| 10/03/2025 | B:UNGRD PLUMB | BRETT LONGNECKER | PARTIAL | Sheet # P113 | 10/2/2025 1:14:00 PM
10/2/2025 1:14 PM FRONT RANGE SEE CR24-0596
Joe 720-341-6598
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
10/3/2025 2:10:24 PM
Underground 4 inch foundation drain for ejector pump in competition storage room. Highlighted in blue on P113. Photo uploaded.
|
|
| 09/30/2025 | B:UNGRD PLUMB | MICHAEL RANKIN | PARTIAL | Detail 2/P500 | 9/29/2025 2:16:47 PM
9/29/2025 2:16 PM FRONT RANGE SEE CR24-0596
Joe- 720-341-6598
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: Stacey@frontrangeplumbing.com
9/30/2025 10:03:23 AM
Partial underground plumbing inspection for 4in foundation drain from ejector pits and 4in pool under drain ok. Highlighted in green detail 2/P500.
|
|
| 09/12/2025 | B:ELECTRICAL TRENCH | JON WHITE | PARTIAL | Temp Service Const Trailer | 9/11/2025 12:46:11 PM
9/11/2025 12:46 PM LAKEWOOD ELECTRIC COMPANY INC
Partial trench inspection for temp power
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
9/12/2025 11:49:05 AM
Partial Underground
- 2" PVC in trench from temp service to Saunders Construction Trailer Temp service. OK to Bury
- (2) 2 1/2" PVC from Temp Service, 100' to east. (Will carry temp power into building). Ok to bury this section
|
|
| 11/14/2025 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 11/13/2025 3:11:41 PM
11/13/2025 3:11 PM LAKEWOOD ELECTRIC COMPANY INC
Outlets in cast-in-place wall
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 3037830600
e-Mail: RECEPTION@LKWD-ELEC.COM
11/14/2025 10:27:58 AM
Area B south wall - 2 receptacle pre cast wall
|
|
| 11/20/2025 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | Duane 720-939-3709 | 11/19/2025 1:27:16 PM
11/19/2025 1:27 PM FRONT RANGE SEE CR24-0596
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: Stacey@frontrangeplumbing.com
11/20/2025 12:11:23 PM
Sump / Sewer underground approved
|
|
| 11/20/2025 | TRAINING_COLBY | COLBY RIGGINS | APPROVED | | |
|
| 11/21/2025 | B:RGH ELECT | VINCE RAPONE | PARTIAL | underground sump pit sleeves | 11/20/2025 1:56:18 PM
11/20/2025 1:56 PM LAKEWOOD ELECTRIC COMPANY INC
Underfloor sump pit conduits
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
11/21/2025 10:42:10 AM
Area B sump pit 4 - 2" pvc conduits good
2 - 2" sleeves to each pit.
|
|
| 12/01/2025 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Gymnasium Cast wall electrical | 11/26/2025 11:44:22 AM
11/26/2025 11:44 AM LAKEWOOD ELECTRIC COMPANY INC
Cast in Place wall rough
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
12/1/2025 2:23:08 PM
Gymnasium Cast wall electrical rough good
Receptacles / fire alarm boxes
|
|
| 12/08/2025 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 12/5/2025 11:47:33 AM
12/5/2025 11:47 AM LAKEWOOD ELECTRIC COMPANY INC
UFER Ground Inspection
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001279
e-Mail: rbinford@lkwd-elec.com
12/8/2025 10:16:39 AM
User ground good
|
|
| 12/09/2025 | B:RGH ELECT | VINCE RAPONE | PARTIAL | pre cast wall rough | 12/8/2025 12:41:19 PM
12/8/2025 12:41 PM LAKEWOOD ELECTRIC COMPANY INC
Are B West Wall Rough
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
12/9/2025 11:17:00 AM
Area b west wall pre cast electrical wall rough good
F/A and WAP
|
|
| 09/10/2025 | PRE CON INSPECTION | BRETT LONGNECKER | APPROVED | Castle Rock Sports Center - Precon | 9/9/2025 7:56:22 AM
9/9/2025 7:56 AM SAUNDERS CONSTRUCTION LLC
Hello, my name is Clay Wagner with Saunders construction. We would like to schedule a preconstruction meeting for the Castle Rock Sports Center Job. Our jobsite trailer is not fully complete yet and our trailer inspection is requested for Thursday morning. So, if it works for you, we can meet at the Town of Castle Rock office for this preconstruction.
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
9/10/2025 8:06:06 AM
Discussed pre con meeting with Clay. Need to reach out to DS construction inspectors and storm water for their pre con meeting.
12/10/2025 9:36:01 AM
Building pre con conducted on 12/10/25 at 8:00 am in Townhall Council Chambers with Josh Combs and Anna Gannon representing Saunders Construction.
|
|
| 12/15/2025 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 12/12/2025 2:40:23 PM
12/12/2025 2:40 PM LAKEWOOD ELECTRIC COMPANY INC
Rough wall inspection for one receptacle outlet, Area B west wall.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
12/15/2025 2:50:51 PM
Receptacle pre cast wall area b good
|
|
| 12/23/2025 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 12/22/2025 12:23:56 PM
12/22/2025 12:23 PM LAKEWOOD ELECTRIC COMPANY INC
Cast-in-place wall rough inspection for 5 devices, Area C West
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
12/23/2025 2:34:34 PM
Pre cast wall rough west side area c good
|
|
| 01/05/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Monolith lighting conduit rough | 1/2/2026 5:49:22 AM
1/2/2026 5:49 AM LAKEWOOD ELECTRIC COMPANY INC
Monolith lighting conduit rough
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
1/5/2026 3:01:25 PM
Stair well low volt lighting sleeves
4 - 1/2" conduits
|
|
| 01/12/2026 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | Duane - 720-939-3709 Onsite contact | 1/9/2026 10:41:03 AM
1/9/2026 10:41 AM FRONT RANGE SEE CR24-0596
Area A Trash Chute
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
1/12/2026 11:19:48 AM
Floor sink in trash shoot approved. Current plans not printed and therefore not high lighted.
|
|
| 01/15/2026 | TRAINING_SHAWN | SHAWN VALENZUELA | PARTIAL | | 1/15/2026 2:38:29 PM
Stairwell a trash room
Stairwell b storage room
|
|
| 01/15/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | SOG, stair A/B, Storage B/SOG | 1/14/2026 1:43:42 PM
1/14/2026 1:43 PM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: RECEPTION@LKWD-ELEC.COM
1/15/2026 3:03:20 PM
Stair A / trash room
Under slab Heater and receptacle pipe good
Stair b and storage under slab pvc good
|
|
| 01/20/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Underground temp power feeder | 1/16/2026 1:30:35 PM
1/16/2026 1:30 PM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
1/20/2026 1:58:52 PM
Temp power trench after road crossing to hill good
|
|
| 01/22/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Temp power UG trench inspection | 1/21/2026 1:22:49 PM
1/21/2026 1:22 PM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001279
e-Mail: rbinford@lkwd-elec.com
1/22/2026 2:04:36 PM
Temp power trench good
Down the hill and across the road south west corner to building good
|
|
| 01/30/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Partial underground duct bank inspection | 1/29/2026 11:07:16 AM
1/29/2026 11:07 AM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
1/30/2026 2:15:02 PM
Under ground - Userk cabinet to electrical room / low volt sleeves
|
|
| 02/11/2026 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 2/10/2026 11:41:31 AM
2/10/2026 11:41 AM FRONT RANGE SEE CR24-0596
Eli 720-201-8763
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: Stacey@frontrangeplumbing.com
2/11/2026 11:44:06 AM
6" and 4"low drains for main locker rooms, ok. Highlight in green. Not connected to back line. Front run through foundation never inspected and back where it runs under large footer. Note all earlier inspections updated in new plans.
|
|
| 02/18/2026 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | Please call ELI 7202018763 when OTW | 2/17/2026 12:52:53 PM
2/17/2026 12:52 PM FRONT RANGE SEE CR24-0596
AM Preferred
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
2/18/2026 12:34:47 PM
Ground pluming at Area A was inspected and on test. See pic at P111.
All ground plumbing up top just before G for the main locker room approved. Drain for urinals was moved to the 4" drain at grid line 11. See pic of P500
|
|
| 02/23/2026 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | AM Preferred | 2/20/2026 7:50:36 AM
2/20/2026 7:50 AM FRONT RANGE SEE CR24-0596
Eli Hulbert 720-201-8763
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
2/23/2026 12:56:29 PM
All ground plumbing through H approved.
|
|
| 02/23/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Partial underslab conduits | 2/20/2026 7:13:31 AM
2/20/2026 7:13 AM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
2/23/2026 2:09:40 PM
Under slab - electrical branch / panel feeders / low volt sleeves good
|
|
| 02/26/2026 | TRAINING_SHAWN | SHAWN VALENZUELA | APPROVED | | 2/26/2026 2:42:57 PM
Training was completed
Underground electrical room
|
|
| 02/26/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Underslab conduit rough | 2/25/2026 12:15:19 PM
2/25/2026 12:15 PM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
2/26/2026 2:47:00 PM
Under slab electrical room good
Ev charger panel
Lighting control panel
High volt panel
|
|
| 03/03/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | Underslab branch conduit rough | 3/2/2026 11:57:52 AM
3/2/2026 11:57 AM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
3/3/2026 8:40:56 AM
Partial underground approved
Branch circuits raceway from electrical room
|
|
| 03/03/2026 | B:UNGRD PLUMB | KEVIN ARENCIBIA | PARTIAL | Storm Drain | 3/2/2026 2:43:15 PM
3/2/2026 2:43 PM FRONT RANGE SEE CR24-0596
underground roof drain area A contact is Eli 720-201-8763
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
3/3/2026 11:42:05 AM
6" storm drain & branch for ORD catch basin at grid A-12 layout & pressure test ok to stub-up; pictures uploaded
|
|
| 03/09/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Slab on grade branch conduit inspection | 3/6/2026 6:36:56 AM
3/6/2026 6:36 AM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
3/9/2026 11:24:51 AM
Area A under slab branch circuit- feeder duct bank pvc good
|
|
| 03/13/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 3/12/2026 2:54:40 PM
3/12/2026 2:54 PM Josh Combs
Rough Frame for Roof Area A
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
3/13/2026 9:47:34 AM
PARAPET ROOF FRAMING AT GRID LINES A LINE & 2 LINE OK.
