11/21/2026
10:55 PM
 
Permit No. 25-0192 Permit Type   COMMERCIAL NEW Site Address   222 BRICKYARD CIR
CASTLE ROCK, CO 80109
Applied   01/16/2025 Applicant   SAUNDERS CONSTRUCTION LLC
Approved   08/22/2025 Owner   TOWN OF CASTLE ROCK
Issued   09/02/2025 Contractor  
Parent Permit No.   Description   BRICKYARD ROCK SPORTS COMPLEX TOWN PROJECT
  Notes   This project shall be reviewed under the 2024 fee schedule per Dave Corliss, Town Manager.
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 10/03/2025B:UNGRD PLUMBBRETT LONGNECKERPARTIALSheet # P11310/2/2025 1:14:00 PM 10/2/2025 1:14 PM FRONT RANGE SEE CR24-0596 Joe 720-341-6598 Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 10/3/2025 2:10:24 PM Underground 4 inch foundation drain for ejector pump in competition storage room. Highlighted in blue on P113. Photo uploaded.

 09/30/2025B:UNGRD PLUMBMICHAEL RANKINPARTIALDetail 2/P5009/29/2025 2:16:47 PM 9/29/2025 2:16 PM FRONT RANGE SEE CR24-0596 Joe- 720-341-6598 Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: Stacey@frontrangeplumbing.com 9/30/2025 10:03:23 AM Partial underground plumbing inspection for 4in foundation drain from ejector pits and 4in pool under drain ok. Highlighted in green detail 2/P500.

 09/12/2025B:ELECTRICAL TRENCHJON WHITEPARTIALTemp Service Const Trailer9/11/2025 12:46:11 PM 9/11/2025 12:46 PM LAKEWOOD ELECTRIC COMPANY INC Partial trench inspection for temp power Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 9/12/2025 11:49:05 AM Partial Underground - 2" PVC in trench from temp service to Saunders Construction Trailer Temp service. OK to Bury - (2) 2 1/2" PVC from Temp Service, 100' to east. (Will carry temp power into building). Ok to bury this section

 11/14/2025B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request11/13/2025 3:11:41 PM 11/13/2025 3:11 PM LAKEWOOD ELECTRIC COMPANY INC Outlets in cast-in-place wall Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 3037830600 e-Mail: RECEPTION@LKWD-ELEC.COM 11/14/2025 10:27:58 AM Area B south wall - 2 receptacle pre cast wall

 11/20/2025B:UNGRD PLUMBMARTIN MAGERSPARTIALDuane 720-939-370911/19/2025 1:27:16 PM 11/19/2025 1:27 PM FRONT RANGE SEE CR24-0596 Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: Stacey@frontrangeplumbing.com 11/20/2025 12:11:23 PM Sump / Sewer underground approved

 11/20/2025TRAINING_COLBYCOLBY RIGGINSAPPROVED

 11/21/2025B:RGH ELECTVINCE RAPONEPARTIALunderground sump pit sleeves11/20/2025 1:56:18 PM 11/20/2025 1:56 PM LAKEWOOD ELECTRIC COMPANY INC Underfloor sump pit conduits Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 11/21/2025 10:42:10 AM Area B sump pit 4 - 2" pvc conduits good 2 - 2" sleeves to each pit.

 12/01/2025B:RGH ELECTVINCE RAPONEPARTIALGymnasium Cast wall electrical11/26/2025 11:44:22 AM 11/26/2025 11:44 AM LAKEWOOD ELECTRIC COMPANY INC Cast in Place wall rough Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 12/1/2025 2:23:08 PM Gymnasium Cast wall electrical rough good Receptacles / fire alarm boxes

 12/08/2025B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request12/5/2025 11:47:33 AM 12/5/2025 11:47 AM LAKEWOOD ELECTRIC COMPANY INC UFER Ground Inspection Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001279 e-Mail: rbinford@lkwd-elec.com 12/8/2025 10:16:39 AM User ground good

 12/09/2025B:RGH ELECTVINCE RAPONEPARTIALpre cast wall rough12/8/2025 12:41:19 PM 12/8/2025 12:41 PM LAKEWOOD ELECTRIC COMPANY INC Are B West Wall Rough Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 12/9/2025 11:17:00 AM Area b west wall pre cast electrical wall rough good F/A and WAP

 09/10/2025PRE CON INSPECTIONBRETT LONGNECKERAPPROVEDCastle Rock Sports Center - Precon9/9/2025 7:56:22 AM 9/9/2025 7:56 AM SAUNDERS CONSTRUCTION LLC Hello, my name is Clay Wagner with Saunders construction. We would like to schedule a preconstruction meeting for the Castle Rock Sports Center Job. Our jobsite trailer is not fully complete yet and our trailer inspection is requested for Thursday morning. So, if it works for you, we can meet at the Town of Castle Rock office for this preconstruction. Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 9/10/2025 8:06:06 AM Discussed pre con meeting with Clay. Need to reach out to DS construction inspectors and storm water for their pre con meeting. 12/10/2025 9:36:01 AM Building pre con conducted on 12/10/25 at 8:00 am in Townhall Council Chambers with Josh Combs and Anna Gannon representing Saunders Construction.

 12/15/2025B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request12/12/2025 2:40:23 PM 12/12/2025 2:40 PM LAKEWOOD ELECTRIC COMPANY INC Rough wall inspection for one receptacle outlet, Area B west wall. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 12/15/2025 2:50:51 PM Receptacle pre cast wall area b good

 12/23/2025B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request12/22/2025 12:23:56 PM 12/22/2025 12:23 PM LAKEWOOD ELECTRIC COMPANY INC Cast-in-place wall rough inspection for 5 devices, Area C West Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 12/23/2025 2:34:34 PM Pre cast wall rough west side area c good

 01/05/2026B:RGH ELECTVINCE RAPONEPARTIALMonolith lighting conduit rough1/2/2026 5:49:22 AM 1/2/2026 5:49 AM LAKEWOOD ELECTRIC COMPANY INC Monolith lighting conduit rough Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 1/5/2026 3:01:25 PM Stair well low volt lighting sleeves 4 - 1/2" conduits

 01/12/2026B:UNGRD PLUMBMARTIN MAGERSPARTIALDuane - 720-939-3709 Onsite contact1/9/2026 10:41:03 AM 1/9/2026 10:41 AM FRONT RANGE SEE CR24-0596 Area A Trash Chute Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 1/12/2026 11:19:48 AM Floor sink in trash shoot approved. Current plans not printed and therefore not high lighted.

 01/15/2026TRAINING_SHAWNSHAWN VALENZUELAPARTIAL1/15/2026 2:38:29 PM Stairwell a trash room Stairwell b storage room

 01/15/2026B:RGH ELECTVINCE RAPONEPARTIALSOG, stair A/B, Storage B/SOG1/14/2026 1:43:42 PM 1/14/2026 1:43 PM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: RECEPTION@LKWD-ELEC.COM 1/15/2026 3:03:20 PM Stair A / trash room Under slab Heater and receptacle pipe good Stair b and storage under slab pvc good

 01/20/2026B:RGH ELECTVINCE RAPONEPARTIALUnderground temp power feeder1/16/2026 1:30:35 PM 1/16/2026 1:30 PM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 1/20/2026 1:58:52 PM Temp power trench after road crossing to hill good

 01/22/2026B:RGH ELECTVINCE RAPONEPARTIALTemp power UG trench inspection1/21/2026 1:22:49 PM 1/21/2026 1:22 PM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001279 e-Mail: rbinford@lkwd-elec.com 1/22/2026 2:04:36 PM Temp power trench good Down the hill and across the road south west corner to building good

 01/30/2026B:RGH ELECTVINCE RAPONEPARTIALPartial underground duct bank inspection1/29/2026 11:07:16 AM 1/29/2026 11:07 AM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 1/30/2026 2:15:02 PM Under ground - Userk cabinet to electrical room / low volt sleeves

 02/11/2026B:UNGRD PLUMBMARTIN MAGERSPARTIALeTRAKiT Inspection Request2/10/2026 11:41:31 AM 2/10/2026 11:41 AM FRONT RANGE SEE CR24-0596 Eli 720-201-8763 Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: Stacey@frontrangeplumbing.com 2/11/2026 11:44:06 AM 6" and 4"low drains for main locker rooms, ok. Highlight in green. Not connected to back line. Front run through foundation never inspected and back where it runs under large footer. Note all earlier inspections updated in new plans.

 02/18/2026B:UNGRD PLUMBMARTIN MAGERSPARTIALPlease call ELI 7202018763 when OTW2/17/2026 12:52:53 PM 2/17/2026 12:52 PM FRONT RANGE SEE CR24-0596 AM Preferred Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 2/18/2026 12:34:47 PM Ground pluming at Area A was inspected and on test. See pic at P111. All ground plumbing up top just before G for the main locker room approved. Drain for urinals was moved to the 4" drain at grid line 11. See pic of P500

 02/23/2026B:UNGRD PLUMBMARTIN MAGERSPARTIALAM Preferred2/20/2026 7:50:36 AM 2/20/2026 7:50 AM FRONT RANGE SEE CR24-0596 Eli Hulbert 720-201-8763 Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 2/23/2026 12:56:29 PM All ground plumbing through H approved.

