Permit No. 24-2894 Permit Type   COMMERCIAL NEW Site Address   1185 ALOHA ST
CASTLE ROCK, CO 80108
Applied   07/22/2024 Applicant   Kelly Florentino
Approved   03/17/2026 Owner   TBAZ LLC
Issued   03/26/2026 Contractor  
Parent Permit No.   Description   DUNKIN DONUTS
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 03/30/2026B:ELECTRICAL TRENCHSHAWN VALENZUELAPARTIALCHRIS 72078500093/30/2026 12:56:52 PM Electrical trench good 3 locations 1. outside mounted gear to inside electrical room 2. Outside stub for data 3. Parking lot lights and menu board Approved to 5 feet outside of building (see photos)

 04/01/2026B:ELECTRICAL SERVICESHAWN VALENZUELANOT APPROVEDUFER - CHRIS 72078500094/1/2026 9:47:30 AM Ufer inspection not approved Ufer was not inspected by the town of castle rock before encased in concrete. Please upload third-party documents that looked at the ufer installation. Those documents need to be uploaded to building counter and reviewed.

 04/02/2026B:UNGRD PLUMBBRETT LONGNECKERPARTIALgrease interceptor vent4/1/2026 9:44:02 AM 4/1/2026 9:44 AM HAYS CONSTRUCTION COMPANY INC Grease trap vent Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 4/2/2026 9:19:12 AM Vent for grease interceptor into foundation foot print ok. Highlighted in blue on P2.

 04/07/2026B:UNGRD PLUMBBRETT LONGNECKERAPPROVEDBuilding Footprint4/6/2026 10:10:51 AM 4/6/2026 10:10 AM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 4/7/2026 11:11:41 AM All underground plumbing.

 04/09/2026B:ELECTRICAL UNDERGRSHAWN VALENZUELAPARTIALunder slab4/8/2026 2:50:39 PM 4/8/2026 2:50 PM HAYS CONSTRUCTION COMPANY INC For building footprint Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 4/9/2026 10:02:58 AM Underground partial approved Notes. Branch circuits throughout under slab of building ( see photos) 4/9/2026 2:07:09 PM Underground under slab inspection partial approved In slab branch circuit conduits through out concrete slab

 04/16/2026B:ELECTRICAL TRENCHSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request4/15/2026 3:04:26 PM 4/15/2026 3:04 PM HAYS CONSTRUCTION COMPANY INC Underground to 3 light posts and drive through SW of building Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 4/16/2026 3:21:40 PM Electrical trench partial Ok to back fill PVC from building to menu sign/ speaker Ok to back fill PVC from light pole to light pole 5 light poles inspected out of 8 Ok to back fill pvc crossing north east side of parking light stub up for jbox (feeding light poles and directional sign. ****Not ok to back fill light pole caissons details per plans shows 6 feet in grade 1 foot above grade****

 04/17/2026B:ELECTRICAL TRENCHSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request4/16/2026 3:14:59 PM 4/16/2026 3:14 PM HAYS CONSTRUCTION COMPANY INC 5 Light posts. 3pm or close if possible. Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 4/17/2026 1:18:07 PM Electrical trench partial approved All light pole casinos approved to poor 2in pvc communications/ low voltage approved to back fill. *****Still need underground inspection***** for 3 light poles on back end of parking lot. West/ north/ north east Two directional signs still need to be inspected east entrance/ south entrance Lateral coming from cores transformer Light pole pvc conduit connecting 2 light poles under south entrance Marquee sign Southwest corner

 05/07/2026PRE CON INSPECTIONBRETT LONGNECKERAPPROVEDeTRAKiT Inspection Request4/21/2026 2:29:28 PM 4/21/2026 2:29 PM HAYS CONSTRUCTION COMPANY INC Pre con prior to framing building Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 5/7/2026 2:42:01 PM Building Pre-Con conducted at Townhall in Townhall Council Chambers Conference room on 5/7/26 at 8:00 am with Roy Hays and Chris Hays of Hays Construction Company.