NOTE: REST OF PARAPET WALL IN BE INSPECTED AT FUTURE INSPECTIONS.
|
|
| 03/20/2026 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | contact Elli 720-201-8763 | 3/20/2026 9:28:11 AM
contact Elli 720-201-8763
3/20/2026 10:28:22 AM
Inspector MAM2 changed the inspection assignment from MAM2 to MAM2
3/20/2026 2:02:22 PM
Groung plumbing drain for mechanical room. Highlighted on P111 and P500.
|
|
| 03/23/2026 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | contact Eli 720-201-8763 | 3/20/2026 8:50:31 AM
3/20/2026 8:50 AM FRONT RANGE SEE CR24-0596
contact Elli 720-201-8763
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
3/23/2026 11:39:13 AM
All ground plumbing in Area B approved and highlighted in green on page P112.
|
|
| 03/24/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | Partial underfloor conduits area B | 3/23/2026 10:08:54 AM
3/23/2026 10:08 AM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
3/24/2026 12:04:12 PM
Under slab conduits - low volt / access control / branch / 1" pvc good
Mezzanine conduits - 3/4 pvc cardio deck conduits good
|
|
| B:RGH MECH | BRETT LONGNECKER | | Underslab electrical area B | 3/25/2026 2:37:32 PM
3/25/2026 2:37 PM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
|
|
| 03/27/2026 | B:RGH ELECT | SHAWN VALENZUELA | CANCEL | Pool equip room underslab. Cardio deck | 3/26/2026 2:54:54 PM
3/26/2026 2:54 PM LAKEWOOD ELECTRIC COMPANY INC
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
3/27/2026 6:44:54 AM
DUPLICATE INSPECTION
|
|
| 03/27/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | contact Eli 720-201-8763 | 3/26/2026 12:38:36 PM
3/26/2026 12:38 PM FRONT RANGE SEE CR24-0596
Eli 720-201-8763 area locker room
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
3/27/2026 8:56:13 AM
Cabana and shower in wall plumbing ok up to 5 ft for first lift of block.
|
|
| 03/27/2026 | B:RGH ELECT | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 3/26/2026 2:57:26 PM
3/26/2026 2:57 PM LAKEWOOD ELECTRIC COMPANY INC
Pool equip room SOG. Cardio deck lighting SOG
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
3/27/2026 2:32:31 PM
Did not look at pool equipment room not ready
Cardio deck lighting good ( see photo)
Underground in area b under mezzanine good ( see photo)
|
|
| 03/30/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | Roof insulation Area A | 3/27/2026 11:28:31 AM
3/27/2026 11:28 AM Josh Combs
Can be at the same time as Rough Frame Area B
Contact Name: Clay Wagner
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
3/30/2026 11:07:56 AM
PARTIAL- ROOF INSULATION AREA - A DENS DECK, (2) LAYERS OF RIDGED INSULATION-OK.
|
|
| 03/30/2026 | B:RGH FRAME | JOE CARBAUGH | NOT APPROVED | Cold Formed Area B Roof | 3/27/2026 11:23:28 AM
3/27/2026 11:23 AM Josh Combs
Contact Name: Clay Wagner
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
3/30/2026 11:07:58 AM
NOT APPROVED -
MISSING SCREWS TO COLD FORMED STEEL FOR SCREW SCHEDULE / ROOF / WALL FRAMING BETWEEN AREA A & B / ON PAGE C2 LEFT OF PAGE UNDER APPROVED FASTENERS.
NOTE: RECALL INSPECTION WHEN ITEMS HAVE BEEN CORRECTED.
|
|
| 03/30/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 3/27/2026 2:39:21 PM
3/27/2026 2:39 PM LAKEWOOD ELECTRIC COMPANY INC
Area B to C underslab conduits. Pool equipment room underslab conduits.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
3/30/2026 3:28:14 PM
Pool equipment room under slab good
|
|
| 03/31/2026 | B:RGH PLUMB | BRETT LONGNECKER | PARTIAL | In wall only locker rooms | 3/30/2026 4:01:29 PM
3/30/2026 4:01 PM FRONT RANGE SEE CR24-0596
locker rooms
Contact Name: Front Range Plumbing Co inc
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
3/31/2026 11:39:11 AM
All in wall rough for DWV and water ok to conceal in locker room as shown on 3/P500.
|
|
| 04/09/2026 | B:UNGRD PLUMB | BRETT LONGNECKER | PARTIAL | Underground for Area C | 4/8/2026 7:54:19 AM
4/8/2026 7:54 AM FRONT RANGE SEE CR24-0596
Am Preferred for Area C
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
4/9/2026 9:51:18 AM
Area C underground DWV ok as highlighted on 3/501 in blue.
|
|
| 04/09/2026 | B:ELECTRICAL TRENCH | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 4/8/2026 2:05:06 PM
4/8/2026 2:05 PM LAKEWOOD ELECTRIC COMPANY INC
Service entrance duct bank and site feeders trench
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
4/9/2026 2:15:44 PM
Transformer to userk under ground approved
Low volt sleeves
Lighting and EV branch
|
|
| 04/10/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 4/9/2026 12:40:06 PM
4/9/2026 12:40 PM LAKEWOOD ELECTRIC COMPANY INC
Underslab rough, area B
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
4/10/2026 2:18:12 PM
Pool wall to aerobics under ground electrical good
Power and FA
|
|
| 04/14/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | Area B roof insulation | 4/13/2026 10:04:23 AM
4/13/2026 10:04 AM Josh Combs
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
4/14/2026 11:12:05 AM
PARTIAL-
1) BATT INSULATION / RIDGED FOAM INSULATION & ATTACHMENT SCHEDULE- OK FOR ROOF AREA (B).
|
|
| 04/16/2026 | B:RGH ELECT | VINCE RAPONE | CANCEL | eTRAKiT Inspection Request | 4/15/2026 12:48:09 PM
4/15/2026 12:48 PM LAKEWOOD ELECTRIC COMPANY INC
Partial program pool bonding
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
4/16/2026 11:09:09 AM
Cancel per Rodger
Reschedule
|
|
| 04/17/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | pool bonding | 4/16/2026 9:40:05 AM
4/16/2026 9:40 AM LAKEWOOD ELECTRIC COMPANY INC
Partial program pool bonding inspection
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
4/16/2026 9:41:33 AM
4/16/2026 9:41 AM LAKEWOOD ELECTRIC COMPANY INC
Partial program pool bonding
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
4/17/2026 1:46:38 PM
Pool bonding
Handicap ramp / upper portion of kiddie pool
|
|
| 04/17/2026 | B:RGH FRAME | JOE CARBAUGH | PARTIAL | Framing Mech Wells High Roof | 4/16/2026 2:52:35 PM
4/16/2026 2:52 PM Josh Combs
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
4/17/2026 3:03:06 PM
PARTIAL-
1) RGH FRAME - ROOF TOP HEAD OF WALL ATTACHMENT & FULL FRAME WALL INSPECTION FOR AREA
|
|
| 04/24/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 4/23/2026 2:46:30 PM
4/23/2026 2:46 PM LAKEWOOD ELECTRIC COMPANY INC
Area C lover level UG conduits. Area C lighting rough at track.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
4/24/2026 1:22:02 PM
Area C upper track slab PVC - lights
Area C lower underground slab branch pvc
|
|
| 04/28/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 4/27/2026 2:02:57 PM
4/27/2026 2:02 PM LAKEWOOD ELECTRIC COMPANY INC
underslab conduit inspection area C north.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
4/28/2026 1:38:41 PM
Area C north under slab branch pvc - bathrooms - storage area
|
|
| 04/29/2026 | B:RGH PLUMB | MARTIN MAGERS | PARTIAL | REQUEST AM | 4/28/2026 10:58:18 AM
4/28/2026 10:58 AM FRONT RANGE SEE CR24-0596
Rough plumb inspection for Area A - Mezzanine Eli 720-201-8763 site contact
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
4/29/2026 2:03:15 PM
Storm Drain, DWV, Water for Mezzanine Area A all ok except stair A roof drain and penetration and water heater Flues. Storm drains stumbled through wall North and NE corner P114. See P121 p501 and P 500 marked in purple. See pictures.