 02/23/2026B:RGH ELECTVINCE RAPONEPARTIALPartial underslab conduits2/20/2026 7:13:31 AM 2/20/2026 7:13 AM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 2/23/2026 2:09:40 PM Under slab - electrical branch / panel feeders / low volt sleeves good

 02/26/2026TRAINING_SHAWNSHAWN VALENZUELAAPPROVED2/26/2026 2:42:57 PM Training was completed Underground electrical room

 02/26/2026B:RGH ELECTVINCE RAPONEPARTIALUnderslab conduit rough2/25/2026 12:15:19 PM 2/25/2026 12:15 PM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 2/26/2026 2:47:00 PM Under slab electrical room good Ev charger panel Lighting control panel High volt panel

 03/03/2026B:RGH ELECTSHAWN VALENZUELAPARTIALUnderslab branch conduit rough3/2/2026 11:57:52 AM 3/2/2026 11:57 AM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 3/3/2026 8:40:56 AM Partial underground approved Branch circuits raceway from electrical room

 03/03/2026B:UNGRD PLUMBKEVIN ARENCIBIAPARTIALStorm Drain3/2/2026 2:43:15 PM 3/2/2026 2:43 PM FRONT RANGE SEE CR24-0596 underground roof drain area A contact is Eli 720-201-8763 Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 3/3/2026 11:42:05 AM 6" storm drain & branch for ORD catch basin at grid A-12 layout & pressure test ok to stub-up; pictures uploaded

 03/09/2026B:RGH ELECTVINCE RAPONEPARTIALSlab on grade branch conduit inspection3/6/2026 6:36:56 AM 3/6/2026 6:36 AM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 3/9/2026 11:24:51 AM Area A under slab branch circuit- feeder duct bank pvc good

 03/13/2026B:RGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request3/12/2026 2:54:40 PM 3/12/2026 2:54 PM Josh Combs Rough Frame for Roof Area A Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 3/13/2026 9:47:34 AM PARAPET ROOF FRAMING AT GRID LINES A LINE & 2 LINE OK. NOTE: REST OF PARAPET WALL IN BE INSPECTED AT FUTURE INSPECTIONS.

 03/20/2026B:UNGRD PLUMBMARTIN MAGERSPARTIALcontact Elli 720-201-87633/20/2026 9:28:11 AM contact Elli 720-201-8763 3/20/2026 10:28:22 AM Inspector MAM2 changed the inspection assignment from MAM2 to MAM2 3/20/2026 2:02:22 PM Groung plumbing drain for mechanical room. Highlighted on P111 and P500.

 03/23/2026B:UNGRD PLUMBMARTIN MAGERSPARTIALcontact Eli 720-201-87633/20/2026 8:50:31 AM 3/20/2026 8:50 AM FRONT RANGE SEE CR24-0596 contact Elli 720-201-8763 Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 3/23/2026 11:39:13 AM All ground plumbing in Area B approved and highlighted in green on page P112.

 03/24/2026B:RGH ELECTVINCE RAPONEPARTIALPartial underfloor conduits area B3/23/2026 10:08:54 AM 3/23/2026 10:08 AM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 3/24/2026 12:04:12 PM Under slab conduits - low volt / access control / branch / 1" pvc good Mezzanine conduits - 3/4 pvc cardio deck conduits good

B:RGH MECHBRETT LONGNECKERUnderslab electrical area B3/25/2026 2:37:32 PM 3/25/2026 2:37 PM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com

 03/27/2026B:RGH ELECTSHAWN VALENZUELACANCELPool equip room underslab. Cardio deck3/26/2026 2:54:54 PM 3/26/2026 2:54 PM LAKEWOOD ELECTRIC COMPANY INC Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 3/27/2026 6:44:54 AM DUPLICATE INSPECTION

 03/27/2026B:RGH PLUMBMARTIN MAGERSPARTIALcontact Eli 720-201-87633/26/2026 12:38:36 PM 3/26/2026 12:38 PM FRONT RANGE SEE CR24-0596 Eli 720-201-8763 area locker room Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 3/27/2026 8:56:13 AM Cabana and shower in wall plumbing ok up to 5 ft for first lift of block.

 03/27/2026B:RGH ELECTSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request3/26/2026 2:57:26 PM 3/26/2026 2:57 PM LAKEWOOD ELECTRIC COMPANY INC Pool equip room SOG. Cardio deck lighting SOG Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 3/27/2026 2:32:31 PM Did not look at pool equipment room not ready Cardio deck lighting good ( see photo) Underground in area b under mezzanine good ( see photo)

 03/30/2026B:INSULATIONJOE CARBAUGHPARTIALRoof insulation Area A3/27/2026 11:28:31 AM 3/27/2026 11:28 AM Josh Combs Can be at the same time as Rough Frame Area B Contact Name: Clay Wagner Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 3/30/2026 11:07:56 AM PARTIAL- ROOF INSULATION AREA - A DENS DECK, (2) LAYERS OF RIDGED INSULATION-OK.

 03/30/2026B:RGH FRAMEJOE CARBAUGHNOT APPROVEDCold Formed Area B Roof3/27/2026 11:23:28 AM 3/27/2026 11:23 AM Josh Combs Contact Name: Clay Wagner Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 3/30/2026 11:07:58 AM NOT APPROVED - MISSING SCREWS TO COLD FORMED STEEL FOR SCREW SCHEDULE / ROOF / WALL FRAMING BETWEEN AREA A & B / ON PAGE C2 LEFT OF PAGE UNDER APPROVED FASTENERS. NOTE: RECALL INSPECTION WHEN ITEMS HAVE BEEN CORRECTED.

 03/30/2026B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request3/27/2026 2:39:21 PM 3/27/2026 2:39 PM LAKEWOOD ELECTRIC COMPANY INC Area B to C underslab conduits. Pool equipment room underslab conduits. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 3/30/2026 3:28:14 PM Pool equipment room under slab good

 03/31/2026B:RGH PLUMBBRETT LONGNECKERPARTIALIn wall only locker rooms3/30/2026 4:01:29 PM 3/30/2026 4:01 PM FRONT RANGE SEE CR24-0596 locker rooms Contact Name: Front Range Plumbing Co inc Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 3/31/2026 11:39:11 AM All in wall rough for DWV and water ok to conceal in locker room as shown on 3/P500.

 04/09/2026B:UNGRD PLUMBBRETT LONGNECKERPARTIALUnderground for Area C4/8/2026 7:54:19 AM 4/8/2026 7:54 AM FRONT RANGE SEE CR24-0596 Am Preferred for Area C Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 4/9/2026 9:51:18 AM Area C underground DWV ok as highlighted on 3/501 in blue.

 04/09/2026B:ELECTRICAL TRENCHVINCE RAPONEPARTIALeTRAKiT Inspection Request4/8/2026 2:05:06 PM 4/8/2026 2:05 PM LAKEWOOD ELECTRIC COMPANY INC Service entrance duct bank and site feeders trench Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 4/9/2026 2:15:44 PM Transformer to userk under ground approved Low volt sleeves Lighting and EV branch

 04/10/2026B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request4/9/2026 12:40:06 PM 4/9/2026 12:40 PM LAKEWOOD ELECTRIC COMPANY INC Underslab rough, area B Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 4/10/2026 2:18:12 PM Pool wall to aerobics under ground electrical good Power and FA

 04/14/2026B:INSULATIONJOE CARBAUGHPARTIALArea B roof insulation4/13/2026 10:04:23 AM 4/13/2026 10:04 AM Josh Combs Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 4/14/2026 11:12:05 AM PARTIAL- 1) BATT INSULATION / RIDGED FOAM INSULATION & ATTACHMENT SCHEDULE- OK FOR ROOF AREA (B).

 04/16/2026B:RGH ELECTVINCE RAPONECANCELeTRAKiT Inspection Request4/15/2026 12:48:09 PM 4/15/2026 12:48 PM LAKEWOOD ELECTRIC COMPANY INC Partial program pool bonding Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 4/16/2026 11:09:09 AM Cancel per Rodger Reschedule

 04/17/2026B:RGH ELECTVINCE RAPONEPARTIALpool bonding4/16/2026 9:40:05 AM 4/16/2026 9:40 AM LAKEWOOD ELECTRIC COMPANY INC Partial program pool bonding inspection Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 4/16/2026 9:41:33 AM 4/16/2026 9:41 AM LAKEWOOD ELECTRIC COMPANY INC Partial program pool bonding Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 4/17/2026 1:46:38 PM Pool bonding Handicap ramp / upper portion of kiddie pool

 04/17/2026B:RGH FRAMEJOE CARBAUGHPARTIALFraming Mech Wells High Roof4/16/2026 2:52:35 PM 4/16/2026 2:52 PM Josh Combs Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 4/17/2026 3:03:06 PM PARTIAL- 1) RGH FRAME - ROOF TOP HEAD OF WALL ATTACHMENT & FULL FRAME WALL INSPECTION FOR AREA

 04/24/2026B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request4/23/2026 2:46:30 PM 4/23/2026 2:46 PM LAKEWOOD ELECTRIC COMPANY INC Area C lover level UG conduits. Area C lighting rough at track. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 4/24/2026 1:22:02 PM Area C upper track slab PVC - lights Area C lower underground slab branch pvc

 04/28/2026B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request4/27/2026 2:02:57 PM 4/27/2026 2:02 PM LAKEWOOD ELECTRIC COMPANY INC underslab conduit inspection area C north. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 4/28/2026 1:38:41 PM Area C north under slab branch pvc - bathrooms - storage area

 04/29/2026B:RGH PLUMBMARTIN MAGERSPARTIALREQUEST AM4/28/2026 10:58:18 AM 4/28/2026 10:58 AM FRONT RANGE SEE CR24-0596 Rough plumb inspection for Area A - Mezzanine Eli 720-201-8763 site contact Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 4/29/2026 2:03:15 PM Storm Drain, DWV, Water for Mezzanine Area A all ok except stair A roof drain and penetration and water heater Flues. Storm drains stumbled through wall North and NE corner P114. See P121 p501 and P 500 marked in purple. See pictures.