 05/22/2026B:INSULATIONJOE CARBAUGHPARTIALROOFING ROY 30359127655/22/2026 11:37:15 AM PARTIAL- 1) TWO LAYERS OF 2.5 RIDGED FOAM INSULATION- OK PER PLAN. NOTE: INSPECTION FOR DOCUMENTATION ONLY AS INSPECTION NOT REQUIRED. MANUFACTURING INSTALLATION INSPECTION DOCUMENTATION DUE BEFORE FINAL.

 05/27/2026B:ROUGH FRAMEJOE CARBAUGHCANCELANSI Blocking inspection5/26/2026 4:09:08 PM 5/26/2026 4:09 PM HAYS CONSTRUCTION COMPANY INC ADA inspection prior to the rough MEP''s. I did not see it on the list. Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ

 05/29/2026B:ELECTRICAL TRENCHSHAWN VALENZUELAPARTIALUnderground Electrical5/28/2026 4:34:43 PM 5/28/2026 4:34 PM HAYS CONSTRUCTION COMPANY INC Trench from building to transformer Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 5/29/2026 2:02:13 PM Electrical trench inspection partial approved Notes. 1 3 1/2 pvc conduit 3 feet deep coming from core transformer heading to east side of building (see photo) At time of trench inspection observed that electrical low-voltage are being installed inside of building. Building is not fully dried in if material being installed is not rated to be exposed to water this material will have to be removed and replaced.

 06/01/2026B:EXTERIOR AND INTERIOR SHEAR AND SHEATHINGJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request5/29/2026 3:25:16 PM 5/29/2026 3:25 PM HAYS CONSTRUCTION COMPANY INC Exterior building plywood Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/1/2026 1:19:46 PM NOT APPROVED 1) EDGE NAILING IS GRATER THAN 4" O.C. AS PER PLAN. / ALL ELEVATIONS. NOTE: PLEASE RE- SCHEDULE INSPECTION WHEN CORRECTIONS HAVE BEEN MADE.

 06/01/2026B:ROUGH ELECTRICALSHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request5/29/2026 3:24:15 PM 5/29/2026 3:24 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/1/2026 2:35:14 PM Rough electrical inspection not approved 1. Building is not dried in at time of inspection building needs to be completely dried in to perform electrical inspection Notes. No rough electrical wall inspection was conducted at this time Please recall rough electrical inspection when building is dried in

 06/03/2026B:EXTERIOR AND INTERIOR SHEAR AND SHEATHINGJOE CARBAUGHAPPROVEDeTRAKiT Inspection Request6/2/2026 3:00:32 PM 6/2/2026 3:00 PM HAYS CONSTRUCTION COMPANY INC For rough in, gas, sewer, and vent Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/3/2026 11:28:08 AM APPROVED. NOTE: HOLD DOWNS TO BE CHECKED AT RGH FRAME.

 06/03/2026B:ROUGH PLUMBINGMARTIN MAGERSNOT APPROVEDeTRAKiT Inspection Request6/2/2026 3:00:32 PM 6/2/2026 3:00 PM HAYS CONSTRUCTION COMPANY INC For rough in, gas, sewer, and vent Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/3/2026 3:06:21 PM Please insulate 3/4 hot lines and recirculating lines. DWV ok Waterlines ok Gas ok to roof. Will be adding piping to RTU

 06/04/2026B:ELECTRICAL TRENCHSHAWN VALENZUELAPARTIALUnderground electrical6/3/2026 1:55:45 PM 6/3/2026 1:55 PM HAYS CONSTRUCTION COMPANY INC Underground conduit for light posts, along north side and over the south entrance roadway Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/4/2026 3:07:59 PM Electrical trench inspection partial approved PVC under parking lot feeding south west pole light by dumpster at 24 inches PVC coming from outside j box on north east side of parking lot stub in landscape at 24 inche Underground still to be inspected 3 pole lights on north end of parking lot 2 directional signs still need inspection Main Dunkin' Donuts sign Please call in trench electrical when ready

 06/05/2026B:ROUGH PLUMBINGJOE CARBAUGHPARTIALPlumbing insulation6/4/2026 7:26:36 PM 6/4/2026 7:26 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/5/2026 11:20:55 AM PARTIAL- RGH PLUMBING (WALLS) ONLY- ITEM CORRECTED FROM 6/3/26 INSPECTION.