|
|
| 04/29/2026 | B:RGH ELECT | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 4/28/2026 2:52:06 PM
4/28/2026 2:52 PM LAKEWOOD ELECTRIC COMPANY INC
Area C north storage room and janitor closet under slab conduits
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
4/29/2026 2:53:16 PM
Under slab pvc - janitor and storage room area - c
|
|
| 05/05/2026 | B:RE ROUGH ELECTRICAL | VINCE RAPONE | CANCEL | eTRAKiT Inspection Request | 5/4/2026 9:48:22 AM
5/4/2026 9:48 AM LAKEWOOD ELECTRIC COMPANY INC
Elevated track area B lighting rough. Temporary service underground conduits.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
5/5/2026 11:13:58 AM
Cancel per Rodger
|
|
| 05/12/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 5/11/2026 8:50:01 AM
5/11/2026 8:50 AM LAKEWOOD ELECTRIC COMPANY INC
Slab on deck conduit for area B elevated track.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
5/12/2026 12:17:46 PM
Area B elevated deck approved
Lights
|
|
| 05/13/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | Roof Insulation | 5/12/2026 8:03:44 AM
5/12/2026 8:03 AM Josh Combs
This inspection is for roof insulation. I don''t see insulation listed in the drop down menu
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
5/13/2026 1:29:08 PM
PARTIAL-
1) 2 LAYERS OF ROOF RIDGED FOAM INSULATION AREA A EAST HIGH ROOF- OK.
|
|
| 05/18/2026 | B:INSULATION | JOE CARBAUGH | CANCEL | Roof insulation | 5/15/2026 9:37:28 AM
5/15/2026 9:37 AM Josh Combs
This is for building and roof insulation. I don''t see insulation listed in the drop down menu
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
5/18/2026 12:09:19 PM
CANCELED - BY SUPERINTENDENT JOSH COMBS.
|
|
| 05/22/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | Roof and Wall Insulation | 5/21/2026 8:14:07 AM
5/21/2026 8:14 AM Josh Combs
Roof and Exterior wall insulation
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
5/22/2026 11:37:18 AM
PARTIAL-
1) HIGH ROOF AREA A & D
2) HIGH ROOF WALL PLAN NORTH & HIGH ROOF PLAN B AREA WALL SOUTH- OK.
|
|
| 05/22/2026 | B:RE ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 5/21/2026 12:33:40 PM
5/21/2026 12:33 PM LAKEWOOD ELECTRIC COMPANY INC
Temporary service UG conduit inspection. East side of bldg.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
5/22/2026 12:04:59 PM
Temp service underground pvc approved
2 - 2-1/2" pvc to disconnect to transformer
|
|
| 05/26/2026 | B:GROUND PLUMBING | MARTIN MAGERS | NOT APPROVED | UG Sanitary Tie in | 5/21/2026 8:42:06 AM
5/21/2026 8:42 AM Josh Combs
UG Sanitary Ties
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
5/26/2026 11:36:23 AM
Tie in not complete.
|
|
| 06/02/2026 | B:INSULATION | MARTIN MAGERS | CANCEL | Roof Insualtion | 6/1/2026 8:08:25 AM
6/1/2026 8:08 AM Josh Combs
This is for roof insulation. Insulation isnt listed on the drop down
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
6/2/2026 7:32:47 AM
CANCEL-
NOTE: CONTRACTOR CANCELED INSPECTION AND HAS INSULATION INSPECTION FOR 06/04/26.
|
|
| 06/02/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 6/1/2026 2:17:19 PM
6/1/2026 2:17 PM LAKEWOOD ELECTRIC COMPANY INC
Elevated track in-slab lighting rough.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 3038827140
e-Mail: rbinford@lkwd-elec.com
6/2/2026 12:04:20 PM
Elevated track deck approved
Lighting pvc
|
|
| 06/02/2026 | B:ELECTRICAL TEMPORARY CONSTRUCTION METER | VINCE RAPONE | NOT APPROVED | eTRAKiT Inspection Request | 6/1/2026 2:16:06 PM
6/1/2026 2:16 PM LAKEWOOD ELECTRIC COMPANY INC
Temporary service inspection.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
6/2/2026 12:04:30 PM
Need CT's installed before meter release
Need 400A fuses
Reschedule
|
|
| 06/03/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 6/2/2026 12:55:44 PM
6/2/2026 12:55 PM LAKEWOOD ELECTRIC COMPANY INC
Program pool bonding
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
6/3/2026 2:05:40 PM
Bonding for 11 - niche lights in program pool approved
|
|
| 06/04/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | area D underslab | 6/3/2026 6:49:30 AM
6/3/2026 6:49 AM LAKEWOOD ELECTRIC COMPANY INC
Underslab conduits area D
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
6/4/2026 1:51:29 PM
Underslab electrical rough area D trunk line to storage room only
Branch pvc
|
|
| 06/04/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 6/1/2026 8:08:57 AM
6/1/2026 8:08 AM Josh Combs
This is for roof insulation. Insulation isnt listed on the drop down
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
6/4/2026 2:26:59 PM
PARTIAL-
1) 2" RIDGE FOAM ROOF INSULATION x 3 - / GRID 9 THROUGH 13 , Z THROUGH S & S THROUGH K - OK.
|
|
| 06/08/2026 | B:ELECTRICAL TEMPORARY CONSTRUCTION METER | VINCE RAPONE | APPROVED | eTRAKiT Inspection Request | 6/5/2026 10:34:00 AM
6/5/2026 10:34 AM LAKEWOOD ELECTRIC COMPANY INC
Temp Service Inspection
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
6/8/2026 10:35:47 AM
Temp meter approved
Okay to release meter
|
|
| 06/08/2026 | B:GROUND PLUMBING | MARTIN MAGERS | PARTIAL | On-site Contact is Eli 7202018763 | 6/5/2026 7:19:18 AM
6/5/2026 7:19 AM FRONT RANGE SEE CR24-0596
Underground Inspection
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
6/8/2026 12:31:36 PM
Deck drain for warm up pool. Marked in green on P111.
|
|
| 06/08/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | On-site contact is Eli - 7202018763 | 6/5/2026 7:13:50 AM
6/5/2026 7:13 AM FRONT RANGE SEE CR24-0596
Rough-in for Overhead DWV/RD & Water heater flues
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
6/8/2026 12:31:41 PM
Storm drains as marked in green on page P111,
DWV as marked in pink on page P112
Storm drains in green and vent in pink on page P122.
DWV for cabana and locker room as marked in pink on page P500
Mezz level B restrooms DWV as marked in pink on P501.
Exhaust and intake for water heater as marked in pink on M111 and M121 on second floor.
|
|
| 06/10/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | Program Pool Piping | 6/9/2026 8:25:58 AM
6/9/2026 8:25 AM SAUNDERS CONSTRUCTION LLC
Will have pressure per specs on the pipes for inspection
Contact Name: SAUNDERS/ASSOCIATED POOL BUILDERS
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
6/10/2026 12:50:06 PM
All pool drain and return approved. Main drain buried past line marked on plans. It was under pressure and engineers third party letter supplied.
|
|
| 06/11/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | under slab area d | 6/10/2026 12:18:34 PM
6/10/2026 12:18 PM LAKEWOOD ELECTRIC COMPANY INC
Area D perimeter underslab branch conduits
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
6/11/2026 12:22:29 PM
Under slab rough electrical approved
Area d - east and north wall
|
|
| 06/12/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Exterior Framing and Insulation | 6/10/2026 7:38:33 AM
6/10/2026 7:38 AM Josh Combs
Exterior Framing and Insulation
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
6/12/2026 1:59:41 PM
PARTIAL-
1) FRAMING FOR SOUTH ENTRANCE AREA B , GRID Line 2 K-H - OK.
|
|
| 06/15/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 6/12/2026 7:30:24 AM
6/12/2026 7:30 AM FRONT RANGE SEE CR24-0596
FRIDAY 6/12/26 if possible please
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
6/15/2026 11:36:22 AM
Roof drains as marked in green on pg 122 and 3/4 water line to hydrant marked in orange on pg 122
Water at B Mezzanine restroom approved as marked in blue on page P501
Bottom drains for to main pool as outlined in pink on page PL310
|
|
| 06/17/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 6/16/2026 12:54:05 PM
6/16/2026 12:54 PM LAKEWOOD ELECTRIC COMPANY INC
Competition pool bonding upper level
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
6/17/2026 3:09:03 PM
Pool bonding shallow end and waiting stairs of competition pool approved
|
|
| 06/18/2026 | B:ROUGH FRAME | JOE CARBAUGH | NOT APPROVED | rough frame for above ceiling top out | 6/17/2026 6:37:32 AM
6/17/2026 6:37 AM SAUNDERS CONSTRUCTION LLC
rough frame for above ceiling top out
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
6/18/2026 11:59:53 AM
NOT APPROVED-
1) HEAD OF WALL FRAME & SPRAY FOAM INSULATION AT MEZZANINE AREA (A) HIGHLIGHTED AREA IN BLUE ON PLANS AND PHOTO ATTACHMENT- OK.
2) HEAD OF WALL FRAME & SPRAY FOAM INSULATION AT MEZZANINE AREA (A) HIGHLIGHTED AREA IN PURPLE
ON PLANS AND PHOTO ATTACHMENT- NOT APPROVED.
NOTE: NEED CLARIFICATION FROM A COLORADO DESIGN PROFESSIONAL FOR TOP OF FRAME WALL FOR USING SLOTTED TRAC VERSES PLAN.
|
|
| 06/18/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | underslab north storage | 6/17/2026 2:07:07 PM
6/17/2026 2:07 PM LAKEWOOD ELECTRIC COMPANY INC
Underground rough area north nprth storage room
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
6/18/2026 1:48:38 PM
North area storage underground approved
Site lighting stubs out of building
|
|
| 06/18/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | competition pool bonding | 6/16/2026 12:55:10 PM
6/16/2026 12:55 PM LAKEWOOD ELECTRIC COMPANY INC
Competition pool bonding lower level
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 719001297
e-Mail: rbinford@lkwd-elec.com
6/18/2026 1:48:43 PM
Competition pool bonding approved - foundation
|
|
| 06/22/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | Area D - Roof Insulation | 6/18/2026 10:03:54 AM
6/18/2026 10:03 AM SAUNDERS CONSTRUCTION LLC
Insulation Verification
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
6/22/2026 11:43:52 AM
PARTIAL-
1) WEST MEC WELL HIGH ROOF WALL AREA THERMAX INSULATION & Z CLIPS - OK.