 04/29/2026B:RGH ELECTVINCE RAPONEPARTIALeTRAKiT Inspection Request4/28/2026 2:52:06 PM 4/28/2026 2:52 PM LAKEWOOD ELECTRIC COMPANY INC Area C north storage room and janitor closet under slab conduits Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 4/29/2026 2:53:16 PM Under slab pvc - janitor and storage room area - c

 05/05/2026B:RE ROUGH ELECTRICALVINCE RAPONECANCELeTRAKiT Inspection Request5/4/2026 9:48:22 AM 5/4/2026 9:48 AM LAKEWOOD ELECTRIC COMPANY INC Elevated track area B lighting rough. Temporary service underground conduits. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 5/5/2026 11:13:58 AM Cancel per Rodger

 05/12/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request5/11/2026 8:50:01 AM 5/11/2026 8:50 AM LAKEWOOD ELECTRIC COMPANY INC Slab on deck conduit for area B elevated track. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 5/12/2026 12:17:46 PM Area B elevated deck approved Lights

 05/13/2026B:INSULATIONJOE CARBAUGHPARTIALRoof Insulation5/12/2026 8:03:44 AM 5/12/2026 8:03 AM Josh Combs This inspection is for roof insulation. I don''t see insulation listed in the drop down menu Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 5/13/2026 1:29:08 PM PARTIAL- 1) 2 LAYERS OF ROOF RIDGED FOAM INSULATION AREA A EAST HIGH ROOF- OK.

 05/18/2026B:INSULATIONJOE CARBAUGHCANCELRoof insulation5/15/2026 9:37:28 AM 5/15/2026 9:37 AM Josh Combs This is for building and roof insulation. I don''t see insulation listed in the drop down menu Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 5/18/2026 12:09:19 PM CANCELED - BY SUPERINTENDENT JOSH COMBS.

 05/22/2026B:INSULATIONJOE CARBAUGHPARTIALRoof and Wall Insulation5/21/2026 8:14:07 AM 5/21/2026 8:14 AM Josh Combs Roof and Exterior wall insulation Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 5/22/2026 11:37:18 AM PARTIAL- 1) HIGH ROOF AREA A & D 2) HIGH ROOF WALL PLAN NORTH & HIGH ROOF PLAN B AREA WALL SOUTH- OK.

 05/22/2026B:RE ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request5/21/2026 12:33:40 PM 5/21/2026 12:33 PM LAKEWOOD ELECTRIC COMPANY INC Temporary service UG conduit inspection. East side of bldg. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 5/22/2026 12:04:59 PM Temp service underground pvc approved 2 - 2-1/2" pvc to disconnect to transformer

 05/26/2026B:GROUND PLUMBINGMARTIN MAGERSNOT APPROVEDUG Sanitary Tie in5/21/2026 8:42:06 AM 5/21/2026 8:42 AM Josh Combs UG Sanitary Ties Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 5/26/2026 11:36:23 AM Tie in not complete.

 06/02/2026B:INSULATIONMARTIN MAGERSCANCELRoof Insualtion6/1/2026 8:08:25 AM 6/1/2026 8:08 AM Josh Combs This is for roof insulation. Insulation isnt listed on the drop down Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 6/2/2026 7:32:47 AM CANCEL- NOTE: CONTRACTOR CANCELED INSPECTION AND HAS INSULATION INSPECTION FOR 06/04/26.

 06/02/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request6/1/2026 2:17:19 PM 6/1/2026 2:17 PM LAKEWOOD ELECTRIC COMPANY INC Elevated track in-slab lighting rough. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 3038827140 e-Mail: rbinford@lkwd-elec.com 6/2/2026 12:04:20 PM Elevated track deck approved Lighting pvc

 06/02/2026B:ELECTRICAL TEMPORARY CONSTRUCTION METERVINCE RAPONENOT APPROVEDeTRAKiT Inspection Request6/1/2026 2:16:06 PM 6/1/2026 2:16 PM LAKEWOOD ELECTRIC COMPANY INC Temporary service inspection. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 6/2/2026 12:04:30 PM Need CT's installed before meter release Need 400A fuses Reschedule

 06/03/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request6/2/2026 12:55:44 PM 6/2/2026 12:55 PM LAKEWOOD ELECTRIC COMPANY INC Program pool bonding Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 6/3/2026 2:05:40 PM Bonding for 11 - niche lights in program pool approved

 06/04/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALarea D underslab6/3/2026 6:49:30 AM 6/3/2026 6:49 AM LAKEWOOD ELECTRIC COMPANY INC Underslab conduits area D Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 6/4/2026 1:51:29 PM Underslab electrical rough area D trunk line to storage room only Branch pvc

 06/04/2026B:INSULATIONJOE CARBAUGHPARTIALeTRAKiT Inspection Request6/1/2026 8:08:57 AM 6/1/2026 8:08 AM Josh Combs This is for roof insulation. Insulation isnt listed on the drop down Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 6/4/2026 2:26:59 PM PARTIAL- 1) 2" RIDGE FOAM ROOF INSULATION x 3 - / GRID 9 THROUGH 13 , Z THROUGH S & S THROUGH K - OK.

 06/08/2026B:ELECTRICAL TEMPORARY CONSTRUCTION METERVINCE RAPONEAPPROVEDeTRAKiT Inspection Request6/5/2026 10:34:00 AM 6/5/2026 10:34 AM LAKEWOOD ELECTRIC COMPANY INC Temp Service Inspection Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 6/8/2026 10:35:47 AM Temp meter approved Okay to release meter

 06/08/2026B:GROUND PLUMBINGMARTIN MAGERSPARTIALOn-site Contact is Eli 72020187636/5/2026 7:19:18 AM 6/5/2026 7:19 AM FRONT RANGE SEE CR24-0596 Underground Inspection Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 6/8/2026 12:31:36 PM Deck drain for warm up pool. Marked in green on P111.

 06/08/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALOn-site contact is Eli - 72020187636/5/2026 7:13:50 AM 6/5/2026 7:13 AM FRONT RANGE SEE CR24-0596 Rough-in for Overhead DWV/RD & Water heater flues Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 6/8/2026 12:31:41 PM Storm drains as marked in green on page P111, DWV as marked in pink on page P112 Storm drains in green and vent in pink on page P122. DWV for cabana and locker room as marked in pink on page P500 Mezz level B restrooms DWV as marked in pink on P501. Exhaust and intake for water heater as marked in pink on M111 and M121 on second floor.

 06/10/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALProgram Pool Piping6/9/2026 8:25:58 AM 6/9/2026 8:25 AM SAUNDERS CONSTRUCTION LLC Will have pressure per specs on the pipes for inspection Contact Name: SAUNDERS/ASSOCIATED POOL BUILDERS Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 6/10/2026 12:50:06 PM All pool drain and return approved. Main drain buried past line marked on plans. It was under pressure and engineers third party letter supplied.

 06/11/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALunder slab area d6/10/2026 12:18:34 PM 6/10/2026 12:18 PM LAKEWOOD ELECTRIC COMPANY INC Area D perimeter underslab branch conduits Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 6/11/2026 12:22:29 PM Under slab rough electrical approved Area d - east and north wall

 06/12/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALExterior Framing and Insulation6/10/2026 7:38:33 AM 6/10/2026 7:38 AM Josh Combs Exterior Framing and Insulation Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 6/12/2026 1:59:41 PM PARTIAL- 1) FRAMING FOR SOUTH ENTRANCE AREA B , GRID Line 2 K-H - OK.

 06/15/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request6/12/2026 7:30:24 AM 6/12/2026 7:30 AM FRONT RANGE SEE CR24-0596 FRIDAY 6/12/26 if possible please Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 6/15/2026 11:36:22 AM Roof drains as marked in green on pg 122 and 3/4 water line to hydrant marked in orange on pg 122 Water at B Mezzanine restroom approved as marked in blue on page P501 Bottom drains for to main pool as outlined in pink on page PL310

 06/17/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request6/16/2026 12:54:05 PM 6/16/2026 12:54 PM LAKEWOOD ELECTRIC COMPANY INC Competition pool bonding upper level Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 6/17/2026 3:09:03 PM Pool bonding shallow end and waiting stairs of competition pool approved

 06/18/2026B:ROUGH FRAMEJOE CARBAUGHNOT APPROVEDrough frame for above ceiling top out6/17/2026 6:37:32 AM 6/17/2026 6:37 AM SAUNDERS CONSTRUCTION LLC rough frame for above ceiling top out Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 6/18/2026 11:59:53 AM NOT APPROVED- 1) HEAD OF WALL FRAME & SPRAY FOAM INSULATION AT MEZZANINE AREA (A) HIGHLIGHTED AREA IN BLUE ON PLANS AND PHOTO ATTACHMENT- OK. 2) HEAD OF WALL FRAME & SPRAY FOAM INSULATION AT MEZZANINE AREA (A) HIGHLIGHTED AREA IN PURPLE ON PLANS AND PHOTO ATTACHMENT- NOT APPROVED. NOTE: NEED CLARIFICATION FROM A COLORADO DESIGN PROFESSIONAL FOR TOP OF FRAME WALL FOR USING SLOTTED TRAC VERSES PLAN.