 06/08/2026B:UFERSHAWN VALENZUELAAPPROVEDeTRAKiT Inspection Request6/8/2026 6:09:44 AM 6/8/2026 6:09 AM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/8/2026 10:06:00 AM Ufer inspection approved Notes Verify Ufer connection at service inspection Ufer connection required to be accessible

 06/08/2026B:ROUGH ELECTRICALSHAWN VALENZUELAPARTIALeTRAKiT Inspection Request6/5/2026 3:22:45 PM 6/5/2026 3:22 PM HAYS CONSTRUCTION COMPANY INC Did not have an option to choose weather barrier for tyvek on etrakitt Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/8/2026 8:23:31 AM Inspector VIRA changed the inspection assignment from VIRA to SHVA 6/8/2026 10:06:04 AM Rough electrical inspection partial approved Notes. Wall rough only approved Hard lid in bathroom only approved

 06/08/2026B:EXTERIOR AND INTERIOR SHEAR AND SHEATHINGJOE CARBAUGHAPPROVEDWeather barrier6/5/2026 3:22:45 PM 6/5/2026 3:22 PM HAYS CONSTRUCTION COMPANY INC Did not have an option to choose weather barrier for tyvek on etrakitt Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/8/2026 1:26:04 PM APPROVED.

 06/09/2026B:ROUGH MECHANICALCOLBY RIGGINSNOT APPROVEDeTRAKiT Inspection Request6/8/2026 3:01:50 PM 6/8/2026 3:01 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/9/2026 12:27:08 PM Inspector JOCA changed the inspection assignment from JOCA to CORI 6/9/2026 1:16:29 PM 1. Bathroom exhaust fan not installed.

 06/09/2026TRAINING_COLBYCOLBY RIGGINSAPPROVED6/9/2026 1:16:36 PM Approved

 06/09/2026B:ROUGH FRAMEJOE CARBAUGHNOT APPROVEDeTRAKiT Inspection Request6/8/2026 3:01:50 PM 6/8/2026 3:01 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/9/2026 2:23:02 PM NOT APPROVED- COMPLETE RGH PLUMBING TO RTU's. COMPLETE RGH MECHANICAL. COMPLETE RGH ELECTRICAL (CEILING) 1) MISSING FIRE BLOCKING AT LID FOR CONCEALED SPACES / EAST & WEST ELEVATIONS. 2) REST OF FRAME - OK. NOTE: FIRE BLOCKING TO BE SPOT CHECKED AT INSULATION INSPECTION.

 06/12/2026B:ROUGH FRAMECOLBY RIGGINSNOT APPROVEDInsulation Inspection6/11/2026 6:32:16 AM 6/11/2026 6:32 AM HAYS CONSTRUCTION COMPANY INC Need insulation partial at west and north exterior wall by walk in cooler / freezer Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/12/2026 1:38:19 PM 1. Plans call for specific insulation ecotouch pink unfaced. Installed is something different please provide an engineer letter stating that what is installed is sufficient or equal to what was requested. Please upload to the permit. 2. Seal around all windows 3. Please upload ESR/ installer certificate of spray foam insulation. Insulation that is installed for the walls are R 21. Note Will. Spot check spots for fire blocking at the next inspection.

 06/17/2026B:ROUGH FRAMEJOE CARBAUGHAPPROVEDInterior screw inspection of ext walls6/17/2026 6:10:58 AM 6/17/2026 6:10 AM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 6/17/2026 2:55:00 PM APPROVED- NOTE: FINAL FRAME TO BE CALLED WHEN (ABOVE GRID) RGH MEP's ARE COMPLETE.