2) EAST MEC WELL HIGH ROOF AREA (D) THERMAX INSULATION & Z CLIPS - OK.
3) AREA (D) ROOF RIDGED FOAM INSULATION TWO LAYERS 2" & DENS DECK -OK.
|
|
| 06/22/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Area B - Head of Wall | 6/18/2026 10:02:37 AM
6/18/2026 10:02 AM SAUNDERS CONSTRUCTION LLC
Head of Wall inspection to release for drywall top out
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
6/22/2026 11:43:56 AM
PARTIAL-
1) HEAD OF WALL FRAMING SECOND FLOOR AREA (B) -OK.
2) ELEVATOR SHAFT (INNER) UL415 1" R1319-301 TYPE SLX SHAFT LINNER, FRAMING & WEB STIFFENERS - OK.
|
|
| 06/22/2026 | B:RE ROUGH FRAME | JOE CARBAUGH | PARTIAL | Area A - Head of Wall | 6/18/2026 10:01:46 AM
6/18/2026 10:01 AM SAUNDERS CONSTRUCTION LLC
Reinspection from Joe''s 6/18 inspection on (1) run of W1060 wall.
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
6/22/2026 11:44:01 AM
PARTIAL-
1) HEAD OF WALL AREA (A) ITEMS CORRECTED - OK.
|
|
| 06/23/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | High Roof Drains in Areas B & C | 6/22/2026 9:17:47 AM
6/22/2026 9:17 AM FRONT RANGE SEE CR24-0596
Rough Plumbing for Areas B & C High roof drains
ETA Eli - 720-201-8763
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
6/23/2026 10:25:24 AM
Storm drains Area B marked in pink on P122.
Storm drains for Area C marked in Pink on P123
|
|
| 06/26/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | wall rough mezzanine A&B | 6/23/2026 12:56:59 PM
6/23/2026 12:56 PM LAKEWOOD ELECTRIC COMPANY INC
Partial wall rough inspection, mezzanine level areas A & B
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
6/26/2026 11:28:16 AM
Electrical wall rough in the mezzanine area A&B approved
|
|
| 07/01/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 6/30/2026 11:00:05 AM
6/30/2026 11:00 AM FRONT RANGE SEE CR24-0596
inwall insulation inspection for tomorrow. Mezzanine level.
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
7/1/2026 11:48:13 AM
Future grease approved as highlighted in green on P111.
Area A An Area B mezzanine walls approved for pipe insulation.
|
|
| 07/02/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 7/1/2026 12:25:43 PM
7/1/2026 12:25 PM LAKEWOOD ELECTRIC COMPANY INC
Underground data conduits, east side of building.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com.
7/2/2026 12:29:30 PM
Low volt sleeves along east side approved
2 - 4" pvc
1 - 2" pvc
|
|
| 07/02/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Roof Insulation | 6/30/2026 2:04:47 PM
6/30/2026 2:04 PM Josh Combs
Roof Insulation
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
7/2/2026 12:34:21 PM
PARTIAL-
1) ROOF INSULATION PART OF THERMAL ENVELOPE GRID LINES 20-22 & H - Z -OK.
|
|
| 07/09/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | contact Eli 720-201-8763 | 7/8/2026 1:11:41 PM
7/8/2026 1:11 PM FRONT RANGE SEE CR24-0596
locker room
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
7/9/2026 12:34:52 PM
Water and gas approved as marked in pink on P111. And P500. All Area A locker Room approved for water test, DWV and Gas. Still needs insulation.
|
|
| 07/09/2026 | B:ROUGH MECHANICAL | MARTIN MAGERS | PARTIAL | Angelo Nieto - 720 - 584 - 6884 | 7/8/2026 12:20:53 PM
7/8/2026 12:20 PM ATEK HEATING & AIR CONDITIONING
AREA A Level 1
Contact Name: Angelo Nieto
Site Address: 222 BRICKYARD CIR
Phone: 7205846884
e-Mail: m.crespin@atekhtg.com
7/9/2026 12:34:58 PM
All duct work installed and sealed 9-13 H-D as shown on M111.
|
|
| 07/14/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 7/13/2026 12:39:13 PM
7/13/2026 12:39 PM FRONT RANGE SEE CR24-0596
overhead roof drain inspection area B
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
7/14/2026 11:02:33 AM
Roof and secondary drains on 1sr floor, Area B approved.
|
|
| B:FINAL ELECTRICAL | VINCE RAPONE | | eTRAKiT Inspection Request | 7/15/2026 11:13:02 AM
7/15/2026 11:13 AM SAUNDERS CONSTRUCTION LLC
Cabana D Ceiling Electrical
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 7194018401
e-Mail: t.woodard@saundersnorwood.com
|
|
| 07/16/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | Roof Insulation | 7/15/2026 6:43:58 AM
7/15/2026 6:43 AM Josh Combs
This is for roof insulation. Building insulation isn''t listed on the drop down.
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
7/16/2026 2:34:39 PM
PARTIAL-
1) ROOF INSULATION AT AREA B - OK. GRID LINES 0.5 THROUGH 2.
|
|
| 07/16/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 7/15/2026 11:50:59 AM
7/15/2026 11:50 AM LAKEWOOD ELECTRIC COMPANY INC
Site electrical underground
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
7/16/2026 2:42:37 PM
Electrical trench east side approved to EV chargers Site lighting location
4 - EV chargers
Site lighting conduit
2 - 2" pvc security pipes
|
|
| 07/17/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 7/15/2026 11:13:01 AM
7/15/2026 11:13 AM SAUNDERS CONSTRUCTION LLC
Cabana D Ceiling Electrical
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 7194018401
e-Mail: t.woodard@saundersnorwood.com
7/17/2026 6:38:41 AM
CBO CHANGED INSPECTION TYPE FROM FINAL TO ROUGH
7/17/2026 10:59:15 AM
Rough plumbing with insulation approved in ceiling of cabana D.
|
|
| 07/17/2026 | B:GAS PIPE AIR TEST | MARTIN MAGERS | CANCEL | | 7/17/2026 10:59:20 AM
Consult on setting meter. Asked them to contact Black Hills.
|
|
| 07/17/2026 | B:ROUGH MECHANICAL | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 7/15/2026 11:13:01 AM
7/15/2026 11:13 AM SAUNDERS CONSTRUCTION LLC
Cabana D Ceiling Electrical
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 7194018401
e-Mail: t.woodard@saundersnorwood.com
7/17/2026 6:38:23 AM
CBO CHANGED INSPECTION TYPE FROM FINAL TO ROUGH
7/17/2026 10:35:41 AM
Inspector JOCA changed the inspection assignment from JOCA to MAM2
7/17/2026 11:26:46 AM
Shafts at 11-F and 11D duct and seal approved.
Ducts in ceiling of Cabana D approved
7/20/2026 8:07:39 AM
Shafts at 11-F and 11D duct and seal approved.
Ducts in ceiling of Cabana D approved check if exhaust fan is needed.
|
|
| 07/17/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 7/16/2026 11:00:45 AM
7/16/2026 11:00 AM LAKEWOOD ELECTRIC COMPANY INC
Partial ceiling rough inspection, Cabana D
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd.elec.com
7/17/2026 2:54:14 PM
Cabana D - rough electrical approved ( for moc up )
Ex fan in cabana ? Nothing installed at time of inspection print does not show one. Cabana has shower toilet and sink
|
|
| 07/20/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | underground electrical | 7/16/2026 9:43:57 AM
7/16/2026 9:43 AM LAKEWOOD ELECTRIC COMPANY INC
Underground site inspection
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
7/20/2026 11:32:33 AM
Partial trench past road crossing up to EV charger bank okay to backfill
|
|
| 07/21/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | Exterior Wall insulation at Metal Panel | 7/20/2026 8:05:23 AM
7/20/2026 8:05 AM Josh Combs
Exterior Wall insulation at Metal Panel. Building insulation isn''t listed on thedrop down menu
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
7/21/2026 10:32:24 AM
PARTIAL-
1) THERMAL MAX RIDGED INSULATION- OK.
2) Z TRACK AT 16INCH O.C. & 4" TAP CONS FOR CONCRETE ATTACHMENT- OK
AREA C GRID LINE H THROUGH GRID LINE X EXTERIOR WALL RIDGED INSULATION- OK.
3) AREA D HIGH ROOF GRIDLINE 18 THROUGH 20 - OK .
|
|
| 07/21/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | Light Pole Conduit | 7/20/2026 3:09:33 PM
7/20/2026 3:09 PM Josh Combs
This inspection is for the conduit installed in the light pole bases.