 06/18/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALunderslab north storage6/17/2026 2:07:07 PM 6/17/2026 2:07 PM LAKEWOOD ELECTRIC COMPANY INC Underground rough area north nprth storage room Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 6/18/2026 1:48:38 PM North area storage underground approved Site lighting stubs out of building

 06/18/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALcompetition pool bonding6/16/2026 12:55:10 PM 6/16/2026 12:55 PM LAKEWOOD ELECTRIC COMPANY INC Competition pool bonding lower level Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 719001297 e-Mail: rbinford@lkwd-elec.com 6/18/2026 1:48:43 PM Competition pool bonding approved - foundation

 06/22/2026B:INSULATIONJOE CARBAUGHPARTIALArea D - Roof Insulation6/18/2026 10:03:54 AM 6/18/2026 10:03 AM SAUNDERS CONSTRUCTION LLC Insulation Verification Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 6/22/2026 11:43:52 AM PARTIAL- 1) WEST MEC WELL HIGH ROOF WALL AREA THERMAX INSULATION & Z CLIPS - OK. 2) EAST MEC WELL HIGH ROOF AREA (D) THERMAX INSULATION & Z CLIPS - OK. 3) AREA (D) ROOF RIDGED FOAM INSULATION TWO LAYERS 2" & DENS DECK -OK.

 06/22/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALArea B - Head of Wall6/18/2026 10:02:37 AM 6/18/2026 10:02 AM SAUNDERS CONSTRUCTION LLC Head of Wall inspection to release for drywall top out Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 6/22/2026 11:43:56 AM PARTIAL- 1) HEAD OF WALL FRAMING SECOND FLOOR AREA (B) -OK. 2) ELEVATOR SHAFT (INNER) UL415 1" R1319-301 TYPE SLX SHAFT LINNER, FRAMING & WEB STIFFENERS - OK.

 06/22/2026B:RE ROUGH FRAMEJOE CARBAUGHPARTIALArea A - Head of Wall6/18/2026 10:01:46 AM 6/18/2026 10:01 AM SAUNDERS CONSTRUCTION LLC Reinspection from Joe''s 6/18 inspection on (1) run of W1060 wall. Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 6/22/2026 11:44:01 AM PARTIAL- 1) HEAD OF WALL AREA (A) ITEMS CORRECTED - OK.

 06/23/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALHigh Roof Drains in Areas B & C6/22/2026 9:17:47 AM 6/22/2026 9:17 AM FRONT RANGE SEE CR24-0596 Rough Plumbing for Areas B & C High roof drains ETA Eli - 720-201-8763 Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 6/23/2026 10:25:24 AM Storm drains Area B marked in pink on P122. Storm drains for Area C marked in Pink on P123

 06/26/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALwall rough mezzanine A&B6/23/2026 12:56:59 PM 6/23/2026 12:56 PM LAKEWOOD ELECTRIC COMPANY INC Partial wall rough inspection, mezzanine level areas A & B Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 6/26/2026 11:28:16 AM Electrical wall rough in the mezzanine area A&B approved

 07/01/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request6/30/2026 11:00:05 AM 6/30/2026 11:00 AM FRONT RANGE SEE CR24-0596 inwall insulation inspection for tomorrow. Mezzanine level.  Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 7/1/2026 11:48:13 AM Future grease approved as highlighted in green on P111. Area A An Area B mezzanine walls approved for pipe insulation.

 07/02/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request7/1/2026 12:25:43 PM 7/1/2026 12:25 PM LAKEWOOD ELECTRIC COMPANY INC Underground data conduits, east side of building. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com. 7/2/2026 12:29:30 PM Low volt sleeves along east side approved 2 - 4" pvc 1 - 2" pvc

 07/02/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALRoof Insulation6/30/2026 2:04:47 PM 6/30/2026 2:04 PM Josh Combs Roof Insulation Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 7/2/2026 12:34:21 PM PARTIAL- 1) ROOF INSULATION PART OF THERMAL ENVELOPE GRID LINES 20-22 & H - Z -OK.

 07/09/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALcontact Eli 720-201-87637/8/2026 1:11:41 PM 7/8/2026 1:11 PM FRONT RANGE SEE CR24-0596 locker room Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 7/9/2026 12:34:52 PM Water and gas approved as marked in pink on P111. And P500. All Area A locker Room approved for water test, DWV and Gas. Still needs insulation.

 07/09/2026B:ROUGH MECHANICALMARTIN MAGERSPARTIALAngelo Nieto - 720 - 584 - 68847/8/2026 12:20:53 PM 7/8/2026 12:20 PM ATEK HEATING & AIR CONDITIONING AREA A Level 1 Contact Name: Angelo Nieto Site Address: 222 BRICKYARD CIR Phone: 7205846884 e-Mail: m.crespin@atekhtg.com 7/9/2026 12:34:58 PM All duct work installed and sealed 9-13 H-D as shown on M111.

 07/14/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request7/13/2026 12:39:13 PM 7/13/2026 12:39 PM FRONT RANGE SEE CR24-0596 overhead roof drain inspection area B Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 7/14/2026 11:02:33 AM Roof and secondary drains on 1sr floor, Area B approved.

B:FINAL ELECTRICALVINCE RAPONEeTRAKiT Inspection Request7/15/2026 11:13:02 AM 7/15/2026 11:13 AM SAUNDERS CONSTRUCTION LLC Cabana D Ceiling Electrical Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 7194018401 e-Mail: t.woodard@saundersnorwood.com

 07/16/2026B:INSULATIONJOE CARBAUGHPARTIALRoof Insulation7/15/2026 6:43:58 AM 7/15/2026 6:43 AM Josh Combs This is for roof insulation. Building insulation isn''t listed on the drop down. Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 7/16/2026 2:34:39 PM PARTIAL- 1) ROOF INSULATION AT AREA B - OK. GRID LINES 0.5 THROUGH 2.

 07/16/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request7/15/2026 11:50:59 AM 7/15/2026 11:50 AM LAKEWOOD ELECTRIC COMPANY INC Site electrical underground Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 7/16/2026 2:42:37 PM Electrical trench east side approved to EV chargers Site lighting location 4 - EV chargers Site lighting conduit 2 - 2" pvc security pipes

 07/17/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request7/15/2026 11:13:01 AM 7/15/2026 11:13 AM SAUNDERS CONSTRUCTION LLC Cabana D Ceiling Electrical Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 7194018401 e-Mail: t.woodard@saundersnorwood.com 7/17/2026 6:38:41 AM CBO CHANGED INSPECTION TYPE FROM FINAL TO ROUGH 7/17/2026 10:59:15 AM Rough plumbing with insulation approved in ceiling of cabana D.

 07/17/2026B:GAS PIPE AIR TESTMARTIN MAGERSCANCEL7/17/2026 10:59:20 AM Consult on setting meter. Asked them to contact Black Hills.

 07/17/2026B:ROUGH MECHANICALMARTIN MAGERSPARTIALeTRAKiT Inspection Request7/15/2026 11:13:01 AM 7/15/2026 11:13 AM SAUNDERS CONSTRUCTION LLC Cabana D Ceiling Electrical Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 7194018401 e-Mail: t.woodard@saundersnorwood.com 7/17/2026 6:38:23 AM CBO CHANGED INSPECTION TYPE FROM FINAL TO ROUGH 7/17/2026 10:35:41 AM Inspector JOCA changed the inspection assignment from JOCA to MAM2 7/17/2026 11:26:46 AM Shafts at 11-F and 11D duct and seal approved. Ducts in ceiling of Cabana D approved 7/20/2026 8:07:39 AM Shafts at 11-F and 11D duct and seal approved. Ducts in ceiling of Cabana D approved check if exhaust fan is needed.

 07/17/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request7/16/2026 11:00:45 AM 7/16/2026 11:00 AM LAKEWOOD ELECTRIC COMPANY INC Partial ceiling rough inspection, Cabana D Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd.elec.com 7/17/2026 2:54:14 PM Cabana D - rough electrical approved ( for moc up ) Ex fan in cabana ? Nothing installed at time of inspection print does not show one. Cabana has shower toilet and sink

 07/20/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALunderground electrical7/16/2026 9:43:57 AM 7/16/2026 9:43 AM LAKEWOOD ELECTRIC COMPANY INC Underground site inspection Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 7/20/2026 11:32:33 AM Partial trench past road crossing up to EV charger bank okay to backfill

 07/21/2026B:INSULATIONJOE CARBAUGHPARTIALExterior Wall insulation at Metal Panel7/20/2026 8:05:23 AM 7/20/2026 8:05 AM Josh Combs Exterior Wall insulation at Metal Panel. Building insulation isn''t listed on thedrop down menu Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 7/21/2026 10:32:24 AM PARTIAL- 1) THERMAL MAX RIDGED INSULATION- OK. 2) Z TRACK AT 16INCH O.C. & 4" TAP CONS FOR CONCRETE ATTACHMENT- OK AREA C GRID LINE H THROUGH GRID LINE X EXTERIOR WALL RIDGED INSULATION- OK. 3) AREA D HIGH ROOF GRIDLINE 18 THROUGH 20 - OK .