 07/01/2026B:ELECTRICAL UNDERGRSHAWN VALENZUELAPARTIAL7/1/2026 1:42:11 PM Electrical underground inspection partial approved Verified the rest of 3 light poles ( all light poles underground complete) Monument sign at Southwest corner of property Directional sign at north east side of property Two directional signs still need to be inspected one is south end of entrance other is east end of entrance Two outdoor junction boxes will be installed in landscape. One is by light hole behind dumpster two is north east corner in between lightbulb and directional sign.

 07/08/2026B:ELECTRICAL SERVICESHAWN VALENZUELANOT APPROVEDMeter release and electrical service7/7/2026 9:56:44 PM 7/7/2026 9:56 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 7/8/2026 2:51:53 PM Electrical service inspection not approved 1. Cold water bond incomplete at time of inspection due to plumbing not being completed 2. Utility transformer not installed at time of inspection Recall inspection when corrections are completed Note. Electrical service inspection will not be approved until utility transformer is set and terminated

 07/17/2026B:ROUGH MECHANICALCOLBY RIGGINSAPPROVEDCeiling mechanical7/16/2026 8:28:14 PM 7/16/2026 8:28 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 7/17/2026 1:47:20 PM Approved

 07/17/2026B:ROUGH PLUMBINGMARTIN MAGERSAPPROVEDCeiling plumbing7/16/2026 8:28:14 PM 7/16/2026 8:28 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 7/17/2026 1:51:34 PM Insulation on pipes in ceiling approved.all rough plumbing approved and ok to cover.

 07/17/2026B:ROUGH ELECTRICALVINCE RAPONEPARTIALCeiling electrical7/16/2026 8:28:14 PM 7/16/2026 8:28 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 7/17/2026 2:54:10 PM Above ceiling electrical approved To complete above ceiling rough electrical need the low volt and security wires installed Reschedule rough electrical when ready

 07/24/2026B:ROUGH ELECTRICALSHAWN VALENZUELANOT APPROVEDCeiling rough for low voltage7/24/2026 6:09:46 AM 7/24/2026 6:09 AM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 7/24/2026 12:13:37 PM Rough electrical inspection not approved 1. Low voltage contractor work is still incomplete at this time reschedule inspection when all ceiling work is complete Note Rooftop rough electrical has not been completed at this time Casework walls, rough electrical has not been completed at this time

 07/27/2026B:ROUGH ELECTRICALSHAWN VALENZUELAAPPROVEDWall, ceiling, and roof7/26/2026 1:53:35 PM 7/26/2026 1:53 PM HAYS CONSTRUCTION COMPANY INC As late as possible please Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 7/27/2026 9:07:57 AM Inspector VIRA changed the inspection assignment from VIRA to SHVA 7/27/2026 2:50:42 PM Rough electrical inspection approved Notes Roof top rough Drop ceiling rough Wall rough Millwork rough

 07/27/2026B:FINAL ELECTRICALSHAWN VALENZUELAPARTIALOn temp power7/26/2026 1:53:36 PM 7/26/2026 1:53 PM HAYS CONSTRUCTION COMPANY INC As late as possible please Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 7/27/2026 9:08:23 AM Inspector VIRA changed the inspection assignment from VIRA to SHVA 7/27/2026 3:16:53 PM Final electrical inspection partial approved Corrections before next inspection 1. Install all blank cover plates throughout 2. Menu sign missing and drive-through. Electrical wires not installed in junction box's 3. Fuses is not installed and main exterior disconnect at this time. 4. Service inspection has not passed. Transformer is still not installed. Meter is not installed. Recall final electrical inspection 7/27/2026 3:22:07 PM Final electrical inspection partial approved Corrections before next inspection 1. Install all blank cover plates throughout 2. Menu sign missing and drive-through. Electrical wires not installed in junction box's 3. Fuses is not installed and main exterior disconnect at this time. 4. Service inspection has not passed. Transformer is still not installed. Meter is not installed. Recall final electrical inspection