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
7/21/2026 3:30:58 PM
Light pole caissons approved - bonding and pvc sleeves
21 total
|
|
| 07/22/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Exterior Frame | 7/21/2026 12:26:45 PM
7/21/2026 12:26 PM Josh Combs
Exterior Frame Canopy
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
7/22/2026 11:04:21 AM
PARTIAL +
1) RGH FRAME FOR NORTH & SOUTH ENTRANCE LIDS/COVERS - OK.
|
|
| 07/22/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | Remaining 3 light pole bases | 7/21/2026 3:42:14 PM
7/21/2026 3:42 PM Josh Combs
Inspection for the 3 light pole bases that weren''t ready at time of inspection
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
7/22/2026 1:43:06 PM
3 light pole bases approved west side of building
|
|
| 07/23/2026 | B:ROUGH FRAME | JOE CARBAUGH | NOT APPROVED | eTRAKiT Inspection Request | 7/22/2026 2:08:00 PM
7/22/2026 2:08 PM SAUNDERS CONSTRUCTION LLC
Level 1 Area B, Mezz Level Area A, Mezz Level Area B
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
7/23/2026 10:04:01 AM
NOT APPROVED-
1) NEED CLARIFICATION FROM A COLORADO DESIGN PROFESSIONAL ON MECHANICAL WALL CONNECTION FOR W1061 GRID LINES A THROUGH F.5.
2) NEED CLARIFICATION FROM A COLORADO DESIGN PROFESSIONAL ON MECHANICAL WALL CONNECTION FOR W1061 GRID LINES Y THROUGH L.
3) RGH FRAMING IN PINK HIGHLIGHTED AREA's PER PIC ATTACHMENT FOR AREA B PLAN A112 - ****OK EXCEPT WALL AT GRID LINES 9- 12.5****
4) REST OF RGH FRAME FOR HIGHLIGHTED AREAS- OK.
|
|
| 07/23/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 7/22/2026 2:04:13 PM
7/22/2026 2:04 PM FRONT RANGE SEE CR24-0596
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
7/23/2026 11:25:18 AM
Areas and Area C water supply, recirculater and pool make up as as out lined in orange on P113 and PP112.
|
|
| 08/04/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 8/3/2026 9:14:12 AM
8/3/2026 9:14 AM LAKEWOOD ELECTRIC COMPANY INC
Site lighting branch underground
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
8/4/2026 11:27:14 AM
South side of building - EV chargers to west corner approved
2 - 2" pvc security
1 - 1" site lighting
|
|
| 08/04/2026 | B:ROUGH FRAME | MARTIN MAGERS | PARTIAL | Ceiling frame in locker room | 7/31/2026 8:14:07 AM
7/31/2026 8:14 AM SAUNDERS CONSTRUCTION LLC
Ceiling frame in locker room
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: C.wagner@saundersinc.com
8/4/2026 2:17:04 PM
Hall in front of cabanas and cabana B and C ceiling framing approved. Marked in green stripes.
8/4/2026 2:21:00 PM
Hall in front of cabanas and cabana B and C ceiling framing approved. Marked in green stripes.
|
|
| 08/05/2026 | B:RE ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | Rough plumbing inspection areas C&D | 8/4/2026 11:03:25 AM
8/4/2026 11:03 AM FRONT RANGE SEE CR24-0596
Contact Eli 720-201-8763
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
8/5/2026 11:21:53 AM
Water, DWV, gas, and drains marked in water orange, gas gree, DWV yellow and roof drains in pink on pages P113, P114, P124 and PP154
All area C restrooms approved for water ,DWV, and gas see page P501.
|
|
| 08/05/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 8/4/2026 11:33:50 AM
8/4/2026 11:33 AM LAKEWOOD ELECTRIC COMPANY INC
Partial site underground inspection
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
8/5/2026 2:25:44 PM
Under ground trench
1" pvc - Tie in 4 pole lights west side
2 - 2" pvc control pipes
|
|
| 08/06/2026 | B:DRYWALL | BRETT LONGNECKER | CANCEL | Screw on ramp scaffold area | 8/5/2026 10:49:00 AM
8/5/2026 10:49 AM SAUNDERS CONSTRUCTION LLC
Screw on ramp scaffold area
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: C.wagner@saundersinc.com
8/6/2026 9:24:31 AM
Canceled per conversation with Clay.
Drywall inspections are only required for fire rated assemblies.
|
|
| 08/07/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 8/6/2026 4:37:46 PM
8/6/2026 4:37 PM LAKEWOOD ELECTRIC COMPANY INC
Underground site lighting branch, west side
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
8/7/2026 2:39:02 PM
Site lighting underground electrical trench west side light poles
2 - 2" pvc conduits for security
1 - 1" pvc light poles
|
|
| 08/07/2026 | B:ROUGH FRAME | MARTIN MAGERS | PARTIAL | Mezz area B elevator shaft | 8/6/2026 10:27:03 AM
8/6/2026 10:27 AM SAUNDERS CONSTRUCTION LLC
Elevator B mezz shaft frame
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 7194018401
e-Mail: T.Woodard@saundersnorwood.com
8/10/2026 7:07:12 AM
Inspected Framing on 2 nd floor Elevator B. first floor was inspected 6/22 by JC.
|
|
| 08/11/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | ceiling frame in locker room | 8/10/2026 12:10:22 PM
8/10/2026 12:10 PM SAUNDERS CONSTRUCTION LLC
ceiling frame in locker room
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
8/11/2026 1:53:35 PM
PARTIAL-
1) FIRST FLOOR AREA (A) CEILIG FRAMING HIGHLIGHTED IN PINK - OK PG A211
|
|
| 08/11/2026 | B:ELECTRICAL TRENCH | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 8/7/2026 12:33:03 PM
8/7/2026 12:33 PM LAKEWOOD ELECTRIC COMPANY INC
Underground site lighting branch conduit, west side
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd.elec.com
8/11/2026 2:17:24 PM
Underground trench approved
West side to light pole on north west corner
|
|
| 08/11/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | locker room | 8/4/2026 11:35:22 AM
8/4/2026 11:35 AM LAKEWOOD ELECTRIC COMPANY INC
Partial above ceiling @ locker rooms
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
8/11/2026 2:17:27 PM
Rough electrical hard lid - 1st floor locker rooms and cabanas approved
Walls approved - locker rooms - 1st floor bathrooms
|
|
| 08/12/2026 | B:ROUGH FRAME | MARTIN MAGERS | PARTIAL | Restroom 161 and 162 frame | 8/11/2026 2:53:00 PM
8/11/2026 2:53 PM SAUNDERS CONSTRUCTION LLC
Restroom 161 and 162 frame
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 7194018401
e-Mail: t.woodard@saundersnorwood.com
8/12/2026 2:09:10 PM
Area A bathrooms framing approved. See A601 marked in pink.
|
|
| 08/13/2026 | B:RE ROUGH MECHANICAL | BRETT LONGNECKER | PARTIAL | mezzanine hvac plan area a | 8/12/2026 12:29:55 PM
8/12/2026 12:29 PM ATEK HEATING & AIR CONDITIONING
Please contact Angelo Nieto prior to arriving
Contact Name: Angelo Nieto
Site Address: 222 BRICKYARD CIR
Phone: 7205846884
e-Mail: m.crespin@atekhtg.com
8/13/2026 1:34:18 PM
Rough mechanical ok as highlighted in blue on town approved M121. Photo Uploaded to permit.
|
|
| 08/13/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 8/13/2026 6:08:20 AM
8/13/2026 6:08 AM LAKEWOOD ELECTRIC COMPANY INC
Partial pool bonding @ competition pool
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
8/13/2026 2:45:56 PM
Pool bonding comp pool okay
Middle trench okay to back fill
|
|
| 08/14/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | Natatorium piping inspection | 8/12/2026 3:25:33 PM
8/12/2026 3:25 PM SAUNDERS CONSTRUCTION LLC
Inlet pipes, gutter dropouts, & main drain.
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3038032820
e-Mail: d.wuthrich@saundersinc.com
8/14/2026 2:58:57 PM
8" main drain from pump pit back to program pool connection , program pool already inspected.
10" gutter drop out for program pool, from program pool to surge tank.
8/14/2026 3:02:31 PM
8%34 main drain from pump pit back to program pool connection , program pool already inspected.
10%34 gutter drop out for program pool, from program pool to surge tank. Approved
|
|
| 07/29/2026 | B:INSULATION | JOE CARBAUGH | PARTIAL | Exterior Wall Insulation | 7/27/2026 10:50:04 AM
7/27/2026 10:50 AM SAUNDERS CONSTRUCTION LLC
Exterior Wall Insulation
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 7209556936
e-Mail: j.orozco@saundersinc.com
7/29/2026 9:28:54 AM
PARTIAL-
1) EXTERIOR RIDGED FOAM INSULATION AT NORTH ENTRANCE CANOPY- OK.
|
|
| 07/20/2026 | B:ROUGH FRAME | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 7/15/2026 11:13:01 AM
7/15/2026 11:13 AM SAUNDERS CONSTRUCTION LLC
Cabana D Ceiling Electrical
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 7194018401
e-Mail: t.woodard@saundersnorwood.com
7/17/2026 5:33:05 AM
7/17/2026 5:33 AM SAUNDERS CONSTRUCTION LLC
Cabana D ceiling framing before cement board
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: C.wagner@saundersinc.com
7/17/2026 6:38:00 AM
CBO CHANGED INSPECTION TYPE FROM FINAL TO ROUGH
7/20/2026 8:51:28 AM
Inspector JOCA changed the inspection assignment from JOCA to MAM2
7/20/2026 2:39:46 PM
cabana D ceiling approved.