 07/21/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALLight Pole Conduit7/20/2026 3:09:33 PM 7/20/2026 3:09 PM Josh Combs This inspection is for the conduit installed in the light pole bases. Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 7/21/2026 3:30:58 PM Light pole caissons approved - bonding and pvc sleeves 21 total

 07/22/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALExterior Frame7/21/2026 12:26:45 PM 7/21/2026 12:26 PM Josh Combs Exterior Frame Canopy Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 7/22/2026 11:04:21 AM PARTIAL + 1) RGH FRAME FOR NORTH & SOUTH ENTRANCE LIDS/COVERS - OK.

 07/22/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALRemaining 3 light pole bases7/21/2026 3:42:14 PM 7/21/2026 3:42 PM Josh Combs Inspection for the 3 light pole bases that weren''t ready at time of inspection Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 7/22/2026 1:43:06 PM 3 light pole bases approved west side of building

 07/23/2026B:ROUGH FRAMEJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request7/22/2026 2:08:00 PM 7/22/2026 2:08 PM SAUNDERS CONSTRUCTION LLC Level 1 Area B, Mezz Level Area A, Mezz Level Area B Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 7/23/2026 10:04:01 AM NOT APPROVED- 1) NEED CLARIFICATION FROM A COLORADO DESIGN PROFESSIONAL ON MECHANICAL WALL CONNECTION FOR W1061 GRID LINES A THROUGH F.5. 2) NEED CLARIFICATION FROM A COLORADO DESIGN PROFESSIONAL ON MECHANICAL WALL CONNECTION FOR W1061 GRID LINES Y THROUGH L. 3) RGH FRAMING IN PINK HIGHLIGHTED AREA's PER PIC ATTACHMENT FOR AREA B PLAN A112 - ****OK EXCEPT WALL AT GRID LINES 9- 12.5**** 4) REST OF RGH FRAME FOR HIGHLIGHTED AREAS- OK.

 07/23/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request7/22/2026 2:04:13 PM 7/22/2026 2:04 PM FRONT RANGE SEE CR24-0596 Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 7/23/2026 11:25:18 AM Areas and Area C water supply, recirculater and pool make up as as out lined in orange on P113 and PP112.

 08/04/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request8/3/2026 9:14:12 AM 8/3/2026 9:14 AM LAKEWOOD ELECTRIC COMPANY INC Site lighting branch underground Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 8/4/2026 11:27:14 AM South side of building - EV chargers to west corner approved 2 - 2" pvc security 1 - 1" site lighting

 08/04/2026B:ROUGH FRAMEMARTIN MAGERSPARTIALCeiling frame in locker room7/31/2026 8:14:07 AM 7/31/2026 8:14 AM SAUNDERS CONSTRUCTION LLC Ceiling frame in locker room Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: C.wagner@saundersinc.com 8/4/2026 2:17:04 PM Hall in front of cabanas and cabana B and C ceiling framing approved. Marked in green stripes. 8/4/2026 2:21:00 PM Hall in front of cabanas and cabana B and C ceiling framing approved. Marked in green stripes.

 08/05/2026B:RE ROUGH PLUMBINGMARTIN MAGERSPARTIALRough plumbing inspection areas C&D8/4/2026 11:03:25 AM 8/4/2026 11:03 AM FRONT RANGE SEE CR24-0596 Contact Eli 720-201-8763 Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 8/5/2026 11:21:53 AM Water, DWV, gas, and drains marked in water orange, gas gree, DWV yellow and roof drains in pink on pages P113, P114, P124 and PP154 All area C restrooms approved for water ,DWV, and gas see page P501.

 08/05/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request8/4/2026 11:33:50 AM 8/4/2026 11:33 AM LAKEWOOD ELECTRIC COMPANY INC Partial site underground inspection Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 8/5/2026 2:25:44 PM Under ground trench 1" pvc - Tie in 4 pole lights west side 2 - 2" pvc control pipes

 08/06/2026B:DRYWALLBRETT LONGNECKERCANCELScrew on ramp scaffold area8/5/2026 10:49:00 AM 8/5/2026 10:49 AM SAUNDERS CONSTRUCTION LLC Screw on ramp scaffold area Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: C.wagner@saundersinc.com 8/6/2026 9:24:31 AM Canceled per conversation with Clay. Drywall inspections are only required for fire rated assemblies.

 08/07/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request8/6/2026 4:37:46 PM 8/6/2026 4:37 PM LAKEWOOD ELECTRIC COMPANY INC Underground site lighting branch, west side Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 8/7/2026 2:39:02 PM Site lighting underground electrical trench west side light poles 2 - 2" pvc conduits for security 1 - 1" pvc light poles

 08/07/2026B:ROUGH FRAMEMARTIN MAGERSPARTIALMezz area B elevator shaft8/6/2026 10:27:03 AM 8/6/2026 10:27 AM SAUNDERS CONSTRUCTION LLC Elevator B mezz shaft frame Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 7194018401 e-Mail: T.Woodard@saundersnorwood.com 8/10/2026 7:07:12 AM Inspected Framing on 2 nd floor Elevator B. first floor was inspected 6/22 by JC.

 08/11/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALceiling frame in locker room8/10/2026 12:10:22 PM 8/10/2026 12:10 PM SAUNDERS CONSTRUCTION LLC ceiling frame in locker room Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 8/11/2026 1:53:35 PM PARTIAL- 1) FIRST FLOOR AREA (A) CEILIG FRAMING HIGHLIGHTED IN PINK - OK PG A211

 08/11/2026B:ELECTRICAL TRENCHVINCE RAPONEPARTIALeTRAKiT Inspection Request8/7/2026 12:33:03 PM 8/7/2026 12:33 PM LAKEWOOD ELECTRIC COMPANY INC Underground site lighting branch conduit, west side Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd.elec.com 8/11/2026 2:17:24 PM Underground trench approved West side to light pole on north west corner

 08/11/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALlocker room8/4/2026 11:35:22 AM 8/4/2026 11:35 AM LAKEWOOD ELECTRIC COMPANY INC Partial above ceiling @ locker rooms Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 8/11/2026 2:17:27 PM Rough electrical hard lid - 1st floor locker rooms and cabanas approved Walls approved - locker rooms - 1st floor bathrooms

 08/12/2026B:ROUGH FRAMEMARTIN MAGERSPARTIALRestroom 161 and 162 frame8/11/2026 2:53:00 PM 8/11/2026 2:53 PM SAUNDERS CONSTRUCTION LLC Restroom 161 and 162 frame Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 7194018401 e-Mail: t.woodard@saundersnorwood.com 8/12/2026 2:09:10 PM Area A bathrooms framing approved. See A601 marked in pink.

 08/13/2026B:RE ROUGH MECHANICALBRETT LONGNECKERPARTIALmezzanine hvac plan area a8/12/2026 12:29:55 PM 8/12/2026 12:29 PM ATEK HEATING & AIR CONDITIONING Please contact Angelo Nieto prior to arriving Contact Name: Angelo Nieto Site Address: 222 BRICKYARD CIR Phone: 7205846884 e-Mail: m.crespin@atekhtg.com 8/13/2026 1:34:18 PM Rough mechanical ok as highlighted in blue on town approved M121. Photo Uploaded to permit.

 08/13/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request8/13/2026 6:08:20 AM 8/13/2026 6:08 AM LAKEWOOD ELECTRIC COMPANY INC Partial pool bonding @ competition pool Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 8/13/2026 2:45:56 PM Pool bonding comp pool okay Middle trench okay to back fill

 08/14/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALNatatorium piping inspection8/12/2026 3:25:33 PM 8/12/2026 3:25 PM SAUNDERS CONSTRUCTION LLC Inlet pipes, gutter dropouts, & main drain. Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3038032820 e-Mail: d.wuthrich@saundersinc.com 8/14/2026 2:58:57 PM 8" main drain from pump pit back to program pool connection , program pool already inspected. 10" gutter drop out for program pool, from program pool to surge tank. 8/14/2026 3:02:31 PM 8%34 main drain from pump pit back to program pool connection , program pool already inspected. 10%34 gutter drop out for program pool, from program pool to surge tank. Approved

 07/29/2026B:INSULATIONJOE CARBAUGHPARTIALExterior Wall Insulation7/27/2026 10:50:04 AM 7/27/2026 10:50 AM SAUNDERS CONSTRUCTION LLC Exterior Wall Insulation Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 7209556936 e-Mail: j.orozco@saundersinc.com 7/29/2026 9:28:54 AM PARTIAL- 1) EXTERIOR RIDGED FOAM INSULATION AT NORTH ENTRANCE CANOPY- OK.

 07/20/2026B:ROUGH FRAMEMARTIN MAGERSPARTIALeTRAKiT Inspection Request7/15/2026 11:13:01 AM 7/15/2026 11:13 AM SAUNDERS CONSTRUCTION LLC Cabana D Ceiling Electrical Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 7194018401 e-Mail: t.woodard@saundersnorwood.com 7/17/2026 5:33:05 AM 7/17/2026 5:33 AM SAUNDERS CONSTRUCTION LLC Cabana D ceiling framing before cement board Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: C.wagner@saundersinc.com 7/17/2026 6:38:00 AM CBO CHANGED INSPECTION TYPE FROM FINAL TO ROUGH 7/20/2026 8:51:28 AM Inspector JOCA changed the inspection assignment from JOCA to MAM2 7/20/2026 2:39:46 PM cabana D ceiling approved. No plans on site to mark.