 07/28/2026B:ELECTRICAL TRENCHVINCE RAPONEAPPROVEDUnderground electrical7/27/2026 9:06:04 PM 7/27/2026 9:06 PM HAYS CONSTRUCTION COMPANY INC Did not have ground electrical on list of inspections Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 7/28/2026 2:07:09 PM Electrical trench complete

 08/12/2026TRAINING_COLBYBRETT LONGNECKERAPPROVED8/12/2026 2:28:05 PM Training Colby for commercial final plumbing inspections.

 08/12/2026B:FINAL PLUMBINGCOLBY RIGGINSNOT APPROVEDeTRAKiT Inspection Request8/11/2026 6:49:40 PM 8/11/2026 6:49 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 8/12/2026 3:19:33 PM 1. Back flow devices need on all beverage machines 2. Trap guards for floor drains 3. Hot water rescuer line needs to be insulated on the boiler 4. Vent termination needs a cap on the roof 5. Paint gas line on the roof Note Restroom sign will be checked at final building

 08/13/2026B:FINAL FRAMEBRETT LONGNECKERAPPROVEDeTRAKiT Inspection Request8/12/2026 1:25:38 PM 8/12/2026 1:25 PM HAYS CONSTRUCTION COMPANY INC TAB has been uploaded Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ

 08/13/2026B:INSULATIONCOLBY RIGGINSAPPROVEDInsulation8/12/2026 1:25:38 PM 8/12/2026 1:25 PM HAYS CONSTRUCTION COMPANY INC TAB has been uploaded Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 8/13/2026 1:02:41 PM Approved

 08/13/2026B:FINAL MECHANICALCOLBY RIGGINSAPPROVEDeTRAKiT Inspection Request8/12/2026 1:25:38 PM 8/12/2026 1:25 PM HAYS CONSTRUCTION COMPANY INC TAB has been uploaded Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 8/13/2026 1:02:43 PM Approved

 08/13/2026L: BACKFLOW SURVEY INSPECTIONERIN SWEENEYAPPROVEDApproved.8/13/2026 1:45:01 PM Field notes attached.

 08/19/2026B:RE FINAL PLUMBINGCOLBY RIGGINSNOT APPROVEDeTRAKiT Inspection Request8/18/2026 3:02:47 PM 8/18/2026 3:02 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 8/19/2026 2:32:12 PM 2. Trap guards for floor drains

 08/27/2026B:RE FINAL PLUMBINGCOLBY RIGGINSAPPROVEDeTRAKiT Inspection Request8/26/2026 10:23:34 PM 8/26/2026 10:23 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 8/27/2026 3:21:01 PM Approved

 09/15/2026U: METER SETGRANT TAYLORMETER INSP FAIL 19/15/2026 11:22:35 AM A $50.00 re-inspection fee will be charged to the building permit. Once corrections have been made, please email your request for a re-inspection to meterset@crgov.com. Please note that we have up to four business days from the initial request to complete the re-inspection. Need to move the fence, wasn't able to get on and turn the valve due to the fence blocking the key. For the mxu mount pex needs to flushed to the wall. Front door needs to be unlocked to do the inspection on meter tree.