No plans on site to mark.
|
|
| 05/29/2026 | B:ROUGH FRAME | MARTIN MAGERS | PARTIAL | Insulation and Framing | 5/27/2026 6:59:51 AM
5/27/2026 6:59 AM Josh Combs
Exterior Insulation and Framing
Contact Name: Josh Combs
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: j.combs@saundersinc.com
5/29/2026 1:10:30 PM
Area C High Roof Wall 2" insulation and Z clips. Marked in green on on A103.
|
|
| 08/17/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Rough Frame for Area A, B Level 1/Mezz | 8/14/2026 9:45:36 AM
8/14/2026 9:45 AM SAUNDERS CONSTRUCTION LLC
Level #1 area A bathrooms walls
Level #1 area B east side wall on court 5,6
Mezzanine area A room 265 and 261
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 7194018401
e-Mail: t.woodard@saundersnorwood.com
8/17/2026 1:24:26 PM
PARTIAL-
1) COLD FORM STEEL WALL RGH FRAME / GRID LINE (P) 2- 9 - OK.
|
|
| 08/18/2026 | B:UNGRD PLUMB | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 8/17/2026 9:27:23 AM
8/17/2026 9:27 AM SAUNDERS CONSTRUCTION LLC
Natatorium piping pressure testing
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: d.wuthrich@saundersinc.com
8/18/2026 3:44:57 PM
Ground plumbing for Main drain for comp pool, inlet drain for comp pool, Inlet piping for the program pool. Highlighted in Pin on P135. all approved.
only overflow drains and inlets by the steps missing for all underground,
|
|
| 08/21/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 8/20/2026 12:02:02 PM
8/20/2026 12:02 PM FRONT RANGE SEE CR24-0596
please call Eli - 720-201-8763
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
8/21/2026 10:38:30 AM
Roof drains at Pool Mechanical Room and Pool Storage P111, Stair B P122, marked in green
Water lines in Pool Mechanical Room except for eye wash station. P500, Marked in green
Storage Room water lines marked in pink P111
|
|
| 08/21/2026 | B:GAS PIPE AIR TEST | MARTIN MAGERS | PARTIAL | WHOLE BLDG STEVIE 3034511971 | 8/21/2026 10:38:34 AM
All gas lines in A, B, and C roofs. Everything done except line on the pool Mech Roof.
Marked on P131, P132, P133 gas in pink
Signing gas on permit card, ok to release meter.
|
|
| 08/21/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | pool Bonding | 8/20/2026 8:22:34 AM
8/20/2026 8:22 AM LAKEWOOD ELECTRIC COMPANY INC
Competition pool bonding
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
8/21/2026 1:47:49 PM
Competition pool bonding of pool lights complete
|
|
| 08/24/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | frame area c | 8/21/2026 6:08:45 PM
8/21/2026 6:08 PM SAUNDERS CONSTRUCTION LLC
frame area c
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
8/24/2026 9:36:36 AM
PARTIAL-
1) FRAMING AREA B GRID 13 LINE WALL OK. Page A122 HIGHLIGHTED IN PINK.
|
|
| 08/26/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 8/25/2026 12:51:24 PM
8/25/2026 12:51 PM SAUNDERS CONSTRUCTION LLC
Mezz Area B Bathroom Ceilings, Gridline 13 Wall between Area A and D
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
8/26/2026 10:07:29 AM
PARTIAL-
1) FRAMING & CONNECTIONS FOR REQUEST ENGINEER DETAIL FOR SK 1 & 2 - OK.
|
|
| 08/28/2026 | B:RE ROUGH MECHANICAL | JOE CARBAUGH | PARTIAL | Area A Mezz | 8/27/2026 8:52:47 AM
8/27/2026 8:52 AM ATEK HEATING & AIR CONDITIONING
Please contact Angelo Nieto prior to arriving.
Contact Name: Angelo Nieto
Site Address: 222 BRICKYARD CIR
Phone: 7205846884
e-Mail: m.crespin@atekhtg.com
8/28/2026 12:23:16 PM
PARTIAL-
1) SEAL & SUPPORT FOR AREA's MARKED IN PINK - OK ON PG 121
NOTE: CONNECTIONS TO RTU's TO BE LOOKED AT FUTURE INSPECTION AT HIGHLIGHTED AREAS ABOVE.
|
|
| B:BUILDING SEPERATION WALL | BRETT LONGNECKER | | eTRAKiT Inspection Request | 9/1/2026 6:03:08 AM
9/1/2026 6:03 AM LAKEWOOD ELECTRIC COMPANY INC
Partial underfloor rough inspection between competition and program pools.
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
|
|
| 08/31/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 8/28/2026 7:11:25 AM
8/28/2026 7:11 AM SAUNDERS CONSTRUCTION LLC
South entrance thermax insulation betweeen gridline J/H, from the mezzanine to the highroof.
POC - Jason Orozco
720-955-6936
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: M.ROTH@SAUNDERSINC.COM
9/1/2026 6:56:26 AM
PARTIAL-
1) RIDGED FOAM INSULATION & Z TRAC - OK AT SOUTH ENTRANCE, GRID LINES J/H MEZZANINE.
|
|
| 09/01/2026 | B:ROUGH PLUMBING | BRETT LONGNECKER | PARTIAL | Pool piping for comp pool | 8/31/2026 9:28:53 AM
8/31/2026 9:28 AM SAUNDERS CONSTRUCTION LLC
Pool piping for comp pool
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: C.wagner@saundersinc.com
9/1/2026 11:25:35 AM
Pipe and test for competition pool ok as highlighted in blue on town approved plans for PL310.
|
|
| 09/01/2026 | B:RE ROUGH MECHANICAL | JOE CARBAUGH | PARTIAL | Please call Angelo Nieto prior to arrive | 8/31/2026 9:18:58 PM
8/31/2026 9:18 PM ATEK HEATING & AIR CONDITIONING
AREA A Rough Overhead Mech Inspection
Contact Name: Angelo Nieto
Site Address: 222 BRICKYARD CIR
Phone: 7205846884
e-Mail: m.crespin@atekhtg.com
9/1/2026 1:57:59 PM
PARTIAL-
1) SEAL & SUPPORT'S AREA B MEZZANINE- OK.
|
|
| 09/01/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 8/31/2026 1:11:44 PM
8/31/2026 1:11 PM SAUNDERS CONSTRUCTION LLC
Mezzanine Area B Bathroom Ceilings
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
9/1/2026 1:58:01 PM
PARTIAL-
1) COLD FORM STEEL FRAMING CEILING ( ONLY) FOR MEN'S & WOMEN'S RESTROOMS - OK.
|
|
| 09/01/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 9/1/2026 6:08:35 AM
9/1/2026 6:08 AM LAKEWOOD ELECTRIC COMPANY INC
Partial underslab rough between competition pool and program pool
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
9/1/2026 2:28:17 PM
Pool conduit feeds - 2 - 2-1/2 "pvc
2 - 2-1/4" pvc for security
1" and 3/4" branch
|
|
| 09/03/2026 | B:RE ROUGH PLUMBING | MARTIN MAGERS | APPROVED | eTRAKiT Inspection Request | 9/2/2026 1:50:24 PM
9/2/2026 1:50 PM FRONT RANGE SEE CR24-0596
contact Eli 720-201-8763
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
9/3/2026 10:50:19 AM
Water and gas lines in the water heater and meter rooms approved.
Water lines to to the pool mechanical room in the pool area approved
Gas lines to RTU on pool mechanical roof approved.
|
|
| 09/03/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/2/2026 6:32:14 AM
9/2/2026 6:32 AM SAUNDERS CONSTRUCTION LLC
Area C Past Gridline 20 Wall Framing
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
9/3/2026 11:34:23 AM
PARTIAL-
1) RGH FRAME HOSPITALITY 145
2) RR , 152/ MEN'S RESTROOM 136 SHARED RESTROOM SINKS 137 & WOMENS RESTROOM 135 - OK.
NOTE: T.O.W. TRACK TO BE RE- INSPECTED AT RR 151 AT FUTURE INSPECTION.
|
|
| 09/03/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 9/2/2026 2:17:40 PM
9/2/2026 2:17 PM LAKEWOOD ELECTRIC COMPANY INC
Electrical rough-in @ demising wall between gymnasiums C & D
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
9/3/2026 2:43:52 PM
Electrical wall rough see page - E112 and E121
|
|
| 09/04/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/3/2026 12:38:22 PM
9/3/2026 12:38 PM SAUNDERS CONSTRUCTION LLC
Screw Inspection, Gridline 13 Wall separating Mezz A from Area D
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
9/4/2026 11:13:48 AM
PARTIAL-
1) DRYWALL SCREW INSPECTION AREA A AT GRID LINES 13 H THROUGH A 7" ON EDGE & 8" IN FEILD -OK PER GA216 TABLE 5.
|
|
| 09/09/2026 | B:SHOWER PAN | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 9/8/2026 1:45:03 PM
9/8/2026 1:45 PM SAUNDERS CONSTRUCTION LLC
Gutter dropout pressure test for the competition pool.
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3038032820
e-Mail: D.Wuthrich@saundersinc.com
9/9/2026 2:50:30 PM
Shower Pan in Cabana D approved
9/9/2026 2:50:37 PM
gutter drop out on east half of competition pool approved. Marked in yellow on PL 310. All pool ground plumbing complete and approved.
|
|
| 09/09/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | CANCEL | eTRAKiT Inspection Request | 9/8/2026 11:33:01 AM
9/8/2026 11:33 AM SAUNDERS CONSTRUCTION LLC
Shower Pan Flood Test Locker Cabanas
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
9/9/2026 2:55:55 PM
Inspection called in wrong. Added shower pan inspection.
|
|
| 08/07/2026 | B:RE ROUGH MECHANICAL | MARTIN MAGERS | PARTIAL | Area B Mezz - Mech RI Inspection | 8/6/2026 10:40:35 AM
8/6/2026 10:40 AM ATEK HEATING & AIR CONDITIONING
Contact Name: Angelo Nieto
Site Address: 222 BRICKYARD CIR
Phone: 7205846884
e-Mail: m.crespin@atekhtg.com
8/10/2026 7:07:10 AM
All area B Mezz mechanical ducts complete and approved.