 05/29/2026B:ROUGH FRAMEMARTIN MAGERSPARTIALInsulation and Framing5/27/2026 6:59:51 AM 5/27/2026 6:59 AM Josh Combs Exterior Insulation and Framing Contact Name: Josh Combs Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: j.combs@saundersinc.com 5/29/2026 1:10:30 PM Area C High Roof Wall 2" insulation and Z clips. Marked in green on on A103.

 08/17/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALRough Frame for Area A, B Level 1/Mezz8/14/2026 9:45:36 AM 8/14/2026 9:45 AM SAUNDERS CONSTRUCTION LLC Level #1 area A bathrooms walls Level #1 area B east side wall on court 5,6 Mezzanine area A room 265 and 261 Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 7194018401 e-Mail: t.woodard@saundersnorwood.com 8/17/2026 1:24:26 PM PARTIAL- 1) COLD FORM STEEL WALL RGH FRAME / GRID LINE (P) 2- 9 - OK.

 08/18/2026B:UNGRD PLUMBMARTIN MAGERSPARTIALeTRAKiT Inspection Request8/17/2026 9:27:23 AM 8/17/2026 9:27 AM SAUNDERS CONSTRUCTION LLC Natatorium piping pressure testing Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: d.wuthrich@saundersinc.com 8/18/2026 3:44:57 PM Ground plumbing for Main drain for comp pool, inlet drain for comp pool, Inlet piping for the program pool. Highlighted in Pin on P135. all approved. only overflow drains and inlets by the steps missing for all underground,

 08/21/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request8/20/2026 12:02:02 PM 8/20/2026 12:02 PM FRONT RANGE SEE CR24-0596 please call Eli - 720-201-8763 Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 8/21/2026 10:38:30 AM Roof drains at Pool Mechanical Room and Pool Storage P111, Stair B P122, marked in green Water lines in Pool Mechanical Room except for eye wash station. P500, Marked in green Storage Room water lines marked in pink P111

 08/21/2026B:GAS PIPE AIR TESTMARTIN MAGERSPARTIALWHOLE BLDG STEVIE 30345119718/21/2026 10:38:34 AM All gas lines in A, B, and C roofs. Everything done except line on the pool Mech Roof. Marked on P131, P132, P133 gas in pink Signing gas on permit card, ok to release meter.

 08/21/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALpool Bonding8/20/2026 8:22:34 AM 8/20/2026 8:22 AM LAKEWOOD ELECTRIC COMPANY INC Competition pool bonding Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 8/21/2026 1:47:49 PM Competition pool bonding of pool lights complete

 08/24/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALframe area c8/21/2026 6:08:45 PM 8/21/2026 6:08 PM SAUNDERS CONSTRUCTION LLC frame area c Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 8/24/2026 9:36:36 AM PARTIAL- 1) FRAMING AREA B GRID 13 LINE WALL OK. Page A122 HIGHLIGHTED IN PINK.

 08/26/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request8/25/2026 12:51:24 PM 8/25/2026 12:51 PM SAUNDERS CONSTRUCTION LLC Mezz Area B Bathroom Ceilings, Gridline 13 Wall between Area A and D Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 8/26/2026 10:07:29 AM PARTIAL- 1) FRAMING & CONNECTIONS FOR REQUEST ENGINEER DETAIL FOR SK 1 & 2 - OK.

 08/28/2026B:RE ROUGH MECHANICALJOE CARBAUGHPARTIALArea A Mezz8/27/2026 8:52:47 AM 8/27/2026 8:52 AM ATEK HEATING & AIR CONDITIONING Please contact Angelo Nieto prior to arriving. Contact Name: Angelo Nieto Site Address: 222 BRICKYARD CIR Phone: 7205846884 e-Mail: m.crespin@atekhtg.com 8/28/2026 12:23:16 PM PARTIAL- 1) SEAL & SUPPORT FOR AREA's MARKED IN PINK - OK ON PG 121 NOTE: CONNECTIONS TO RTU's TO BE LOOKED AT FUTURE INSPECTION AT HIGHLIGHTED AREAS ABOVE.

B:BUILDING SEPERATION WALLBRETT LONGNECKEReTRAKiT Inspection Request9/1/2026 6:03:08 AM 9/1/2026 6:03 AM LAKEWOOD ELECTRIC COMPANY INC Partial underfloor rough inspection between competition and program pools. Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com

 08/31/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request8/28/2026 7:11:25 AM 8/28/2026 7:11 AM SAUNDERS CONSTRUCTION LLC South entrance thermax insulation betweeen gridline J/H, from the mezzanine to the highroof. POC - Jason Orozco 720-955-6936 Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: M.ROTH@SAUNDERSINC.COM 9/1/2026 6:56:26 AM PARTIAL- 1) RIDGED FOAM INSULATION & Z TRAC - OK AT SOUTH ENTRANCE, GRID LINES J/H MEZZANINE.

 09/01/2026B:ROUGH PLUMBINGBRETT LONGNECKERPARTIALPool piping for comp pool8/31/2026 9:28:53 AM 8/31/2026 9:28 AM SAUNDERS CONSTRUCTION LLC Pool piping for comp pool Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: C.wagner@saundersinc.com 9/1/2026 11:25:35 AM Pipe and test for competition pool ok as highlighted in blue on town approved plans for PL310.

 09/01/2026B:RE ROUGH MECHANICALJOE CARBAUGHPARTIALPlease call Angelo Nieto prior to arrive8/31/2026 9:18:58 PM 8/31/2026 9:18 PM ATEK HEATING & AIR CONDITIONING AREA A Rough Overhead Mech Inspection Contact Name: Angelo Nieto Site Address: 222 BRICKYARD CIR Phone: 7205846884 e-Mail: m.crespin@atekhtg.com 9/1/2026 1:57:59 PM PARTIAL- 1) SEAL & SUPPORT'S AREA B MEZZANINE- OK.

 09/01/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request8/31/2026 1:11:44 PM 8/31/2026 1:11 PM SAUNDERS CONSTRUCTION LLC Mezzanine Area B Bathroom Ceilings Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 9/1/2026 1:58:01 PM PARTIAL- 1) COLD FORM STEEL FRAMING CEILING ( ONLY) FOR MEN'S & WOMEN'S RESTROOMS - OK.

 09/01/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request9/1/2026 6:08:35 AM 9/1/2026 6:08 AM LAKEWOOD ELECTRIC COMPANY INC Partial underslab rough between competition pool and program pool Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 9/1/2026 2:28:17 PM Pool conduit feeds - 2 - 2-1/2 "pvc 2 - 2-1/4" pvc for security 1" and 3/4" branch

 09/03/2026B:RE ROUGH PLUMBINGMARTIN MAGERSAPPROVEDeTRAKiT Inspection Request9/2/2026 1:50:24 PM 9/2/2026 1:50 PM FRONT RANGE SEE CR24-0596 contact Eli 720-201-8763 Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 9/3/2026 10:50:19 AM Water and gas lines in the water heater and meter rooms approved. Water lines to to the pool mechanical room in the pool area approved Gas lines to RTU on pool mechanical roof approved.

 09/03/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/2/2026 6:32:14 AM 9/2/2026 6:32 AM SAUNDERS CONSTRUCTION LLC Area C Past Gridline 20 Wall Framing Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 9/3/2026 11:34:23 AM PARTIAL- 1) RGH FRAME HOSPITALITY 145 2) RR , 152/ MEN'S RESTROOM 136 SHARED RESTROOM SINKS 137 & WOMENS RESTROOM 135 - OK. NOTE: T.O.W. TRACK TO BE RE- INSPECTED AT RR 151 AT FUTURE INSPECTION.

 09/03/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request9/2/2026 2:17:40 PM 9/2/2026 2:17 PM LAKEWOOD ELECTRIC COMPANY INC Electrical rough-in @ demising wall between gymnasiums C & D Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 9/3/2026 2:43:52 PM Electrical wall rough see page - E112 and E121

 09/04/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/3/2026 12:38:22 PM 9/3/2026 12:38 PM SAUNDERS CONSTRUCTION LLC Screw Inspection, Gridline 13 Wall separating Mezz A from Area D Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 9/4/2026 11:13:48 AM PARTIAL- 1) DRYWALL SCREW INSPECTION AREA A AT GRID LINES 13 H THROUGH A 7" ON EDGE & 8" IN FEILD -OK PER GA216 TABLE 5.

 09/09/2026B:SHOWER PANMARTIN MAGERSPARTIALeTRAKiT Inspection Request9/8/2026 1:45:03 PM 9/8/2026 1:45 PM SAUNDERS CONSTRUCTION LLC Gutter dropout pressure test for the competition pool. Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3038032820 e-Mail: D.Wuthrich@saundersinc.com 9/9/2026 2:50:30 PM Shower Pan in Cabana D approved 9/9/2026 2:50:37 PM gutter drop out on east half of competition pool approved. Marked in yellow on PL 310. All pool ground plumbing complete and approved.