 09/22/2026U:METER SET COMMGRANT TAYLORAPPROVED

 09/28/2026B:ELECTRICAL SERVICESHAWN VALENZUELAAPPROVEDMeter release9/25/2026 3:07:50 PM 9/25/2026 3:07 PM HAYS CONSTRUCTION COMPANY INC As late as possible please. Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 9/28/2026 12:49:42 PM Electrical service inspection approved All corrections completed Ok to release meter

 10/05/2026B:FINAL ELECTRICALSHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request10/2/2026 7:03:13 AM 10/2/2026 7:03 AM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 10/5/2026 12:51:16 PM Final electrical inspection not approved 1. No access to inside of building to perform final electrical inspection Recall inspection when someone is available to meet on site

 10/06/2026B:FINAL ELECTRICALSHAWN VALENZUELANOT APPROVEDeTRAKiT Inspection Request10/5/2026 1:14:23 PM 10/5/2026 1:14 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 10/6/2026 1:40:44 PM Final electrical inspection not approved 1. Missing 2 emergency lights for path of egress on both exterior doors, 2018 IBC 1008.3.2 1008.3 Recall inspection when corrections have been completed All other corrections have been completed

 10/07/2026B:FINAL ELECTRICALSHAWN VALENZUELAAPPROVEDeTRAKiT Inspection Request10/6/2026 4:55:25 PM 10/6/2026 4:55 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 10/7/2026 8:14:11 AM Inspector VIRA changed the inspection assignment from VIRA to SHVA 10/7/2026 10:46:14 AM Final electrical inspection approved

 10/08/2026B:REQUEST TCO REVIEWBUILDING COUNTERCANCELeTRAKiT Inspection Request10/8/2026 6:26:18 AM 10/8/2026 6:26 AM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 10/8/2026 8:49:27 AM TCO IS GENERATED FROM FINAL BUILDING INSPECTION

 10/09/2026B:FINAL BUILDINGJON WHITENOT APPROVEDeTRAKiT Inspection Request10/8/2026 1:01:57 PM 10/8/2026 1:01 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 10/8/2026 1:10:59 PM 10/8/2026 1:10 PM HAYS CONSTRUCTION COMPANY INC Contact Name: HAYS CONSTRUCTION COMPANY INC Site Address: 1185 ALOHA ST Phone: 3037945469 e-Mail: S.CAMPBELL@HAYSCO.BIZ 10/9/2026 1:11:35 PM Final Building Not Approved 1- Complete Final Fire and Final Zoning Site Compliance Inspections 2- Label all emergency lighting circuits at panels 3- Complete all striping of parking area, including accessible parking spaces, and accessible paths AT THIS TIME, STOCK AND TRAIN HAS BEEN APPROVED BY THE BUILDING DIVISION AND CASTLE ROCK FIRE AND LIFE SAFETY (PER FIRE MARSHAL). PLEASE SEE NOTES BELOW FOR STOCK AND TRAIN CONDITIONS; - NO PUBLIC ALLOWED INTO STORE PRIOR TO TCO/CO ISSUANCE - NO OVERHEAD WORK IS TO BE PERFORMED DURING HOURS WHERE STORE EMPLOYEES ARE ON SITE - ALL STORE EMPLOYEES SHALL FOLLOW CONTRACTOR SAFETY PROTOCOLS WHILE ON SITE - ALL EGRESS PATH ON INTERIOR AND EXTERIOR OF BUSINESS SHALL BE KEPT CLEAR AT ALL TIMES DURING THE STOCK AND TRAIN PERIOD

 10/09/2026TRAINING_JOEJOE CARBAUGHAPPROVED10/9/2026 1:13:25 PM TRAINING WITH JON WHITE FOR STOCK & TRAIN.

 10/19/2026Z:FNL SITE COMPLIASCOTT SEUBERTAPPROVEDSTRIPING AT END OF DAY 3PM10/19/2026 3:48:21 PM approved

 10/19/2026B:RE FINAL BUILDINGJON WHITEAPPROVED FOR CO10/19/2026 4:05:41 PM Final Building Inspection Approved - All previous corrections have been completed - Building Division has approved to begin the TCO/CO process. As a reminder, The TCO/CO process can take up to 3 days for the reviews from the Town of Castle Rock departments to be completed. Once the process has been completed, the applicant will be notified via email.

 10/21/2026Z:FNL SITE COMPLIASCOTT SEUBERTAPPROVED10/21/2026 7:55:03 AM approved