8/10/2026 7:08:38 AM
All area B Mezz mechanical ducts complete and approved.
|
|
| 09/10/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 9/9/2026 1:44:22 PM
9/9/2026 1:44 PM LAKEWOOD ELECTRIC COMPANY INC
Electrical service inspection
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
9/10/2026 3:06:32 PM
Transformer to userk cabinet approved
Userk to MDB approved
Okay to release meter
|
|
| 09/10/2026 | B:GROUND PLUMBING | MARTIN MAGERS | APPROVED | afternoon preferred | 9/9/2026 1:26:17 PM
9/9/2026 1:26 PM FRONT RANGE SEE CR24-0596
Contact Name: ELI HULBERT
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: stacey@frontrangeplumbing.com
9/11/2026 7:08:41 AM
Deck drain ground plumbing for the comp pool approved. Marked in orange on PL310. All ground plumbing complete and approved.
|
|
| 09/11/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/9/2026 10:40:13 AM
9/9/2026 10:40 AM SAUNDERS CONSTRUCTION LLC
Screw Inspection Gridline 13 Wall Separating Mezzanine Area B from Gym Area C
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
9/11/2026 11:22:46 AM
PARTIAL-
1) DRY WALL & SCREW INSPECTION FOR GRID LINE WALL 13 AREA (B) OK.
|
|
| 09/14/2026 | B:RE ROUGH FRAME | JOE CARBAUGH | PARTIAL | Insulation Inspection | 9/10/2026 9:53:11 AM
9/10/2026 9:53 AM SAUNDERS CONSTRUCTION LLC
South mezzanine entrance insulation and northwest entrance.
POC Jason Orozco
720-955-6936
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: M.ROTH@SAUNDERSINC.COM
9/14/2026 3:29:43 PM
PARTIAL-
1) RIDGED FOAM INSULATION & WALL Z TRACK AT NORTH WEST ENTRY & SOUTH ENTRY - OK.
|
|
| 09/15/2026 | B:GROUND PLUMBING | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/14/2026 12:49:03 PM
9/14/2026 12:49 PM SAUNDERS CONSTRUCTION LLC
Underground plumbing for the diving board agitator.
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3038032820
e-Mail: d.wuthrich@saundersinc.com
9/15/2026 9:41:16 AM
Inspector CORI changed the inspection assignment from CORI to JOCA
9/15/2026 10:20:51 AM
PARTIAL-
1) PLUMBING PRESSER TEST FOR DIVING BOARD AGITATOR - OK.
|
|
| 09/15/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | canopy lights | 9/14/2026 1:03:39 PM
9/14/2026 1:03 PM LAKEWOOD ELECTRIC COMPANY INC
Lighting rough inspection at south entry canopy
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
9/15/2026 2:31:02 PM
Rough electrical
5 - canopy lights
4 - canopy speakers
South entrance canopy
|
|
| 09/16/2026 | B:RE ROUGH MECHANICAL | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 9/15/2026 8:54:37 AM
9/15/2026 8:54 AM ATEK HEATING & AIR CONDITIONING
Contact Name: Angelo Nieto
Site Address: 222 BRICKYARD CIR
Phone: 7205846884
e-Mail: m.crespin@atekhtg.com
9/16/2026 9:06:47 AM
PARTIAL-
DUCT, SIZE, LAYOUT & SEAL & SUPPORT - OK/ PLANS MARKED UP ON M112 AREA B.
|
|
| 09/17/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 9/16/2026 1:23:46 PM
9/16/2026 1:23 PM LAKEWOOD ELECTRIC COMPANY INC
Underslab rough Area A "Leave Out"
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
9/17/2026 2:24:23 PM
Underslab power
Area A leave out
First aid
Pool managers office
|
|
| 09/21/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 9/18/2026 1:52:45 PM
9/18/2026 1:52 PM SAUNDERS CONSTRUCTION LLC
Shower Flood Test Locker Room Cabana B and C
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
9/21/2026 1:39:54 PM
Cabana B and C shower pans approved. As marked in green on P111.
|
|
| 09/22/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | mezz ceiling frame and area b level 1 | 9/22/2026 6:23:36 AM
9/22/2026 6:23 AM SAUNDERS CONSTRUCTION LLC
mezz ceiling frame and area b level 1
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: c.wagner@saundersinc.com
9/22/2026 2:47:42 PM
PARTIAL-
1) NEED CLARIFICATION FROM A COLORADO DESIGN PROFESSIONAL ON CEIING FRAMING (ATTACHMENT) TOO TENSION PLATE FOR ROOF SHEAR DIAPHRAGM/ PAGE A222 AREA B GRID LINES 9- 11 Y - Z.
2) CEILING FRAMING (ONLY) AT AREA B GRID LINES N - X 10 - 10.5 OK (PENDING) RGH MEPS & FIRE.
3) CEILING FRAMING (ONLY) AT ORANGE HIGHLIGHTED AREAS ON PAGE A 221 SUPER-SEEDED by ASI 06 AREA A OK (PENDING)RGH MEPS & FIRE.
|
|
| 09/23/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | electrical rough hard lids | 9/22/2026 11:57:52 AM
9/22/2026 11:57 AM LAKEWOOD ELECTRIC COMPANY INC
Various wall/ceiling rough inspections
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
9/23/2026 2:56:16 PM
Above ceiling hard lid
Mezzanine A bathrooms
Spectator soffit - lights
Rough electrical walls
Rec gym B demising wall camera/receptacle/horn strobe
Knee wall okay
|
|
| 09/24/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | CANCEL | eTRAKiT Inspection Request | 9/23/2026 6:56:25 AM
9/23/2026 6:56 AM LAKEWOOD ELECTRIC COMPANY INC
Partial underground site branch
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
9/24/2026 2:25:04 PM
Cancel per Rodger
|
|
| 09/25/2026 | B:ROUGH MECHANICAL | JOE CARBAUGH | PARTIAL | Area C lover lever bathrooms | 9/24/2026 1:37:09 PM
9/24/2026 1:37 PM ATEK HEATING & AIR CONDITIONING
Call Angelo Nieto
Contact Name: Angelo Nieto
Site Address: 222 BRICKYARD CIR
Phone: 7205846884
e-Mail: m.crespin@atekhtg.com
9/25/2026 10:32:38 AM
PARTIAL-
1) SEAL / SUPPORT & SIZE FOR DUCTS AT AREA (C) PG M113 GRID H- T / 20-21 - OK.
|
|
| 09/25/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | frame | 9/23/2026 6:45:15 AM
9/23/2026 6:45 AM SAUNDERS CONSTRUCTION LLC
re-inspection on 1 wall on area b mezz as well as other frame.
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
9/25/2026 10:32:41 AM
PARTIAL-
1) RE- INSPECTION ON ITEM FROM 9/22/26 AREA(B) PAGE A222 GRID LINE 10-10.5 Z-Y - OK.
2) CEILING & WALL RGH FRAME FOR AREA PG A211 GRID 12.5 - S - Y - OK.
|
|
| 09/25/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 9/24/2026 12:10:30 PM
9/24/2026 12:10 PM LAKEWOOD ELECTRIC COMPANY INC
Undergroind site branch inspection
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
9/25/2026 2:21:14 PM
Electrical trench
South side parking lot approved
6 light poles
|
|
| 10/06/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 10/5/2026 6:32:15 AM
10/5/2026 6:32 AM LAKEWOOD ELECTRIC COMPANY INC
Competition pool partial bonding inspection
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
10/6/2026 1:24:46 PM
Bonding program pool pour 10 okay
Starting block bonging and timing system okay
Rough electrical multi purpose room A and B divider room
|
|
| B:ROUGH FRAME | BRETT LONGNECKER | | eTRAKiT Inspection Request | 10/7/2026 7:59:38 AM
10/7/2026 7:59 AM SAUNDERS CONSTRUCTION LLC
Level 1 Area A and B, Mezzanine Area A and B
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
|
|
| 10/07/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | Pre-pour inspection for pool drains | 10/6/2026 10:30:13 AM
10/6/2026 10:30 AM FRONT RANGE SEE CR24-0596
Pre-pour inspection for pool drains IF required POUR IS AM on 10/7
Contact Name: Eli
Site Address: 222 BRICKYARD CIR
Phone: 7202018763
e-Mail: Stacey@frontrangeplumbing.com
10/7/2026 9:55:37 AM
All floor drains in the pool area approved.
|
|
| 10/07/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Ceiling Frame throughout | 10/6/2026 3:02:20 PM
10/6/2026 3:02 PM SAUNDERS CONSTRUCTION LLC
Area B elevator shaft
Area A soffits
Area B sounds
Area A L1 soffit
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 7202528955
e-Mail: J.combs@saundersinc.com
10/7/2026 11:14:29 AM
PARTIAL-
1) HARD LID FRAMING 2nd FLOOR - CHECK IN 201, CHILD WATCH 211, UPPER LOBBY 200 - OK.
2) HARD LID FRAMING 1st FLOOR - GYP BD, CONFERENCE ROOM 118, OFFICES 125, 126 & 127, ELEV. B - OK.