 09/09/2026B:ROUGH PLUMBINGMARTIN MAGERSCANCELeTRAKiT Inspection Request9/8/2026 11:33:01 AM 9/8/2026 11:33 AM SAUNDERS CONSTRUCTION LLC Shower Pan Flood Test Locker Cabanas Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 9/9/2026 2:55:55 PM Inspection called in wrong. Added shower pan inspection.

 08/07/2026B:RE ROUGH MECHANICALMARTIN MAGERSPARTIALArea B Mezz - Mech RI Inspection8/6/2026 10:40:35 AM 8/6/2026 10:40 AM ATEK HEATING & AIR CONDITIONING Contact Name: Angelo Nieto Site Address: 222 BRICKYARD CIR Phone: 7205846884 e-Mail: m.crespin@atekhtg.com 8/10/2026 7:07:10 AM All area B Mezz mechanical ducts complete and approved. 8/10/2026 7:08:38 AM All area B Mezz mechanical ducts complete and approved.

 09/10/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request9/9/2026 1:44:22 PM 9/9/2026 1:44 PM LAKEWOOD ELECTRIC COMPANY INC Electrical service inspection Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 9/10/2026 3:06:32 PM Transformer to userk cabinet approved Userk to MDB approved Okay to release meter

 09/10/2026B:GROUND PLUMBINGMARTIN MAGERSAPPROVEDafternoon preferred9/9/2026 1:26:17 PM 9/9/2026 1:26 PM FRONT RANGE SEE CR24-0596 Contact Name: ELI HULBERT Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: stacey@frontrangeplumbing.com 9/11/2026 7:08:41 AM Deck drain ground plumbing for the comp pool approved. Marked in orange on PL310. All ground plumbing complete and approved.

 09/11/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/9/2026 10:40:13 AM 9/9/2026 10:40 AM SAUNDERS CONSTRUCTION LLC Screw Inspection Gridline 13 Wall Separating Mezzanine Area B from Gym Area C Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 9/11/2026 11:22:46 AM PARTIAL- 1) DRY WALL & SCREW INSPECTION FOR GRID LINE WALL 13 AREA (B) OK.

 09/14/2026B:RE ROUGH FRAMEJOE CARBAUGHPARTIALInsulation Inspection9/10/2026 9:53:11 AM 9/10/2026 9:53 AM SAUNDERS CONSTRUCTION LLC South mezzanine entrance insulation and northwest entrance. POC Jason Orozco 720-955-6936 Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: M.ROTH@SAUNDERSINC.COM 9/14/2026 3:29:43 PM PARTIAL- 1) RIDGED FOAM INSULATION & WALL Z TRACK AT NORTH WEST ENTRY & SOUTH ENTRY - OK.

 09/15/2026B:GROUND PLUMBINGJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/14/2026 12:49:03 PM 9/14/2026 12:49 PM SAUNDERS CONSTRUCTION LLC Underground plumbing for the diving board agitator. Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3038032820 e-Mail: d.wuthrich@saundersinc.com 9/15/2026 9:41:16 AM Inspector CORI changed the inspection assignment from CORI to JOCA 9/15/2026 10:20:51 AM PARTIAL- 1) PLUMBING PRESSER TEST FOR DIVING BOARD AGITATOR - OK.

 09/15/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALcanopy lights9/14/2026 1:03:39 PM 9/14/2026 1:03 PM LAKEWOOD ELECTRIC COMPANY INC Lighting rough inspection at south entry canopy Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 9/15/2026 2:31:02 PM Rough electrical 5 - canopy lights 4 - canopy speakers South entrance canopy

 09/16/2026B:RE ROUGH MECHANICALJOE CARBAUGHPARTIALeTRAKiT Inspection Request9/15/2026 8:54:37 AM 9/15/2026 8:54 AM ATEK HEATING & AIR CONDITIONING Contact Name: Angelo Nieto Site Address: 222 BRICKYARD CIR Phone: 7205846884 e-Mail: m.crespin@atekhtg.com 9/16/2026 9:06:47 AM PARTIAL- DUCT, SIZE, LAYOUT & SEAL & SUPPORT - OK/ PLANS MARKED UP ON M112 AREA B.

 09/17/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request9/16/2026 1:23:46 PM 9/16/2026 1:23 PM LAKEWOOD ELECTRIC COMPANY INC Underslab rough Area A "Leave Out" Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 9/17/2026 2:24:23 PM Underslab power Area A leave out First aid Pool managers office

 09/21/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request9/18/2026 1:52:45 PM 9/18/2026 1:52 PM SAUNDERS CONSTRUCTION LLC Shower Flood Test Locker Room Cabana B and C Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 9/21/2026 1:39:54 PM Cabana B and C shower pans approved. As marked in green on P111.

 09/22/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALmezz ceiling frame and area b level 19/22/2026 6:23:36 AM 9/22/2026 6:23 AM SAUNDERS CONSTRUCTION LLC mezz ceiling frame and area b level 1 Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: c.wagner@saundersinc.com 9/22/2026 2:47:42 PM PARTIAL- 1) NEED CLARIFICATION FROM A COLORADO DESIGN PROFESSIONAL ON CEIING FRAMING (ATTACHMENT) TOO TENSION PLATE FOR ROOF SHEAR DIAPHRAGM/ PAGE A222 AREA B GRID LINES 9- 11 Y - Z. 2) CEILING FRAMING (ONLY) AT AREA B GRID LINES N - X 10 - 10.5 OK (PENDING) RGH MEPS & FIRE. 3) CEILING FRAMING (ONLY) AT ORANGE HIGHLIGHTED AREAS ON PAGE A 221 SUPER-SEEDED by ASI 06 AREA A OK (PENDING)RGH MEPS & FIRE.

 09/23/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALelectrical rough hard lids9/22/2026 11:57:52 AM 9/22/2026 11:57 AM LAKEWOOD ELECTRIC COMPANY INC Various wall/ceiling rough inspections Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 9/23/2026 2:56:16 PM Above ceiling hard lid Mezzanine A bathrooms Spectator soffit - lights Rough electrical walls Rec gym B demising wall camera/receptacle/horn strobe Knee wall okay

 09/24/2026B:ROUGH ELECTRICALVINCE RAPONECANCELeTRAKiT Inspection Request9/23/2026 6:56:25 AM 9/23/2026 6:56 AM LAKEWOOD ELECTRIC COMPANY INC Partial underground site branch Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 9/24/2026 2:25:04 PM Cancel per Rodger

 09/25/2026B:ROUGH MECHANICALJOE CARBAUGHPARTIALArea C lover lever bathrooms9/24/2026 1:37:09 PM 9/24/2026 1:37 PM ATEK HEATING & AIR CONDITIONING Call Angelo Nieto Contact Name: Angelo Nieto Site Address: 222 BRICKYARD CIR Phone: 7205846884 e-Mail: m.crespin@atekhtg.com 9/25/2026 10:32:38 AM PARTIAL- 1) SEAL / SUPPORT & SIZE FOR DUCTS AT AREA (C) PG M113 GRID H- T / 20-21 - OK.

 09/25/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALframe9/23/2026 6:45:15 AM 9/23/2026 6:45 AM SAUNDERS CONSTRUCTION LLC re-inspection on 1 wall on area b mezz as well as other frame. Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 9/25/2026 10:32:41 AM PARTIAL- 1) RE- INSPECTION ON ITEM FROM 9/22/26 AREA(B) PAGE A222 GRID LINE 10-10.5 Z-Y - OK. 2) CEILING & WALL RGH FRAME FOR AREA PG A211 GRID 12.5 - S - Y - OK.

 09/25/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request9/24/2026 12:10:30 PM 9/24/2026 12:10 PM LAKEWOOD ELECTRIC COMPANY INC Undergroind site branch inspection Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 9/25/2026 2:21:14 PM Electrical trench South side parking lot approved 6 light poles

 10/06/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request10/5/2026 6:32:15 AM 10/5/2026 6:32 AM LAKEWOOD ELECTRIC COMPANY INC Competition pool partial bonding inspection Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 10/6/2026 1:24:46 PM Bonding program pool pour 10 okay Starting block bonging and timing system okay Rough electrical multi purpose room A and B divider room

B:ROUGH FRAMEBRETT LONGNECKEReTRAKiT Inspection Request10/7/2026 7:59:38 AM 10/7/2026 7:59 AM SAUNDERS CONSTRUCTION LLC Level 1 Area A and B, Mezzanine Area A and B Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com

 10/07/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALPre-pour inspection for pool drains10/6/2026 10:30:13 AM 10/6/2026 10:30 AM FRONT RANGE SEE CR24-0596 Pre-pour inspection for pool drains IF required POUR IS AM on 10/7 Contact Name: Eli Site Address: 222 BRICKYARD CIR Phone: 7202018763 e-Mail: Stacey@frontrangeplumbing.com 10/7/2026 9:55:37 AM All floor drains in the pool area approved.

