM Gordon Galbraith Generator blackout test with Castle Rock Fire & DFPC at 9AM Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/21/2026 10:42:52 AM Final electrical inspection partial approved Notes Generator black-out test. Verify critical branch circuits switch with generator when normal loss of power is simulated. Verified receptacles, EM lights exit lights. This inspection was scheduled on core and shell permit. Verified these teams on IT side also.

 10/22/2026B:FINAL PLUMBINGMARTIN MAGERSAPPROVEDeTRAKiT Inspection Request10/19/2026 1:57:36 PM 10/19/2026 1:57 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/22/2026 1:46:40 PM All plumbing and gas pipe approved.

 10/22/2026B:FINAL MECHANICALJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request10/19/2026 1:57:10 PM 10/19/2026 1:57 PM Gordon Galbraith Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/22/2026 1:55:12 PM APPROVED. 1) CONTROL WIRING AT EXHAUST FAN FOR A & 4B ROOF TOP. 2) STATIC PRESSURE AT RTU SENSOR. 3) REST OF CORE & SHELL - OK. NOTE: ITEMS ABOVE TO BE CHECKED AT FINAL BUILDING.

 10/22/2026B:FINAL ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request10/19/2026 1:55:44 PM 10/19/2026 1:55 PM Gordon Galbraith Panels & gear, panel schedules, phenolic labels etc etc. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/22/2026 2:57:54 PM Final electrical inspection partial approved for core and shell only Rooms with corrections 1. Facp room 160. Label all blank j box cover plates, data missing bushing and ko fillers 2. Med gas room 190 label blank j box covers 3. Room 150 water entry label j box covers 4. 1st floor data room e140 label all j box covers, disconnect, thermostat incomplete 5. 1st floor ambulance entry missing can light trim controls incomplete 6. Access panel not installed for for sign j box 1st floor elevator lobby 7. 2nd floor room e220 label disconnects, label receptacles, emt missing bushing, have all junction boxes closed Recall inspection when corrections are completed Not inspection at this time Roof top final inspection, exterior site inspection light poles, complete service inspection.

 10/23/2026B:ELECTRICAL SERVICESHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request10/21/2026 11:46:13 AM 10/21/2026 11:46 AM Gordon Galbraith Service inspection. Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 10/26/2026 7:00:51 AM Electrical service inspection not approved 1. Plans show aluminum wire feeding generator currently installed is 3 parallel runs of 4 300 and 1/0 ground in each conduit. Please upload plans showing copper in replacement of aluminum. Recall inspection when corrections are completed Rest of service ok pending revision

 10/23/2026B:FINAL ELECTRICALSHAWN VALENZUELACANCELeTRAKiT Inspection Request10/22/2026 3:43:19 PM 10/22/2026 3:43 PM Gordon Galbraith Roof & any labeling / fixes Dan Castro can get done between now & 10/23 PM Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com

 10/26/2026Z:FNL SITE COMPLIASCOTT SEUBERTAPPROVED10/26/2026 12:48:09 PM approved . waiting sign call for inspections.

 10/26/2026B:FINAL ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request10/21/2026 11:48:21 AM 10/21/2026 11:48 AM Gordon Galbraith Roof & exterior finals. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/26/2026 2:28:30 PM Final electrical inspection partial approved core and shell only Core and shell electrical service has not passed at this time. Final building for core and shell can not be approved until electrical service is approved Notes Roof top core and shell final inspection approved Inside building core and shell approved Outside exterior inspection has not been completed at this time. Schedule inspection when ready.

 10/27/2026B:FINAL ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request10/26/2026 3:03:26 PM 10/26/2026 3:03 PM Gordon Galbraith Final exterior. Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 10/27/2026 3:22:34 PM Final electrical inspection, core, and shell only Generator revision needs to be reviewed and approved by the town of Castlerock before final electrical inspection will be approved Exterior final electrical is approved

 10/27/2026B:ELECTRICAL SERVICESHAWN VALENZUELAAPPROVEDeTRAKiT Inspection Request10/23/2026 3:15:01 PM 10/23/2026 3:15 PM Gordon Galbraith Final, including all fixes noted during other final inspections. Contact Name: Dan Castro Site Address: 4141 PLUM CREEK BLVD Phone: 7205958205 e-Mail: ggalbraith@tcco.com 10/27/2026 3:22:37 PM Electrical service inspection approved All corrections have been completed Generator revision has been uploaded. This has not been reviewed by the town of Castle rock until this revision is reviewed and approved. This will hold up final electrical inspection on Core Shell.

 10/28/2026B:REQUEST TCO REVIEWBUILDING COUNTERCANCELeTRAKiT Inspection Request10/22/2026 7:15:10 PM 10/22/2026 7:15 PM Gordon Galbraith Pending TCO inspections on 10/27 & document upload to eTrakit. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/28/2026 8:07:33 AM The Final Building inspection determines when a TCO or CO can be issued.

 10/27/2026B:FINAL BUILDINGBRETT LONGNECKERINC OK FOR TCOeTRAKiT Inspection Request10/22/2026 7:14:15 PM 10/22/2026 7:14 PM Gordon Galbraith Attempting to get DFPC, Castle Rock Fire, & Castle Rock Building all on site at 2pm for life safety & building TCO final. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/27/2026 3:46:12 PM 1. 1st floor data room fireproofing at beams needs patches from removed fireproofing. 2. Complete final mechanical. 3. Complete final electrical. 4. Compete final fire.

 10/29/2026B:FIRE STOPPING AND PENETRATIONSJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request10/28/2026 2:17:33 PM 10/28/2026 2:17 PM Gordon Galbraith Missed conduit firestopping on 2nd floor. Contact Name: Gordon Galbraith Site Address: 4141 PLUM CREEK BLVD Phone: 3038422415 e-Mail: ggalbraith@tcco.com 10/29/2026 2:32:52 PM NOT APPROVED. NOTE: FIRE STOP FOR CONFERENCE 211 ABOVE GRID TO BE LOOKED AT BUILDING FINAL. REST OF FIRE STOP - OK. FIRE STOP OK FOR TCO.

 11/12/2026B:RE FINAL ELECTRICALSHAWN VALENZUELAAPPROVEDeTRAKiT Inspection Request11/10/2026 12:15:52 PM 11/10/2026 12:15 PM Braden Frey Updated one-line showing change in generator feeder material uploaded to eTrackit. Contact Name: Braden Frey Site Address: 4141 PLUM CREEK BLVD Phone: 3035183298 e-Mail: bmfrey@tcco.com 11/12/2026 11:54:00 AM Final electrical inspection approved All corrections have been completed