NOTE: ****COMPLETE ALL RGH MEP's & CASTLE ROCK FIRE INSPECTIONS ABOVE HARD LID BEFORE CLOSING. ****
|
|
| 10/07/2026 | B:WATER RESISTIVE BA | JOE CARBAUGH | PARTIAL | Tyvek weather barrier inspection | 10/5/2026 8:29:23 AM
10/5/2026 8:29 AM SAUNDERS CONSTRUCTION LLC
POC Jason Orozco Cell - 7209556936
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: M.ROTH@SAUNDERSINC.COM
10/7/2026 11:14:31 AM
PARTIAL-
1) NORTH ENTRANCE ROOF FACE WEATHER BARRIER - OK.
|
|
| 10/07/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 10/6/2026 12:40:23 PM
10/6/2026 12:40 PM LAKEWOOD ELECTRIC COMPANY INC
Misc wall rough inspections
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
10/7/2026 2:01:53 PM
Hard lid area B mezz bathrooms
Hard lid area B corridor/ party rooms
Hard lid area B check in
Hard lid area B missed framing
Area C gym soffit
Area D gym soffit and gym wall to area A
|
|
| 10/08/2026 | B:ROUGH MECHANICAL | MARTIN MAGERS | APPROVED | Area A, Area B, Lower Level B Final Insp | 10/7/2026 12:16:56 PM
10/7/2026 12:16 PM ATEK HEATING & AIR CONDITIONING
Please contact Angelo Nieto when arriving on site 720-584-6884
Contact Name: Angelo Nieto
Site Address: 222 BRICKYARD CIR
Phone: 7205846884
e-Mail: m.crespin@atekhtg.com
10/8/2026 12:58:11 PM
Mezz A and B Ceilings approved to be covered. All rough Mech approved.
|
|
| 10/09/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 10/8/2026 9:34:45 AM
10/8/2026 9:34 AM SAUNDERS CONSTRUCTION LLC
Flood Test Showers: Men''s and Women''s Locker Room 8 total
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
10/9/2026 12:16:56 PM
Inspected the 8 shower pans in the men's and women's bathrooms. The 2 outer showers are approved and the 2 inner showers need more slope to 1/4 slope in 12 in, for both the men's and women's shower area.
|
|
| 10/12/2026 | B:ROUGH ELECTRICAL | SHAWN VALENZUELA | PARTIAL | eTRAKiT Inspection Request | 10/6/2026 10:51:29 AM
10/6/2026 10:51 AM LAKEWOOD ELECTRIC COMPANY INC
Pool bonding inspection
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
10/12/2026 12:51:42 PM
Rough electrical partial inspection approved
Areas inspected
Area b1 first floor soffit north of b1 gym
Pool bonding inspection
Competition pool Pour 11
Notes
#8 solid bare bonding wire
12 Pool frame bonds
7 grab bar bonds
1 Handicap lift bonded
5 starting blocks bonded
|
|
| 10/14/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 10/13/2026 11:41:28 AM
10/13/2026 11:41 AM SAUNDERS CONSTRUCTION LLC
Area B Level 1 Soffits
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
10/14/2026 12:07:02 PM
PARTIAL-
1) SOFFIT RGH FRAMING/ AREA ( B) - OK.
NOTE: COMPLETE ALL RGH MEP's & FIRE INSPECTIONS BEFORE GYP.
|
|
| 10/14/2026 | B:WATER RESISTIVE BA | JOE CARBAUGH | PARTIAL | Tyvek waterproofing | 10/13/2026 7:41:16 AM
10/13/2026 7:41 AM SAUNDERS CONSTRUCTION LLC
Tyvek waterproofing, south and east building elevations. POC - Ryan Mcvicker 720-236-6346
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: M.ROTH@SAUNDERSINC.COM
10/14/2026 8:37:41 AM
JOCA changed Inspection Type from B:ROUGH FRAME to B:WATER RESISTIVE BA
10/14/2026 12:07:05 PM
PARTIAL-
1) WEATHER BARRIER/ SOUTH ENTRANCE RIM- OK.
NOTE: UPPER RIM SOUTH / EAST WEATHER BARRIER TO BE INSPECTED AT FUTURE INSPECTION.
|
|
| 10/14/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 10/12/2026 12:52:17 PM
10/12/2026 12:52 PM SAUNDERS CONSTRUCTION LLC
Area A Locker Room Shower Flood Test, Four Remaining Showers not previously accepted.
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
10/14/2026 2:20:19 PM
Corrections made. All shower pans are approved.
|
|
| 10/14/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 10/13/2026 2:16:11 PM
10/13/2026 2:16 PM LAKEWOOD ELECTRIC COMPANY INC
Competition pool bonding
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
10/14/2026 2:32:33 PM
Pool bonding pour 12
Diving board / ladder
11 starting blocks
|
|
| 10/15/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | pool bonding complete | 10/14/2026 9:23:47 AM
10/14/2026 9:23 AM LAKEWOOD ELECTRIC COMPANY INC
Poll bonding inspection
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
10/15/2026 1:08:56 PM
Pool bonding complete pour 12
|
|
| 10/27/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | PARTIAL | eTRAKiT Inspection Request | 10/27/2026 6:22:30 AM
10/27/2026 6:22 AM FRONT RANGE SEE CR24-0596
Eli is onsite 720-201-8763
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
10/27/2026 3:30:14 PM
DWV and water for trash roo and laundry marked in orange on P111
All rough plumbing, with the exception of roof drains at the pool area are complete and approved.
|
|
| 10/28/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | rough electrical | 10/27/2026 11:41:38 AM
10/27/2026 11:41 AM LAKEWOOD ELECTRIC COMPANY INC
Partial wall rough, north side area C
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
10/28/2026 10:28:35 AM
Walls and ceiling rough electrical C north locker rooms approved
Lower competition hall walls only electrical rough
Area A locker room entry approved above ceiling
|
|
| B:RE ROUGH FRAME | BRETT LONGNECKER | | Cold formed metal framing inspection | 10/28/2026 11:39:26 AM
10/28/2026 11:39 AM SAUNDERS CONSTRUCTION LLC
POC Jason Orozco 7209556936
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: M.ROTH@SAUNDERSINC.COM
|
|
| 10/29/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | area c frame and ceiling frame | 10/28/2026 11:42:41 AM
10/28/2026 11:42 AM SAUNDERS CONSTRUCTION LLC
area c frame and ceiling frame
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: t.woodard@saundersnorwood.com
10/29/2026 2:32:46 PM
PARTIAL-
1) HARD LID CEILING FRAMING FOR LEVEL 1 AREA C BATHROOMS - OK.
|
|
| B:ROUGH FRAME | BRETT LONGNECKER | | Tyvek Inspection | 10/29/2026 11:32:29 AM
10/29/2026 11:32 AM SAUNDERS CONSTRUCTION LLC
Tyvek waterproofing at the upper and lower exterior natatorium elevations. POC Jason O. 720 955 6936
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: M.ROTH@SAUNDERSINC.COM
|
|
| 11/04/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | eTRAKiT Inspection Request | 11/2/2026 2:41:38 PM
11/2/2026 2:41 PM SAUNDERS CONSTRUCTION LLC
Tyvek at the south and north of the building. POC Jason Orozco Phone:7209556936
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 3036999000
e-Mail: M.ROTH@SAUNDERSINC.COM
11/4/2026 11:32:03 AM
PARTIAL-
1) WEATHER BARRIER, RIGID FOAM, & TYVEK AT SOUTH EAST OF ENTRANCE & EAST ELEVATION THROUGH GRID LINE 7 - OK.
|
|
| 11/04/2026 | B:ROUGH PLUMBING | MARTIN MAGERS | APPROVED | eTRAKiT Inspection Request | 11/3/2026 2:29:45 PM
11/3/2026 2:29 PM FRONT RANGE SEE CR24-0596
Eli 720-201-8763 roof drain rough
Contact Name: FRONT RANGE SEE CR24-0596
Site Address: 222 BRICKYARD CIR
Phone: 3034511971
e-Mail: stacey@frontrangeplumbing.com
11/4/2026 3:06:44 PM
South storm drains approved. All rough in plumbing complete.
|
|
| 11/12/2026 | B:ROUGH FRAME | JOE CARBAUGH | PARTIAL | Area A South Bridge Wall | 11/10/2026 6:47:56 AM
11/10/2026 6:47 AM SAUNDERS CONSTRUCTION LLC
Area A South Bridge Wall Frame
Contact Name: SAUNDERS CONSTRUCTION LLC
Site Address: 222 BRICKYARD CIR
Phone: 6308999796
e-Mail: c.wagner@saundersinc.com
11/12/2026 8:42:43 AM
PARTIAL-
1) BRIDGE AREA (A) RGH WALL FRAMING - OK.
|
|
| 11/12/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 11/10/2026 2:55:51 PM
11/10/2026 2:55 PM LAKEWOOD ELECTRIC COMPANY INC
Underground site conduit inspection north side of building along Brick Yard Circle
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
11/12/2026 3:04:13 PM
North side of building
2 - 4" pvc fiber conduit - 2 ground boxes
1 - 2" pvc monument sign
East side
2 - 1" site lighting and power
|
|
| 11/20/2026 | B:ROUGH ELECTRICAL | VINCE RAPONE | PARTIAL | eTRAKiT Inspection Request | 11/20/2026 6:24:26 AM
11/20/2026 6:24 AM LAKEWOOD ELECTRIC COMPANY INC
Partial overhead rough @ locker rooms
Contact Name: LAKEWOOD ELECTRIC COMPANY INC
Site Address: 222 BRICKYARD CIR
Phone: 7196001297
e-Mail: rbinford@lkwd-elec.com
11/20/2026 1:50:22 PM
Above ceiling locker rooms
|
|