 10/07/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALCeiling Frame throughout10/6/2026 3:02:20 PM 10/6/2026 3:02 PM SAUNDERS CONSTRUCTION LLC Area B elevator shaft Area A soffits Area B sounds Area A L1 soffit Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 7202528955 e-Mail: J.combs@saundersinc.com 10/7/2026 11:14:29 AM PARTIAL- 1) HARD LID FRAMING 2nd FLOOR - CHECK IN 201, CHILD WATCH 211, UPPER LOBBY 200 - OK. 2) HARD LID FRAMING 1st FLOOR - GYP BD, CONFERENCE ROOM 118, OFFICES 125, 126 & 127, ELEV. B - OK. NOTE: ****COMPLETE ALL RGH MEP's & CASTLE ROCK FIRE INSPECTIONS ABOVE HARD LID BEFORE CLOSING. ****

 10/07/2026B:WATER RESISTIVE BAJOE CARBAUGHPARTIALTyvek weather barrier inspection10/5/2026 8:29:23 AM 10/5/2026 8:29 AM SAUNDERS CONSTRUCTION LLC POC Jason Orozco Cell - 7209556936 Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: M.ROTH@SAUNDERSINC.COM 10/7/2026 11:14:31 AM PARTIAL- 1) NORTH ENTRANCE ROOF FACE WEATHER BARRIER - OK.

 10/07/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request10/6/2026 12:40:23 PM 10/6/2026 12:40 PM LAKEWOOD ELECTRIC COMPANY INC Misc wall rough inspections Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 10/7/2026 2:01:53 PM Hard lid area B mezz bathrooms Hard lid area B corridor/ party rooms Hard lid area B check in Hard lid area B missed framing Area C gym soffit Area D gym soffit and gym wall to area A

 10/08/2026B:ROUGH MECHANICALMARTIN MAGERSAPPROVEDArea A, Area B, Lower Level B Final Insp10/7/2026 12:16:56 PM 10/7/2026 12:16 PM ATEK HEATING & AIR CONDITIONING Please contact Angelo Nieto when arriving on site 720-584-6884 Contact Name: Angelo Nieto Site Address: 222 BRICKYARD CIR Phone: 7205846884 e-Mail: m.crespin@atekhtg.com 10/8/2026 12:58:11 PM Mezz A and B Ceilings approved to be covered. All rough Mech approved.

 10/09/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request10/8/2026 9:34:45 AM 10/8/2026 9:34 AM SAUNDERS CONSTRUCTION LLC Flood Test Showers: Men''s and Women''s Locker Room 8 total Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 10/9/2026 12:16:56 PM Inspected the 8 shower pans in the men's and women's bathrooms. The 2 outer showers are approved and the 2 inner showers need more slope to 1/4 slope in 12 in, for both the men's and women's shower area.

 10/12/2026B:ROUGH ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request10/6/2026 10:51:29 AM 10/6/2026 10:51 AM LAKEWOOD ELECTRIC COMPANY INC Pool bonding inspection Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 10/12/2026 12:51:42 PM Rough electrical partial inspection approved Areas inspected Area b1 first floor soffit north of b1 gym Pool bonding inspection Competition pool Pour 11 Notes #8 solid bare bonding wire 12 Pool frame bonds 7 grab bar bonds 1 Handicap lift bonded 5 starting blocks bonded

 10/14/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request10/13/2026 11:41:28 AM 10/13/2026 11:41 AM SAUNDERS CONSTRUCTION LLC Area B Level 1 Soffits Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 10/14/2026 12:07:02 PM PARTIAL- 1) SOFFIT RGH FRAMING/ AREA ( B) - OK. NOTE: COMPLETE ALL RGH MEP's & FIRE INSPECTIONS BEFORE GYP.

 10/14/2026B:WATER RESISTIVE BAJOE CARBAUGHPARTIALTyvek waterproofing10/13/2026 7:41:16 AM 10/13/2026 7:41 AM SAUNDERS CONSTRUCTION LLC Tyvek waterproofing, south and east building elevations. POC - Ryan Mcvicker 720-236-6346 Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: M.ROTH@SAUNDERSINC.COM 10/14/2026 8:37:41 AM JOCA changed Inspection Type from B:ROUGH FRAME to B:WATER RESISTIVE BA 10/14/2026 12:07:05 PM PARTIAL- 1) WEATHER BARRIER/ SOUTH ENTRANCE RIM- OK. NOTE: UPPER RIM SOUTH / EAST WEATHER BARRIER TO BE INSPECTED AT FUTURE INSPECTION.

 10/14/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request10/12/2026 12:52:17 PM 10/12/2026 12:52 PM SAUNDERS CONSTRUCTION LLC Area A Locker Room Shower Flood Test, Four Remaining Showers not previously accepted. Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 10/14/2026 2:20:19 PM Corrections made. All shower pans are approved.

 10/14/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request10/13/2026 2:16:11 PM 10/13/2026 2:16 PM LAKEWOOD ELECTRIC COMPANY INC Competition pool bonding Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 10/14/2026 2:32:33 PM Pool bonding pour 12 Diving board / ladder 11 starting blocks

 10/15/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALpool bonding complete10/14/2026 9:23:47 AM 10/14/2026 9:23 AM LAKEWOOD ELECTRIC COMPANY INC Poll bonding inspection Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 10/15/2026 1:08:56 PM Pool bonding complete pour 12

 10/27/2026B:ROUGH PLUMBINGMARTIN MAGERSPARTIALeTRAKiT Inspection Request10/27/2026 6:22:30 AM 10/27/2026 6:22 AM FRONT RANGE SEE CR24-0596 Eli is onsite 720-201-8763 Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 10/27/2026 3:30:14 PM DWV and water for trash roo and laundry marked in orange on P111 All rough plumbing, with the exception of roof drains at the pool area are complete and approved.

 10/28/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALrough electrical10/27/2026 11:41:38 AM 10/27/2026 11:41 AM LAKEWOOD ELECTRIC COMPANY INC Partial wall rough, north side area C Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 10/28/2026 10:28:35 AM Walls and ceiling rough electrical C north locker rooms approved Lower competition hall walls only electrical rough Area A locker room entry approved above ceiling

B:RE ROUGH FRAMEBRETT LONGNECKERCold formed metal framing inspection10/28/2026 11:39:26 AM 10/28/2026 11:39 AM SAUNDERS CONSTRUCTION LLC POC Jason Orozco 7209556936 Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: M.ROTH@SAUNDERSINC.COM

 10/29/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALarea c frame and ceiling frame10/28/2026 11:42:41 AM 10/28/2026 11:42 AM SAUNDERS CONSTRUCTION LLC area c frame and ceiling frame Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: t.woodard@saundersnorwood.com 10/29/2026 2:32:46 PM PARTIAL- 1) HARD LID CEILING FRAMING FOR LEVEL 1 AREA C BATHROOMS - OK.

B:ROUGH FRAMEBRETT LONGNECKERTyvek Inspection10/29/2026 11:32:29 AM 10/29/2026 11:32 AM SAUNDERS CONSTRUCTION LLC Tyvek waterproofing at the upper and lower exterior natatorium elevations. POC Jason O. 720 955 6936 Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: M.ROTH@SAUNDERSINC.COM

 11/04/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALeTRAKiT Inspection Request11/2/2026 2:41:38 PM 11/2/2026 2:41 PM SAUNDERS CONSTRUCTION LLC Tyvek at the south and north of the building. POC Jason Orozco Phone:7209556936 Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 3036999000 e-Mail: M.ROTH@SAUNDERSINC.COM 11/4/2026 11:32:03 AM PARTIAL- 1) WEATHER BARRIER, RIGID FOAM, & TYVEK AT SOUTH EAST OF ENTRANCE & EAST ELEVATION THROUGH GRID LINE 7 - OK.

 11/04/2026B:ROUGH PLUMBINGMARTIN MAGERSAPPROVEDeTRAKiT Inspection Request11/3/2026 2:29:45 PM 11/3/2026 2:29 PM FRONT RANGE SEE CR24-0596 Eli 720-201-8763 roof drain rough Contact Name: FRONT RANGE SEE CR24-0596 Site Address: 222 BRICKYARD CIR Phone: 3034511971 e-Mail: stacey@frontrangeplumbing.com 11/4/2026 3:06:44 PM South storm drains approved. All rough in plumbing complete.

 11/12/2026B:ROUGH FRAMEJOE CARBAUGHPARTIALArea A South Bridge Wall11/10/2026 6:47:56 AM 11/10/2026 6:47 AM SAUNDERS CONSTRUCTION LLC Area A South Bridge Wall Frame Contact Name: SAUNDERS CONSTRUCTION LLC Site Address: 222 BRICKYARD CIR Phone: 6308999796 e-Mail: c.wagner@saundersinc.com 11/12/2026 8:42:43 AM PARTIAL- 1) BRIDGE AREA (A) RGH WALL FRAMING - OK.

 11/12/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request11/10/2026 2:55:51 PM 11/10/2026 2:55 PM LAKEWOOD ELECTRIC COMPANY INC Underground site conduit inspection north side of building along Brick Yard Circle Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 11/12/2026 3:04:13 PM North side of building 2 - 4" pvc fiber conduit - 2 ground boxes 1 - 2" pvc monument sign East side 2 - 1" site lighting and power

 11/20/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALeTRAKiT Inspection Request11/20/2026 6:24:26 AM 11/20/2026 6:24 AM LAKEWOOD ELECTRIC COMPANY INC Partial overhead rough @ locker rooms Contact Name: LAKEWOOD ELECTRIC COMPANY INC Site Address: 222 BRICKYARD CIR Phone: 7196001297 e-Mail: rbinford@lkwd-elec.com 11/20/2026 1:50:22 PM Above ceiling locker rooms